Loading…
Loading…
Tender Value
₹1.1 Cr
EMD Value
₹2.2 L
Closing Date
7 Sept 2026, 5:00 pm
AMIT
Municipal Council Jind
UPGRADATION OF PARKING AREA in transferred HUDA sectors and Housing Board ,MC Jind
2026_HRY_543903_1
2026E93D9E06 1AE6 4B57 837E AC1178B0F0ED300ULB
Open Tender
Civil Works
Works
270 days
Jind
2 documents required · 2 mandatory
₹15,000
₹2.2 L
Yes
27 Aug 2026
27 Aug 2026
8 Sept 2026
27 Aug 2026
7 Sept 2026
27 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | (DSR Item 8.14.16) Supplying, Installation, Testing and Commissioning of Street light LED fixture, powder coated
pressure die cast aluminium body with built in or separate driver as per the requirement with Driver
efficiency )85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to
50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency )85%,THD ( 10%
as per IEC 61000-3-2, P. F.=0.95, IP-66,IK-10, CRI )70, under voltage and over voltage protection,
EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road
and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver and electrical
circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life
ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As
per ANSI Bin), SDCM(Standard Deviation Color Matching) (5, Maximum power consumption should
not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor
single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen
efficacy )135 lm/Watt output . LM79 and LM80 Test report and all testing required for LED fixtures
as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as
per requirement. (Thermal management: heat sink of aluminium housing such that LED junction
temperature shall not rise above 90°C). | 76 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.81 MB
BOQ_623412.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].