Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹28.9 LAccepted-AOC | L-1 | Accepted-AOC Lowest bidder | |
| 2 | L-2₹32.1 L+₹3.2 L (11.1%)Rejected-AOC H NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR 144 022 PUNJAB | JALANDHAR | JALANDHAR | PUNJAB | 144022 | L-2 | Rejected-AOC other than lowest bidder | |
| 3 | L-3₹32.4 L+₹3.5 L (12.2%)Rejected-AOC | L-3 | Rejected-AOC other than lowest bidder |
Tender Value
₹31 L
EMD Value
₹62,000
Closing Date
6 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Lt Col Ram G
GE Kaluchak Pin-900673 C/O 56 APO
SPL REPAIR REPLACEMENT OF BER DG SET, VOLTAGE STABLIZER, VT SUBMERSIBLE PUMPS AND OTHET ALLIED WORKS AT KALUCHAK AND RATNUCHAK MIL STN UNDER GE KALUCHAK
2023_MES_594002_1
GE/KC/NIT-14/2023-24
Open Tender
Civil Works
Item Rate
180 days
Kaluchak
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE Kaluchak
₹62,000
Yes
14 Aug 2023
9 May 2023
13 Jun 2023
9 May 2023
6 Jun 2023
23 May 2023
9 May 2023 - 16 May 2023
Amount
Supply, installation, testing & commissioning of Diesel Engine driven water cooled generating set of capacity 62.5 KVA, 415 Volts, BHP as per manufacture recommendation, AC supply, 50 Hz, 3 phase 4 wire, 0.8 PF at NTP, speed 1500 RPM at Ratnuchak, mounted on common base frame with flexible coupling and meeting the requirement of IS-4722/BIS specification with CPCB approved acoustic enclosures fabricated out of CRCA sheets as per manufacture recommendation, sound proofing of enclosures is done with high quality foam conforming to IS-8183 for 75 dBT 01 metre, complete in all respect including 1st fill of lub oil and foundation as per manufacturers recommendations, consisting of the followings :-
(A) DIESEL ENGINE : Water cooled diesel engine of adequate capacity suitable to deliver 62.5 KVA power at 1500 RPM generally in accordance with latest BIS/IS Specification provided with blower fan, 12 volts self starting including maintenance free battery of suitable capacity, charging dynamo/alternator, air cleaner, diesel/oil filters, complete in all respect. The Diesel engine shall be capable of takings 10% over load for one hour for every 12 hours running conforming to the environment (PROTECTION ACT 1986) (29 OF 1986) and as amended vide Gazette of India Notification Part II sections III Sub Section (I) dated 12 Jul 2004. (B) ENGINE INSTRUMENT PANEL : All relevant information shall be displayed on a complete panel for easy monitoring of lubricant, oil pressure, battery charging, ammeter, hours meter, starting switch etc (C) FUEL TANK : In built fuel tank adequate capacity for 12 hours running with stop cock, drain plug as per recommendation of OEM.
(D) ALTERNATOR : 62.5 KVA at NTP at Ratnuchak Mil Stn, 3 phase 50 Hz, 415 volts, AC supply, 0.8 PF at 1500 RPM, it shall be self excited screen protected and drip proof type brushless, conforming to relevant IS/BIS code as per latest manufacturing schedule. (E) CONTROL PANEL : The standard control panel shall be built in accoustic enclosures with the following accessories complete wired with suitable size of copper cable with following accessories:- (i) MCCB of suitable rating with over load and short circuit protection. (ii) Digital Ammeter (iii) Digital Voltmeter (iv) One set of indicating LED lamps RYB and fuses. (v) Frequency meter, RPM meter, Hour meter, Fuel level indicator. (vi) KWH meter of suitable capacity digital type for 3 phase 415 volt AC supply and for unbalanced load. (vii) Water temperature gauge, oil pressure gauge
(F) The Gen set must be affixed with label meeting the following requirement (The label shall be durable and legible) (a) Name and address of the engine manufacturer. (b) Statement that this engine conforms to the environment (PROTECTION) (c) Type and approval certificate number. (d) Date of manufacturing of Gen set. (G) ACOUSTIC ENCLOSURE : Acoustic enclosure should be as per manufacturer recommendation. The walls of enclosures will be insulated to get 75 dba at 1 meter sound leveled as recommended by ministry of environment and forest. The enclosure shall have following provisions : (i) Fitting arrangement (ii) Point for neutral and bod earthing (iii) Fuel drain (iv) Lub oil drainage (v) Air breather (vi) Easy stop push button (vii) Panel meter viewing window (viii) Canopy light as per OEM recommendations.
Notes : (i) DG set should be sound proof as per latest policy. (ii) First filling of Engine oil and Fuel etc should be arranged by contractor for testing. (iii)DG set shall be fixed on PCC plateform all as per the manufacturers instructions and the cost of PCC plateform shall be deemed included in the quoted rates of this item. (iv) The cost for dismantling of existing BER/unserviceable Diesel Engine Generating set of any capacity upto 62.5 KVA with all electric connection and deposited to MES store yard including demolition of old PCC foundation shall be deemed in the quoted rates of this item.
Supplying, installing, testing and commissioning of BEE star rated ISI marked submersible pump set conforming to IS:8034:2002 with Amdt No 1 (with upto date ammendments) suitable for bore size 150/200 mm and 100 mm dia discharge pipe, not less than 8 stage (as per manufacturers design) discharge capacity not less than 1200 LPM at 92 metre head, motor rating 35HP, pump in multistage construction with radial or mixed flow impellers coupled with water filled squirrel cage induction motor 3 phase 415 volts, stainless steel motor casing, pump impellers made of bronze (material of main parts of pump set shall be as per clause 6.2 of IS:8034-2002 with upto date ammendments) for use in borewells for handling clear water having motor to IS 9238:1995 with amdt 1&2 (with upto date ammendments) of wet type for continuous rating operating at 2900 RPM synchronous suitable for 415 volts ,+/- 6% 3 phase AC supply, the motor shall be provided with suitable
size 3 mtr length PVC copper cable flexible insulated and PVC sheathed 3 core flat type of ISI marked and supplied by OEM including providing suitable MS clamp made from 10mm thick MS plate of 50mm width total length of MS clamp shall be 375mm to 425mm apprx with suitable drill holes two nos on each side alongwith suitable nuts/ bolts/ washers etc as required at site, complete all as specified & directed. Notes : (i) All testing arrangement of pumpset shall be made by contractor for which rates deemed to be included in quoted rate. (ii) Any item like cutting, welding etc required at site for making connections shall be deemed included in quoted rate of this item.
Supplying, installing, testing and commissioning of BEE star rated ISI marked submersible pump set conforming to IS:8034:2002 with Amdt No 1 (with upto date ammendments) suitable for bore size 150/200 mm and 80/100 mm dia discharge pipe, not less than 8 stage (as per manufacturers design) discharge capacity not less than 600 LPM at 98 metre head, motor rating 20HP, pump in multistage construction with radial or mixed flow impellers coupled with water filled squirrel cage induction motor 3 phase 415 volts, stainless steel motor casing, pump impellers made of bronze (material of main parts of pump set shall be as per clause 6.2 of IS:8034-2002 with upto date ammendments) for use in borewells for handling clear water having motor to IS 9238:1995 with amdt 1&2 (with upto date ammendments) of wet type for continuous rating operating at 2900 RPM synchronous suitable for 415 volts ,+/- 6% 3 phase AC supply, the motor shall be provided with suitable
size 3 mtr length PVC copper cable flexible insulated and PVC sheathed 3 core flat type of ISI marked and supplied by OEM including providing suitable MS clamp made from 10mm thick MS plate of 50mm width total length of MS clamp shall be 375mm to 425mm apprx with suitable drill holes two nos on each side alongwith suitable nuts/ bolts/ washers etc as required at site, complete all as specified & directed. Notes : (i) All testing arrangement of pumpset shall be made by contractor for which rates deemed to be included in quoted rate. (ii) Any item like cutting, welding etc required at site for making connections shall be deemed included in quoted rate of this item.
PVC insulated and sheathed flat 3 core, 10 Sqmm copper stranded conductor water proof submersible cable fixed to submersible monoblock pump set to starter as directed including testing & taking out old unserviceable cable and depositing to MES storeyard, complete all as specified & directed.
PVC insulated and sheathed flat 3 core, 16 Sqmm copper stranded conductor water proof submersible cable fixed to submersible monoblock pump set to starter as directed including testing & taking out old unserviceable cable and depositing to MES storeyard, complete all as specified & directed.
Pressure gauge, 100mm dia with ball valve of pressure 25 Kg/Sqcm, complete all as specified & directed.
ERW Steel Column Pipe, medium grade, 4.50 mm (7 SWG) wall thickness, 100 mm bore, 3 metre in length each with drilled double flange ends having two cable slots on each flange complete with SS bolts, nuts, washers & rubber insertion gaskets including lowering into the tube-well, testing and commissioning, complete all as specified & directed.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes, testing after completion including disconnecting and taking out old unserviceable cable, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in any type of soil for foundation of pole, stay, taking up or laying of cable etc, complete all as specified & directed. Note : Due care shall be taken while deciding cable route for excavation. However any damage to Signal, BSNL, MES cable water/sewage pipe or any other service while excavation will be made good by the contractor and cost of the same for jointing material & labour is deemed to be included in the cost of excavation.
Sand cushioning to under ground cable, laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete punned to 18cm, complete all as specified and directed. Note:- Punned thickness of sand will be measured and paid.
Brick well burnt locally available sub class 'B' laid over sand cushioning for mechanical cable protection in trenches with width of brick perpendicular to the length of cable, complete all as specified & directed.
Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25cm, complete all as specifed & directed.
Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point, complete all as specified & directed.
Galvanised iron tube 50mm bore light grade (ISI marked) for cable protection to poles/under floor/under roads/alongwith walls complete including MS clamps of flat iron 25x3mm duly painted, GI nuts, bolts and washers & sealing of pipe ends with approved sealing compound including taking down old unserviceable tube, complete all as specified and directed.
Supplying, installing, testing and commissioning of CPRI approved, factory made, LT panel board, cubical, outdoor type, floor mounted double door, 3 phase 4 wire, 50 cycles, 415 Volts, made of 3.15 thick CRCA sheet for load bearing members and 16 SWG (1.6 mm thick) for doors covers and internal partitions, duly powder coated on both side, base frame of the panel shall be made of ICMC channel of size 50 x50 x 6mm duly grouted on platform made of brick work in cement mortar 1:4, 15mm thick plastering in cement mortar 1:4 having minimum height of 600mm, the panel shall be provided with separate compartments for each switch gears with hinged door including interlocking with switch gears,
the panel board shall be suitable for AC, 415 Volts, 50 Hz, 3 phase, 4 wire supply complete with epoxy insulated 315 Amps rated high conductivity aluminium bus bars, supported with DMC / SMC barriers and colour coded, prewired with copper cable, the degree of protection IP-54. the panel shall be complete with instrumentation such as LED phase indicating lamps and CT's including extended aluminium strip of rating of Incomer 160Amps and outgoing as per rating of MCCB’s, including aluminium lugs to connect the cable dismantled before etc. complete all as specified, directed & comprising of the followings:-
(a) MCCB 160 Amps, 4 pole with breaking capacity 36KA (Adjustable thermal & fixed magnetic release) - 01 No (Incomer) (b) On load change over switch, 160 Amps, 4 pole, 415V, 50Hz - 01 No (c) MCCB 63 Amps, 4 pole with breaking capacity 16KA (Adjustable thermal & fixed magnetic release) - 02 Nos (Outgoing) & 01 No spare (d) MCB SPN 32 Amps with breaking capacity 10 KA - 02 Nos (e) Three phase Multifunctional Digital Meter for measuring Voltage, Amper, Frequency & Power Factor - 01 No (f) Phase indication LED lamps - 01 Set (g) CT'S 400/5 - 01 Set
Notes : (a) Design/ drawing/ BOM of the panel board showing the dimensions including accessories is to be obtained from panel board manufacturer and is to be got approved from Accepting officer before placing order to the manufacturer. (b). Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates.
Supplying, installing, testing and commissioning of BEE star rated ISI marked submersible pump set conforming to IS:8034:2002 with Amdt No 1 (with upto date ammendments) suitable for bore size 200/300 mm (as per manufacturers design) discharge capacity not less than 600 LPM at 40 metre head, motor & pump in multistage construction with radial or mixed flow impellers coupled with water filled squirrel cage induction motor 3 phase 415 volts, stainless steel motor casing, pump impellers made of bronze (material of main parts of pump set shall be as per clause 6.2 of IS:8034-2002 with upto date ammendments) for use in borewells for handling clear water having motor to IS 9238:1995 with amdt 1&2 (with upto date ammendments) of wet type for continuous rating operating at 2900 RPM synchronous suitable for 415 volts ,+/- 6% 3 phase AC supply, the motor shall be provided with suitable
size 3 mtr length PVC copper cable flexible insulated and PVC sheathed 3 core flat type of ISI marked and supplied by OEM including providing suitable MS clamp made from 10mm thick MS plate of 50mm width total length of MS clamp shall be 375mm to 425mm apprx with suitable drill holes two nos on each side alongwith suitable nuts/ bolts/ washers etc as required at site, complete all as specified & directed. Note : (i) All testing arrangement of pumpset shall be made by contractor for which rates deemed to be included in quoted rate. (ii) Non return valve - 01 no of suitable size from pump to main delivery line shall be deemed included in quoted rate of this item. (iii) Any item like cutting, welding etc required at site for making connections shall be deemed included in quoted rate of this item.
Supplying, installing, testing and commissioning of BEE star rated ISI marked submersible pump set conforming to IS:8034:2002 with Amdt No 1 (with upto date ammendments) suitable for bore size 200/300 mm (as per manufacturers design) discharge capacity not less than 600 LPM at 60 metre head, motor & pump in multistage construction with radial or mixed flow impellers coupled with water filled squirrel cage induction motor 3 phase 415 volts, stainless steel motor casing, pump impellers made of bronze (material of main parts of pump set shall be as per clause 6.2 of IS:8034-2002 with upto date ammendments) for use in borewells for handling clear water having motor to IS 9238:1995 with amdt 1&2 (with upto date ammendments) of wet type for continuous rating operating at 2900 RPM synchronous suitable for 415 volts ,+/- 6% 3 phase AC supply, the motor shall be provided with suitable
size 3 mtr length PVC copper cable flexible insulated and PVC sheathed 3 core flat type of ISI marked and supplied by OEM including providing suitable MS clamp made from 10mm thick MS plate of 50mm width total length of MS clamp shall be 375mm to 425mm apprx with suitable drill holes two nos on each side alongwith suitable nuts/ bolts/ washers etc as required at site, complete all as specified & directed. Note : (i) All testing arrangement of pumpset shall be made by contractor for which rates deemed to be included in quoted rate. (ii) Non return valve - 01 no of suitable size from pump to main delivery line shall be deemed included in quoted rate of this item. (iii) Any item like cutting, welding etc required at site for making connections shall be deemed included in quoted rate of this item.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 3 meter (BGL), connected to galvanized iron earth strip 32x6mm size (up to 7.5m in length from earth plate) by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 50mm bore 'light grade' galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt etc including connected to test point and testing on completion, complete all as shown in electrical plate No 3 of SSR Part-I 2009 & as directed.
UNITED ENGINEERING CORPORATION
DARVESH ENGINEERING WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .