Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹42.3 L+₹2.3 L (5.75%)Rejected-Finance OLD JAIL ROAD NEAR JILA GARDEN RAJKOT 360001 | RAJKOT | GUJARAT | 360001 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹44 L+₹4 L (10.0%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹44.4 L+₹4.4 L (11.0%)Rejected-Finance 107 265 BRAHAMA NAGAR KANPUR UP 208012 | KANPUR NAGAR | UTTAR PRADESH | 208012 | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹45.7 L+₹5.7 L (14.3%)Rejected-Finance CHENNAI | CHENNAI | TAMIL NADU | 600001 | L5 | Rejected-Finance Being L5 |
Tender Value
₹48.6 L
EMD Value
₹97,267
Closing Date
7 Dec 2023, 4:00 pmClosed
Asst.Gen.Manager(E-E)
O/o AGM(E-E), Airports Authority of India, Coimbatore International Airport, Coimbatore-641014.
Replacement old 1500 KVA Transformer of the substation with Dry type Transformer at Coimbatore international Airport
2023_AAI_174377_1
AAI/CBE/ENGG(E)/1600 KVA TRANSFORMER/23-24
Open Tender
Electrical Works
Works
120 days
Coimbatore International Airport
Please refer Tender documents.
24 documents required · 24 mandatory
₹1,180
₹97,267
1 Apr 2024
16 Nov 2023
8 Dec 2023
16 Nov 2023
7 Dec 2023
16 Nov 2023
16 Nov 2023 - 23 Nov 2023
Amount
SITC of Cast Resin Dry Type 1600 KVA , 11/ 0.433 KV, 3 Phase, 50 Hz, Dyn 11 vector group, copper wound, class F insulation associated with winding temperature indicator/controller actuated by means of resistance temperature detector embedded in LV windings, indoor type Transformer with % impedance as per ECBC norms, tapping for on-load operation on HV side in steps of.+5% to -7.5% at the step of 2.5% with RTCC panel including control wiring, having cable end boxes on HV side suitable for 3x 185 sqmm XLPE cable of 11 KV grade and 2500 amps. C&S make TPN AL sandwich bus trunking arrangement on LV side with neutral brought out separately including termination of already laid copper conductor multicore control cable from transformer to HT breaker for safety tripping, connection of earthing strips, suitably mounted on M.S. Channel i/c supplying and grouting of suitable M.S. Channel with all accessories and confirming to IS 11171:1985 & as per specification attached complete in all respects as required at site.
Carrying out necessary modifications works on C&S make TPN AL 2500 Amps, sandwich bus trunking arrangement for termination of the existing sandwich bus trunking on LV side of new transformer including supply of all required accessories,additional copper strips of size 50x5 mm, removal of existing shutter of room, making brick work, plastering, paiting, providing glass door with alumium frames etc making the room dust proof as per site requirement complete as required. It is recommended that contractors visit the site to familiarize themselves with the location and the necessary work that needs to be undertaken there.
Disconnection of the BBT, HT cable and control cables, earthing strips from the existing transformer, removing the transformer from the transformer room and shifting the location as specified by the Engineer-in-Charge including wrapping the transformer with suitable material for protection from rain, dust , sun light etc complete as required.
DOSHI ELECTRIC ENGG. CO.
ABM ELECTRICALS
Awasthi Electric Works
vk sam engineering
Balaji Engineering
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .