Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.9 LAccepted-AOC | ₹28.9 L | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹29.7 L+₹84,832.50 (2.94%)Rejected-Finance | ₹29.7 L+₹84,832.50 (2.94%) | L2 | Rejected-Finance Higher Bidder |
| 3 | Rejected-Technical FLAT NO 7 MHAMBRE BLDG DR FRANCISCO LUIS GOMES ROAD VASCO DA GAMA GOA 403 802 | SOUTH GOA | GOA | 403802 | - | - | Rejected-Technical Not recommended since non enisted in b(ii) |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not recommended since non enisted in b(ii) |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not recommended since non enisted in b(ii) |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
14 Nov 2022, 6:00 pmClosed
SH A K SINGH SE CWE NAVY VASCO
CWE NAVY VASCO VASCO DA GAMA GOA 403802
SPECIAL REPAIRS REPLACEMENT OF HT OH LINE INTO HT UG CABLE AND CONNECTED ITEMS OF GSEB 11 KV DOUBLE FEEDER LINE AT NOFRA
2022_MES_558219_1
85619/E8
Open Tender
Civil Works
Item Rate
180 days
CWE NAVY VASCO
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
Yes
GE GOMANTAK
₹58,000
Yes
17 Nov 2022
17 Oct 2022
16 Nov 2022
17 Oct 2022
14 Nov 2022
31 Oct 2022
Amount
Excavation in trenches not exceeding 1.5 m width and not exc 1.5m in depth getting out in hard/dense soil complete all as specified and as directed.
Excavation in trenches not exceeding 1.5 m width and not exc 1.5m in depth getting out in soft disintegrated rock complete all as specified and as directed.
M&L for Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in thick using excavated hard/dense soil complete all as specified and as directed.
M&L for Removal of surplus soil to a distance not exceeding 50 m and depositing where directed complete all as specified and as directed.
M&L for fixing GI tubing 80mm dia light grade use for the protection of cable complete all as specified and as directed.
M&L for Double Wall Corrugated (DWC) High density polyethylene pipes (HDPE) of 90mm dia laid in trenches for cable protection complete all as specified and as directed.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm complete all as specified and as directed.
M & L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm including dismantling old burnt cable joint termination heat shrink type complete all as specified and as directed.
M & L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 120 sqmm including dismantling old burnt cable joint termination complete all as specified and as directed.
S&F PCC cable route marker of size 900x100x50mm, embossed with 'HT UG cable 11kV' and excavation of 40cm depth, grouted in and including PCC (1:2:4) type B-2 (using 20mm graded stone aggregate)complete all as specified and as directed.
S & F prestressed concrete pole 11 mtr long, 152mm x152mm at top and 152 mm x 260mm at bottom class 9 including painting upto 1.5 mtr from the ground level in 30cm wide synthetic enamelled paint strip complete all as specified and as directed.
M & L for Heavy gang operated triple pole mechanically operated air break on load disconnecting switch each pole consist of galvanised iron base HT 11KV with porcelain insulators per phase non ferrous knife and spring loaded contact GI pipe of adequate length for operation from ground level and operating handle complete in both OFF and ON position capacity 11 KV 200 Amps including taking down old one complete all as specified and as directed.
M & L for 11 KV Heavy Drop Out Fuse complete in each pole consist of galvanised iron base HT 11KV with porcelain insulators including taking down old one complete all as specified and as directed.
M&L for HT 11 KV Disc type insulator with hardware, single disc assembly, porcelain insulators, vitreous145mm high and 255 mm dia and socket type, including taking down old unsv complete all as specified and as directed.
S&F for Pin type porcelain insulators including one galvanised mild steel spindle two GI washers and one GI iron nut 150mm height, 150mm dia for 11 KV grade including dismantling the old U/S insulator complete all as specified and as directed.
S & F lightening arrestor HT 11000 KV pole mounting with porcelain insulators complete with all fittings transmission class nominal discharge current upto 65 KA including removing the defective one complete all as specified and as directed.
Supply and fixing cross arms for two pole structure with GOD, LA as ISMC-75x6mm, MS flat 50x6mm, bracing supports clamps and back plats fabricated for structural steel sections including suitable size of nut, bolts & washers, welding being cold or hot drilling holes for bolts of suitable shape or size as indicated or directed and inclusive of one primer coat, one under coat and finishing coat of paint complete all as specified and as directed.
M/L for earthing complete with steel earth plate eletrode 60cm x 60cm x6mm thick buried dirctly in ground vertically (earth pit not less than 2.25 mtr below ground level) with top edge of plat not less than 1.5 mtr below ground level connected to GI earth strip 25x4mm by means of bolts. nuts,check nuts and washers etc including protection pipe 15mm dia up to 7.5m length, provision the earth lead to earth connection in ther main distribution box with lugs and GI nuts, bolts, earthing shall be done all as per shown electrical plate No 5 of SSR part 1 Including neccessary excavation in soft disintergrated rock and provision of 15mm dia pipe with funnel, PCC earth chamber of 100mm thick precast RCC cover with suitable precast RCC frame and earth test point and testing in presence of Engr-in-Charge.complete all as specified and as directed.
M & L for Stay assembly of 20mm dia stay rod complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and as directed.
Loop type insulator, vitreous porcelain, brown, Large size, with overall dimensions 90mmx140mm, clearance of hole 25.5mm complete all as specified and directed.
M & L PCC type D-2, (1:4:8) (using 40 mm graded aggregate) for foundation, filling and mass concrete complete all as specified and as directed.
Supervision charges of 15% of total value the estimate to be paid to Goa State Electricity Board (GSEB) and to make liaison with GSEB for connection complete all as specified and as directed. Note :- (a) Contractor should hold Goa State Electricity Board (GSEB) HT electrical license. (b) Contractor has to laise with GSEB for shutdown and connecting of all the cables. (c) Contractor should be responsible for the payment of Electrical Inspection charges. (d) Contractor has to liaise with Panchayat to cross the civil area. (e) Contractor has to quote the rates considereing all the above aspects. (f) Contractor has to obtain completion certificate from respective GSEB sub divison after completion of work.
Dismantling of ACSR condctor of any size from pole complete and hand over to concerned GSEB sub division complete all as specified and as directed.
Dismantling steel poles/struts, any size complete and hand over to concerned GSEB sub division complete all as specified and as directed.
MARINE ELECTRICAL AGENCIES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .