Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAdmitted-Finance | ₹1.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.2 Cr+₹1.8 L (1.53%)Admitted-Finance | ₹1.2 Cr+₹1.8 L (1.53%) | L2 | Admitted-Finance |
| 3 | L3₹1.2 Cr+₹5.2 L (4.38%)Admitted-Finance | ₹1.2 Cr+₹5.2 L (4.38%) | L3 | Admitted-Finance |
| 4 | L4₹1.3 Cr+₹13.4 L (11.4%)Admitted-Finance | ₹1.3 Cr+₹13.4 L (11.4%) | L4 | Admitted-Finance |
| 5 | Not Admitted-Fee/PreQual/Technical 111 90 VIJAY PATH MANSAROVAR JAIPUR RAJASTHAN 302020 | JAIPUR | RAJASTHAN | 302020 | - | - | Not Admitted-Fee/PreQual/Technical No EMD or Fee received |
| Sl No | Description | Qty | Unit | BABEL BROTHERS L2 | M/S Anil Brothers L3 | Shanti Enterprises L4 | GANPATI COMMUNICATION SERVICES L1 |
|---|---|---|---|---|---|---|---|
| 1.00Part-II {Providing HT/LT Electrification work in remaining area in main mandi yard Balicha under KUMS Udaipur(Grain)} | |||||||
| 1.10Supply installation testing & Commissioning of Copper wound distribution Transformer of following rating and % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled losses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core design including standard accessories like conservator with prismatic oil level gauge , silica gel breather, Bucholz relay, pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box, LT cable box with Busbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ), temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device, Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test in OEM's own lab shall be witnessed by Department engineer Physically. | |||||||
| 1.20Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge. | |||||||
| 1.30 | 315 KV | 2 | Each | 2,00,000 ₹4,00,000 Lowest | 7,60,000 ₹15,20,000 | 9,25,000 ₹18,50,000 | 7,80,000 ₹15,60,000 |
Tender Value
₹1.6 Cr
EMD Value
₹3.3 L
Closing Date
19 Jan 2023, 6:00 pmClosed
Executive Engineer
RSAMB Electric Division Jaipur
Package 03/2022-23 remaining electric work of HT/LT and Street lighting in new mandi yard Balicha under KUMS (Grain) Udaipur
2023_RSAMB_314531_1
RSAMB/Elec/NIT-12/2022-23
Open Tender
Electrical Works
Percentage
240 days
Jaipur
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,000
EE RSAMB Electric Division Jaipur
₹3.3 L
Yes
27 Jan 2023
12 Jan 2023
23 Jan 2023
12 Jan 2023
19 Jan 2023
13 Jan 2023
Amount
Part-II {Providing HT/LT Electrification work in remaining area in main mandi yard Balicha under KUMS Udaipur(Grain)}
Supply installation testing & Commissioning of Copper wound distribution Transformer of following rating and % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled losses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core design including standard accessories like conservator with prismatic oil level gauge , silica gel breather, Bucholz relay, pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box, LT cable box with Busbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ), temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device, Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test in OEM's own lab shall be witnessed by Department engineer Physically.
Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge.
Bidder Name
Amount
BABEL BROTHERS(GSTN-08AABFB1105A1ZI)
M/S Anil Brothers(GSTN-08AHUPG5285A1Z6)
Shanti Enterprises(GSTN-08ABHPA4131G1Z6)
GANPATI COMMUNICATION SERVICES(GSTN-08AMAPG7177L1ZP)
M/S Anil Brothers
GANPATI COMMUNICATION SERVICES
Shanti Enterprises
M/S Anil Brothers
Shanti Enterprises
BABEL BROTHERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.17 MB
Tendernotice_2.pdf
PDF • 0.48 MB
Tendernotice_3.pdf
PDF • 0.34 MB
Tendernotice_4.pdf
PDF • 0.12 MB
BOQ_557305.xls
BOQ • 0.44 MB
Bid-Doc-Balicha.pdf
Tender Documents • 1.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .