Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.8 CrAccepted-AOC F 31 INDUSTRIAL AREA PHASE VIII SAS NAGAR MOHALI 160071 | S A S NAGAR | PUNJAB | 160071 | ₹23.8 Cr | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹26.2 CrRejected-AOC | ₹26.2 Cr | L2 | Rejected-AOC NOT BEING LOWEST |
| 3 | L3₹26.9 CrRejected-AOC | ₹26.9 Cr | L3 | Rejected-AOC NOT BEING LOWEST |
Tender Value
₹23 Cr
EMD Value
₹14.8 L
Closing Date
26 Oct 2022, 6:00 pmClosed
Chief Engineer Chennai Zone
Chief Engineer Chennai Zone, Island Grounds, Chennai- 600009
PROVN OF SEWAGE TREATMENT PLANT (STP) AT VARIOUS LOCATIONS AT BANGALORE (PHASE-II)
2022_MES_548791_1
88544/E8
Open Tender
Construction Works
1460 days
Bangalore
ALL AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹3,000
Garrison Engineer (south) Bangalore
₹14.8 L
Yes
25 Nov 2022
30 Aug 2022
28 Oct 2022
30 Aug 2022
26 Oct 2022
4 Oct 2022
30 Aug 2022 - 20 Sept 2022
Amount
SCHEDULE `A' PART - I
SCHEDULE `A' PART - I is not prepriced by MES and prepriced rates indicating 0.00 under column 5 signifies this fact only. Bidders shall insert their rates in Green field under Col-6.
Design and Construction of Pump House cum Toilet and Restroom (11 Nos) with permanent specification having Plinth Area of 25sqm each with RCC framed construction using M-25 (Design Mix) in foundation concrete, footings, plinth beam, Columns, lintel, roof beam, roof slab, PCC Solid Block walling, Internal & External plastering, finishing, Roof Treatment, Anti termite treatment, Rolling Shutter, Pressed steel door frame, flush shutter, glazed skelton door shutter, fly proof box type steel window, PVC door, Wall & floor tiles, sanitary fittings & taps in toilets, plinth protection, including necessary excavation in all types of strata, refilling of earth and disposal of surplus earth within 500m lead, all soil waste pipe up to first manhole, etc., complete at following locations all as specified and as directed :-
Item No.1.00 Contd…
(a) GE (SOUTH) : i) BD Bk - 01 No ii) SOC - 01 No iii) GTOC / GTE - 01 No iv) RMS - 01 No v) DAD / DCA - 01 No vi) SUOE - 01 No --------------- Total - 06 Nos --------------- (b) GE (NORTH) : i) RC Line - 01 No ii) Meanee Line - 01 No iii) FMME & - 01 No Assey Line __________ Total - 03 Nos ------------- (c) GE (CENTRAL) : i) VOC - 01 No ii) Old Domlur - 01 No ------------- Total - 02 Nos ------------- Grand Total - 11 Nos -------------- Total Nos of Pump House = 11 Nos Total Plinth Area (25sqm x 11) = 275 sqm
Designing and constructing of RCC Sumpwell (Lift-well) for average flow of waste upto 50cum/ day with Pump Room (clear height 3mtr) over and above the Sumpwell with M-30 design mix foundation concrete, container walls, bottom slab, top RCC roof slab with CI manhole covers, plastering, water proofing, epoxy paint inside, Superstructure of pump room with PCC Solid Block walling, Internal & External plastering, finishing, RCC roof slab, Roof Treatment, Anti termite treatment, Floor tiling, PVC door, Flooring, etc., all as per zonal specification including necessary excavation in all types of strata, refilling of earth and disposal of surplus earth within 500m lead, all piping connections, valves, MS ladder, suitable window opening with ventilator, BB chambers within 5m of outer wall of tank, etc., including testing for water tightness and hydraulic functioning complete all as shown on drawings, as specified and as directed for the following sizes of Sumpwell & location :-
RCC Sumpwell of size 2.0m dia x 2.6m depth Location : GE (NORTH) - Meanee Lines
RCC Sumpwell of size 2.0m dia x 2.65m depth Location : GE (NORTH) - Meanee Lines
RCC Sumpwell of size 3.0m dia x 3.55m depth Location : GE (SOUTH) - DAD/ DCA
RCC Sumpwell of size 4.0m dia x 3.45m depth Location : GE (SOUTH) - DAD/ DCA
All as per Srl Item No.2 above but RCC Sumpwell (Lift-well) for average flow of waste 51 to 100cum/ day with Pump Room (clear height 3mtr) over and above the Sumpwell of size 4.0m dia x 4.35m depth Location : GE (SOUTH) - Bd Bk
Designing and constructing of RCC Collection Sumpwell with RCC M-30 design mix foundation concrete, container walls, bottom slab, top RCC roof slab with CI manhole covers, plastering, water proofing, epoxy paint inside, etc., all as per zonal specification including necessary excavation in all types of strata, refilling of earth and disposal of surplus earth within 500m lead, all piping connections, valves, MS ladder, ventilation shaft, BB chambers within 5m of outer wall of tank, etc., including testing for water tightness and hydraulic functioning, complete all as specified and as directed for the following sizes of Collection Sumpwell and locations :-
RCC Collection Sumpwell of size 3.0m dia x 3.8m depth Location : GE (North) - RC Lines
RCC Collection Sumpwell of size 4.0m dia x 3.8m depth Location : GE (North) - FMME & Assey Line
RCC Collection Sumpwell of size 5.0m dia x 3.45m depth Location : GE (North) - Meanee Line
RCC Collection Sumpwell of size 4.0m dia x 4.65m depth Location : GE (South) - Bd Bk
RCC Collection Sumpwell of size 2.0m dia x 2.7m depth Location : GE (South) - SOC & SUOE
RCC Collection Sumpwell of size 3.5m dia x 1.85m depth Location : GE (South) - RMS
RCC Collection Sumpwell of size 5.0m dia x 3.7m depth Location : GE (South) - DAD/DCA
RCC Collection Sumpwell of size 3.0m dia x 2.45m depth Location : GE (South) - GTOC/ GTE
RCC Collection Sumpwell of size 3.0m dia x 2.95m depth Location : GE (Central) - VOC
RCC Collection Sumpwell of size 3.0m dia x 2.6m depth Location : GE (Central) - Old Domlur
GENERAL SUMMARY NOTE : Schedule ‘A’ Part II to X are under Ser No. 5.00 to 13.00 are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lumpsum price worked out by the tenderer for SITE CLEARANCE as listed in Schedule ‘A’ Part-II
Lumpsum price worked out by the tenderer for INTERNAL WATER SUPPLY as listed in Schedule ‘A’ Part-III
Lumpsum price worked out by the tenderer for INTERNAL ELECTRIC SUPPLY as listed in Schedule ‘A’ Part-IV
Lumpsum price worked out by the tenderer for ROADS/ FOOT PATH as listed in Schedule ‘A’ Part-V
Lumpsum price worked out by the tenderer for EXTERNAL WATER SUPPLY/ TREATED WATER SUPPLY as listed in Schedule ‘A’ Part-VI
Lumpsum price worked out by the tenderer for EXTERNAL ELECTRIC SUPPLY as listed in Schedule ‘A’ Part-VII
Lumpsum price worked out by the tenderer for SEWAGE DISPOSAL as listed in Schedule ‘A’ Part-VIII
Lumpsum price worked out by the tenderer for AREA DRAINAGE as listed in Schedule ‘A’ Part-IX
Lumpsum price worked out by the tenderer for COMPOUND WALL/ FENCING/ GATE as listed in Schedule ‘A’ Part-X
SCHEDULE `A' PART - XI to XIV are not prepriced by MES and prepriced rates indicating 0.00 under column 5 signifies this fact only. Bidders shall insert their rates in Green field under Col-6.
SCHEDULE 'A' PART XI - STANDBY DG SET
Supply install , testing and commisioning of silent Diesel Engine driven Generating Set of capacity 100 KVA, water/ air cooled type 415 volts, 3 phase 4 wire, acoustic proof comprising of Diesel engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms and foundation, etc., coupled to Engine, installed fixed on base plate with anti vibration pads / friction pads and comprising of the following components :- (A) Engine : Direct couple Diesel Engine electric start, water cooled suitably derated of Matching BHP for driving 100 KVA capacity alternator, four stroke confirming to IS 10001/10002 for continuous running and capable of taking 10 % over load for per hour complete with following accessories:-
(i) Flexible coupling with guards (ii) Lubricating oil filters (iii) Air Cleaner with filters (iv) Antivibrating Pads as reccomended by the Manufacturer. (v) Starter motor with electric start (vi) Battery Charger and connected items. (vii) Battery of 12 Volt and 180 AH with terminals (viii) Standered safety devices (ix) Feul tank for running caapcity DG set for min 08 Hours enclosed within the canopy all as per CPCB with level indicator, fuel inlet, fuel outlet, drain plug, air vent and locking arrangements, etc., incl fuel pipe connection fro fuel tank to DG set and over flow from DG set to fuel tank complete with valves
All as per Item No 15.00 above but of DG set of 82.5 KVA Capcacity [Location : DCA/ DAD]
All as per Item No 15.00 above but of DG set of 62.5 KVA Capcacity [Location : Baird Bk]
All as per Item No 15.00 above but of DG set of 50 KVA Capcacity [Location : RC Line]
All as per Item No 15.00 above but of DG set of 40 KVA Capcacity [Location : Domlur/ FMME/ Assey Line]
All as per Item No 15.00 above but of DG set of 30 KVA Capcacity [Location : RMS/ GTOC/ GTE/ VOC]
All as per Item No 15.00 above but of DG set of 20 KVA Capcacity [Location : SOC]
All as per Item No 15.00 above but of DG set of 10 KVA Capcacity [Location : Dhobighat/ SUE]
Material and labour for earthing using GI strip as earthing lead complete with galavanished steel earth plate electriide 600cmx 600cmx6mm thick burried directly in ground, earth pit lass than 2.25meter deep below ground level with top edge of the plate not less than 1.5m below normal ground level connected to galvanished iron as earthing lead strip 32x6mm (up to 7.5meter length) by means of bolts, nuts, check nuts and washers complete all as shown in electrical plate No 3 and connected to earthing test point including excavation & earthwork in any type of soil, adequate quantity of charcoil dust & salt, PCC pit, CI covers, funnel with watering pipe, wire mesh and testing on complete complete all as specified and as directed (For DG sets).
SCHEDULE 'A' PART XII - SEWAGE TREATMENT PLANTS
Supply, install, test & commissioning of Sewage Treatment Plant based on principle of aerobic attached growth non-clogging randomnly Moving Bed Bio-reactor Technology MBBR) with the DESIGN DATAS mentioned in Particular Specification as Annexure I to Particular Specifications including all civil, pumping and electricals works in accorodance with latest engineering practice complete all as shown on drawings and as specified of following capacity and location :- Make of plant : (a) Ion exchange India Ltd/ (b) Thermax Limited/ (c) Fontus Water Ltd/ (d) M/S Optimus Enviropro Pvt Ltd (e) Hydrotech Pariyabaran.
STP of 420 KLD capacity at DAD [GE (South)]
STP of 400 KLD capacity at Meaneee Line [GE (North)]
STP of 300 KLD capacity at FMME/ Assay Line [GE (North)] & Bd Bk [GE (South)]
STP of 230 KLD capacity at RC Line [GE (North)]
STP of 160 KLD capacity at GTOC [GE (South)] & Domlur [GE (Central)]
STP of 120 KLD capacity at RMS [GE (South)]
STP of 80 KLD capacity at VOC [GE (Central)]
STP of 45 KLD capacity at SOC [GE (South)]
STP of 30 KLD capacity at SUOE [GE (South)]
Supply, installation including lowering, testing and commissioning of submersible pump set capable of delivering discharge of 350 LPM at 25mtr head (3 HP capacity), 3 Phase, 415Volts, 50 Hz, non clog, vertical type, stainless steel impellers and with solid handling, non clog to pass 40mm particles including with guide rail and 1.0 ton capacity chain pulley block -01 No with non rusted steel lifting chain, etc., suitable for the sewage pump, including float switch for automatic operation complete with all accessories all as specified and directed.
Supply, installation including lowering, testing and commissioning of submersible pump set capable of delivering discharge of 225 LPM at 25mtr head (2 HP), 3 Phase, 415Volts, 50 Hz, non clog, vertical type, stainless steel impellers and with solid handling, non clog to pass 40mm particles including with guide rail and 1.0 ton capacity chain pulley block -01 No with non rusted steel lifting chain, etc., suitable for the sewage pump, including float switch for automatic operation complete with all accessories all as specified and directed.
Supply, installation including lowering, testing and commissioning of submersible pump set capable of delivering discharge of 140 LPM at 25mtr head (1 HP), 3 Phase, 415Volts, 50 Hz, non clog, vertical type, stainless steel impellers and with solid handling, non clog to pass 40mm particles including with guide rail and 1.0 ton capacity chain pulley block -01 No with non rusted steel lifting chain, etc., suitable for the sewage pump, including float switch for automatic operation complete with all accessories all as specified and directed.
Supply, installation including lowering, testing and commissioning of submersible pump set capable of delivering discharge of 110 LPM at 25mtr head (1 HP), 3 Phase, 415Volts, 50 Hz, non clog, vertical type, stainless steel impellers and with solid handling, non clog to pass 40mm particles including with guide rail and 1.0 ton capacity chain pulley block -01 No with non rusted steel lifting chain, etc., suitable for the sewage pump, including float switch for automatic operation complete with all accessories all as specified and directed.
SCHEDULE 'A' PART XIII - MISCELLANEOUS ITEMS
SEWAGE DISPOSAL
Supply and fixing SFRC manholes covering of size 710mm dia x 50mm thick (Heavy duty M-25 grade) including frame, etc., complete all as specified and directed
Material & labour for laying of DWCPE Sewage pipeline 150mm dia bore (Grade SN4) of pipe incl sealing of joints, fittings, etc., complete with collars, etc., complete all as specified and directed
Material & labour for laying of DWCPE Sewage pipeline 250mm dia bore (Grade SN4) of pipe incl sealing of joints, fittings, etc., complete with collars, etc., complete all as specified and directed
Cleaning of manholes to remove all sludge/waste materials including solid waste including blocking of existing incoming sewer till the connection of new pipe line, etc., complete all as specified and as directed.
ROADS/ FOOTPATH
Material & labour for providing 150mm thick granular sub base Grading -V as sub base and drainage layer providing coarse grade crushed stone aggregates of Granite/ Trap/Basalt materials, mixing in a mechanical mix plant at OMC, carriage of mixed materials to work site, spreading in uniform layers with motor grade on prepared surface and compacting with vibratory power roller to achieve the 98% protector density, complete as per specification in clause 401 of MORTH V revision complete all as specified and as directed.
Material & labour for 150mm thick (compacted thickness) WMM (in two layers, each layer consisting of 75mm thick ) with course aggregates of grading 53mm to 75 micron mixed in batch mixing plant of suitable capacity, spread, rolled and consolidated to required gradient and camber and the optimum moisture for mixing shall be as per IS-2720 Part 8 complete all as specified and directed by Engineer-in-Charge.
Material & labour for applying tack coat with bitumen emulsion (RS-1, grade confirming to IS:8887 at 5.00kg/ 10Sqm) using emulsion pressure distributor on the prepared bituminous/granular surface cleaned with mechanical broom and complete all as specified and directed by Engineer-in-Charge.
Material & labour preparation of new or previously treated surfaces to recieve thermostatic paint laying of road marking with hot applied Thermoplastic compound with Reflector zing glass beads on Bituminous surface, 2.5mm thick including reflector zing glass beads @ 250gms per sqm area is exclusive of surface applied glass beads as per IRC:35-1997, and the finished surface to be level, uniform and free from steaks and holes all as specified and directed. (Make: Asian Apcolite or equivalent)
TREATED WATER SUPPLY
M & L for cutting the existing hard standing/PCC/WBM road by mechanical means at a depth not less than 80cm and 30cm in width for passing of cable through GI pipe, returning filling in, complete including finishing the surfaces by providing cement concrete, bottom filled with excavated earth and finishing to a uniform smooth surface, removing the surplus soil, etc., complete all as specified and directed. Note : PCC for road cutting will be measured and paid under relevant item of the schedule.
Material and labour for construction of new valve chamber 90x90x90cm inner dimensions, brick masonary in CM 1:4 PCC base in 1:3:6 of 7.5cm thick & plastering 15cm thick in CM 1:4 in inner side/ coping of all chamber fabrication of Iron frame 40x40x6mm size angle iron MS cover 3mm thick with hinges and locking arrangements duly painted including necessary excavation, earth work, etc., all as specified and directed.
Material and labour for construction of new valve chamber 60x60x60cm inner dimensions, brick masonary in CM 1:4 PCC base in 1:3:6 of 7.5cm thick & plastering 15cm thick in CM 1:4 in inner side/ coping of all chamber fabrication of Iron frame 40x40x6mm size angle iron MS cover 3mm thick with hinges and locking arrangements duly painted including necessary excavation, earth work, etc., complete all as specified and directed.
Supply and fixing of full circle metal impact sprinkler, corrosion proof I beam construction for added strength, stainless steel spindle, fulcrum pin and spring well balanced gun metal swing arm to ensure smooth and uniform rotation, brass nozzles with hydro dynamically designed inner profile for precise jet and longer radius of throw 360 degree angle view complete set all as specified and directed.
Supply and fix mono block motor with pump set of 1500LPM capacity complete 3 phase 415Volts 50 Hz of electrically driven, 10mtrs head including suitable size suction and delivery pipe line up to 10m, foot valve, NRV, DOL starter and PVC Copper cable from starter to Pump motor, HP/LP Pressure switch, Ultrasonic level switch for all as per OEM recommendations complete nut bolt, washers, etc., all as specified and as directed. [Location : DAD/DCA]
Supply and fix mono block motor with pump set of 1000LPM capacity complete 3 phase 415Volts 50 Hz of electrically driven, 10mtrs head including suitable size suction and delivery pipe line up to 10m, foot valve, NRV, DOL starter and PVC Copper cable from starter to Pump motor HP/LP Pressure switch, Ultrasonic level switch for automatic operation all as per OEM recommendations complete nut bolt, washers, etc., all as specified and as directed [Location : Baird Bk]
Supply and fix mono block motor with pump set of 900LPM capacity complete 3 phase 415Volts 50 Hz of electrically driven, 10mtrs head including suitable size suction and delivery pipe line up to 10m, foot valve, NRV, DOL starter and PVC Copper cable from starter to Pump motor HP/LP Pressure switch, Ultrasonic level switch for automatic operation all as per OEM recommendations complete nut bolt, washers, etc., all as specified and as directed. [Location : GTOC/Domlur/RCLine/FMME]
Supply and fix mono block motor with pump set of 500LPM capacity complete 3 phase 415Volts 50 Hz of electrically driven, 10mtrs head including suitable size suction and delivery pipe line up to 10m, foot valve, NRV, DOL starter and PVC Copper cable from starter to Pump motor HP/LP Pressure switch, Ultrasonic level switch for automatic operation all as per OEM recommendations complete nut bolt, washers, etc., all as specified and as directed. [Location : Meanee line/VOC/RMS]
Supply and fix mono block motor with pump set of 300LPM capacity complete 3 phase 415Volts 50 Hz of electrically driven, 10mtrs head including suitable size suction and delivery pipe line up to 10m, foot valve, NRV, DOL starter and PVC Copper cable from starter to Pump motor HP/ LP Pressure switch, Ultrasonic level switch for automatic operation all as per OEM recommendations complete nut bolt, washers, etc., all as specified and as directed. [Location : SOC/ Dhobi ghat]
EXTERNAL ELECTRIC SUPPLY
Supply, Installation, testing and commissioning of LT feeder pillar box, factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz AC supply, vermin proof, front and rear opening, hinged doors, etc., powder coated as per seven tank process and IP-65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral tinned copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works complete with copper strips of suitable size for connecting MCCB complete andcomprising of the following:- Location : Main LT panel for Meanee line
Incoming : (a) MCCB 160A FP 25KA Thermal magentic release -01 No Outgoing : (b) MCCB TP 125 Amps 25 KA Thermal magentic release - 1 No (For STP) (c) MCB TPN 32 Amps - 2 Nos (For sewage pumping station1 & 2 starter panel) (d) MCB TPN 63 Amps - 03 Nos (e) Star delta starter for 10 Hp pumps- 02 Nos (f) MCB SPN 20 Amps - 3 Nos (for Building & st Light) (g) Street light timer (Astro type) with TP contactor 16A - 01 set (h) Digital Volt meter 0 - 415 Volts (j) Digital Amp meter 0 - 200 Amps with CT (k) LED phase indicating lamps (R,Y &B) (l) Three Phase Capacitor Bank fixed 15 KVAR (MPP Type) with capacitor duty contactor - 01 No.
Supply, Installation, testing and commissioning of LT feeder pillar box, (Starter panel for Sewage Puming Station 1 & 2 at Meanee line) factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz AC supply, vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP-65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works, etc., complete with copper strips of suitable size for connecting MCCB complete and comprising of the following:- Incoming : (a) MCB TPN 32A - 01 No Outgoing (b) MCB 32A with DOL Starter for 1 HP Pump - 03 Nos (2W +1S) (c) The panel shall comprise ultrosonic level sensor for each pump motor and controlled by PLC (d) Measuring instruments like Multifunction meter with CTs and Indication Lamps.
Supply, Installation, testing and commissioning of LT feeder pillar box, (Main LT panel for DAD/ DCA Line) factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz A C supply, vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP 65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works, etc., complete with copper strips of suitable size for connecting MCCB complete and comprising of the following:-
Incoming : (a) MCCB 160A FP 25KA Thermal magentic release - 01 No Outgoing (b) MCCB TP 125 Amps 25 KA Thermal magentic release - 1 No ( For STP) (c) MCB TPN 32 Amps - 2 Nos (For sewage pumping station1 & 2 starter panel) (d) MCB TPN 63 Amps - 03 Nos (e) Star delta starter for 10 Hp pumps - 02 Nos (f) MCB SPN 20 Amps - 3 Nos ( for Building & st Light) (g) Street light timer (Astro type) with SP contactor 16A - 01 set, (h) Digital Volt meter 0 - 415 Volts (j) Digital Amp meter 0 - 200 Amps with CT (k) LED phase indicating lamps (R,Y &B) (l) Three Phase Capacitor Bank fixed 20KVAR (MPP Type) with capacitor duty contactor - 01 No.
Supply, Installation, testing and commissioning of LT feeder pillar box, (Starter panel for sewage puming station 1 & 2 at DAD/ DCA) factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz AC supply, vermin proof, front and rear opening, hinged doors, etc., powder coated as per seven tank process and IP 65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works, etc., complete with copper strips of suitable size for connecting MCCB and comprising of the following :- Incoming : (a) MCB TPN 32A - 01 No Outgoing : (b) MCB 32A with DOL Starter for 3 HP Pump - 03 Nos (2W +1S) (c) The panel shall comprise ultrosonic level sensor for each pump motor and controlled by PLC (d) Measuring instruments like Multifunction meter with CTs' and Indication Lamps.
Supply, Installation, testing and commissioning of LT feeder pillar box, (MAIN LT PANEL FOR Bd BRK) factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz AC supply, vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP 65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works, etc., complete with copper strips of suitable size for connecting MCCB and comprising of the following :-
Incoming : (a) MCCB 160A FP 25KA Thermal magentic release -01 No Outgoing (b) MCCB TP 125 Amps 25 KA Thermal magentic release - 1 No (For STP) (c) MCB TPN 32 Amps - 2 Nos (For sewage pumping station1 & 2 starter panel) (d) MCB TPN 63 Amps - 03 Nos (e) Star delta starter for 10 Hp pumps- 02 Nos (f) MCB SPN 20 Amps - 3 Nos ( for Building & st Light) (g) Street light timer (Astro type) with SP contactor 16A - 01 set (h) Digital Volt meter 0 - 415 Volts (j) Digital Amp meter 0 - 200 Amps with CT (k) LED phase indicating lamps (R,Y & B) (l) Three Phase Capacitor Bank fixed 10 KVAR (MPP Type) with capacitor duty contactor - 01 No.
Supply, Installation, testing and commissioning of LT feeder pillar box, (Starter panel for sewage puming station 1 Bd Brk) factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz A C supply, vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP 65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works, etc., complete with copper strips of suitable size for connecting MCCB and comprising of the following:- Incoming (a) MCB TPN 32A - 01 No Outgoing (b) MCB 32A with DOL Starter for 3 HP Pump - 03 Nos ( 2W +1S) (c) The panel shall comprise ultrosonic level sensor for each pump motor and controlled by PLC (d) Measuring instruments like Multifunction meter with CTs and Indication Lamps.
Supply, Installation, testing and commissioning of LT feeder pillar box, (Main LT panel for SOC/ VOC/ RMS/ (GTOC/ GTE)/ Domlur/ Dhoboghat) factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz AC supply, vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP-65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works, etc., with copper strips of suitable size for connecting MCCB complete and comprising of the following:-
Incoming : (a) 100A MCCB FP 16 KA Thermal magnetic type - 01 No Outgoing (b) MCCB TP 63Amps 16 KA Thermal magnetic type - 1 No ( For STP) (c) MCB TPN 63 Amps - 02 Nos (d) DOL Starter for 5 HP pump - 02 Nos (e) MCB SPN 20 Amps - 3 Nos (for Building & st Light) (d) Street light timer with SP contactor 16A - 1 No (e) Digital Volt meter 0 - 415 Volts (f) Digital Amp meter 0 - 200 Amps with CT (g) LED phase indicating lamps (h) Three Phase Capacitor Bank fixed 10 KVAR (MPP Type) with capacitor duty contactor - 01 No
Supply, Installation, testing and commissioning of LT feeder pillar box, (Main LT panel for RC line/ FMME) factory made, CPRI approved, outdoor type floor mounting with channel iron pedestal frame made out of 3.0mm thick CRCA sheet steel for outer sheet and 2.0mm for inner sheet, compartmental type, dust proof, free standing, suitable for working on 440Volts 3 phase 50 Hz AC supply, vermin proof, front and rear opening, hinged doors etc powder coated as per seven tank process and IP-65 protection, cable alley, cable entry hole at the bottom, earth strip, 3 phase and neutral copper bus bar suitable capacity with non adhesive color coded insulation sleeves mounted on insulators, drilled holes on bus bar strips for tapping including nuts bolts and washers, PCC works, etc., with copper strips of suitable size for connecting MCCB complete and comprising of the following :-
Incoming (a) 160A MCCB FP 16 KA - 01 No Outgoing (b) MCCB TP 125Amps 16 KA, thermal magnetic type -1No (For STP) (c) MCB TPN 63 Amps with DOL Starter of capacity 5 HP pumps - 02 Nos (For Treated water) (d) MCB SPN 20 Amps - 1 No (For Building & Street Light) (e) Street light timer (Astro type) with SP contactor 16A - 1 Set (f) Digital Volt meter 0 - 415 Volts (g) Digital Amp meter 0 - 200 Amps with CT (g) LED phase indicating lamps R,Y & B (h) Three Phase Capacitor Bank fixed 5 KVAR (MPP Type) with capacitor duty contactor - 01 No
Material and labour for explusion fuse unit 11 KV drop out upto 25Amps complete all specified and as directed.
Material & Labour for solid copper conductor of 8mm dia bent to shape fixing at HT 2 pole structure and in HT as jumper connection with insulating sleeves, etc., complete all as directed.
Material & Labour for Wiring with three core sheathed of 1.5Sqmm PVC insulated FRLS Cable with multistranded copper conductor, 1100Volts grade, confirming to IS:694, including drawn through the octagonal pole and connection to light fiting and MCBs all as specified and as directed. Note: Two runs of 1.50sqmm multistranded cable shall be considered as one unit length.
Supply and fix junction box made out of one piece mould SMC base SMC door size 250x200x100mm with hinged cover suitable for and including 2 terminal connector block for incoming and outgoing cable, Fuse cut out 2 Amps - 01 No fixed on steel/ RCC poles with suitable clamps made out 25mm x 3mm flat iron, bolts, nuts and washers, etc., complete all as specified and as directed.
Supply and fix Cable Route indicator showing HT Cable and route of the cable with arrow made of CI in suitable elipitcal shape and fix on angle iron duly embedded in PCC block in ground complete all as specified and directedcomplete all as specified and as directed.
SCHEDULE 'A' PART XV (MANNING AND OPERATION OF STP DURING DEFECTS LIABILITY PERIOD)
(xvi) Suitable disposal for output of sludge retrieved from sludge handling unit shall be carried out at a location as directed by Engineer-in-Charge. (xvii) Maintaining of log books for records of operation of plants including cost of stationary. (xviii) Back wash of dual media filter and activate carbon filter weekly. (xix) Screening of inlet & outlet mesh box of MBBR reactor weekly. (xx) Washing of tube media with low pressure jut of raw water required. (xxi) Draining of burnout lubricant oil and refilling of appropriate lubricant oil in air blower after 2000-2500 hrs of operation including cost of lubricant (xxii) Maintenacne and operation of filter press and collecting output neatly. (xxiii) Operation of standby DG set st and when required. (xxiv) Operating clear water pumps regularly and in consultation with Engr-in-charge.
Manning and operation, Routine maintenance of Sewage Treatment Plants along with DG Sets and including all E/M inventory pertains to 11 Nos of STPs to be supplied, installed and commissioned in the contract to be carried out round the clock including all Sundays and public holidays by employing the man power and shift timings as mentioned below for operation of plant daily including supply of water treatment chemicals (i.e. Bio septic clean powder, sodium Hypochloride, Dap enzime, Calcium Hypo Chloride and Bleaching powder, etc.,), Activated Carbon Filter media (ACF). Activated Sand filter media (ASF), MBBR fluidized bio-media, Bacteria culture and other consumables required for smooth running of STP Plant and provision of reliever for weekly off and carrying out daily, weekly, monthly, quarterly & half yearly maintenance etc., complete for during Defects Liability period (i.e. after physical completion of Phase I) all as specified and as directed.
All as per Serial Item No 59.00 here-in-above, but for balance period of first year during defects liability period and second year during defects liability period.
All as per Serial Item No 59.00 here-in-above, but for balance period of second year during defects liability period.
Chauhan Associates
C R R CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
Download all tender documents and submit your bid