Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.6 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹2.6 L+₹150 (0.06%)Rejected-Finance | L2 | Rejected-Finance Not being L1 | |
| 3 | L3₹2.6 L+₹4,050 (1.58%)Rejected-Finance | L3 | Rejected-Finance Not being L1 | |
| 4 | L4₹2.6 L+₹8,250 (3.23%)Rejected-Finance | L4 | Rejected-Finance Not being L1 |
| Sl No | Description | Qty | Unit | MK ENGINEERING L1 | SWASTHIK ENGINEERING WORKS L2 | M/s Kamal Electrical L3 | ANITA VARMA ENTERPRISES L4 |
|---|---|---|---|---|---|---|---|
| 1.00 | Taking down defective AHU motor and Supply, installation, testing & commissioning of AHU induction motor suitable for 415 V ,3 phase system 415+-10% volt, 13.7A, 0.87 PF, 50Hz and 87.5% Eff having capacity 7.5KW/10 HP complete all as specified and as directed by Engineer-in-charge. | 1 | Each | 85,000 ₹85,000 Lowest | 85,100 ₹85,100 | 85,500 ₹85,500 | 86,000 ₹86,000 |
| 2.00 | M&L for Servicing of Air Handling Units (AHU) of capacity 15600 CFM, by removing the filter, vacuumising the filter, washing the filter and reinstalling the cleaned filter, brush the cooling coil and spray the foam coil cleaner including rinsing of coil, alignment of shaft & Motor, servicing of chilled water line strainer for the AHUs, tightening of terminals of motor, replacement of V belts, replacement of bearings complete all as specified and as directed by Engineer-in-charge.
Note: The unit rate quoted shall deemed to be include the cost of blowing out the dust, chemical cleaning by spraying the organic based scale removing agent (Vaniklin) at the appropriate ratio till removal of complete dust & scale deposits in the fin area of evaporator coil, flushing through for proper air flow across the coil, cleaning of expansion valve; greasing of blower motor, checking of electrical connection, cleaning of air filters,greasing of blower motor,replacement of unserviceable bearings, V belts, water drain lines, renewal of rusted sheet metal screws, applying synthetic enamel paint over a coat of primer on the rusted portion and testing & commissioning the unit all as specified and as directed by Engineer-in-Charge. | 2 | Each Job | 30,500 ₹61,000 Lowest | 30,500 ₹61,000 Lowest | 30,600 ₹61,200 | 31,000 ₹62,000 |
| 3.00 | Material and labour for carrying out servicing/overhauling , repairs and maintenance of Cooling tower of 100 TR water cooled chiller type central AC plant by dismanlting /taking down the CT fan motor of flange mounted extended type shaft upto 5 HP, 3 phase, 415 volts, 50 Hz, along with fan assembly, and including cleaning & removeal of scales, inspection, cleaning and replacement of PVC fills, PVC eliminator, FRP louvers, motor cover, splash cups etc complete including renewal of all corroded bolts & nuts, terminal block, and re-assembling, fixing in position, fixing of fan blade, and alignment of the fan blade for the suitable air throw of the cooling tower,painting with two coats of synthetic enamel paint over a coat of anticorrosive paint after preparation of surfaces, testing & commissioning the cooling tower motor all as specified and as directed by the Engineer-in-Charge.
Note:- (a) The unit rate quoted shall deemed to include the cost for all T&P, chemicals required for cleaning, FRP compound, nut bolts etc complete for keeping the Cooling tower in operational condition. | 1 | Each Job | 32,000 ₹32,000 | 31,600 ₹31,600 Lowest | 32,500 ₹32,500 | 33,000 ₹33,000 |
| 4.00 | M&L for De-scaling of condenser unit of AC plant of capacity 50 TR by draining condenser water from equipments and pipes. Recirculating water inside the pipes with descaling liquid solution(Carbon Tetra Chloride Solution) and flushing out 3-4 times. Recirculating fresh water inside the pipes and flushing out five to six times so that descaling liquid is completely cleaned out along with Scales from the pipe line complete all as specified and as directed by Engineer-in-charge of the following capacity of AC plant are as under:-
Note:- Each condenser unit will be measured and paid separately. | 3 | Each Job | 23,500 ₹70,500 Lowest | 23,600 ₹70,800 | 23,900 ₹71,700 | 24,500 ₹73,500 |
| 5.00 | Taking down defective fuses and supply & fixing fuse of size A4, 125 A, 80 KA complete all as specified and as directed. | 3 | Each | 2,350 ₹7,050 Lowest | 2,400 ₹7,200 | 2,900 ₹8,700 | 3,100 ₹9,300 |
Tender Value
₹2.6 L
EMD Value
₹5,114
Closing Date
15 Oct 2025, 6:00 pmClosed
GE, Minniebay, Sri Vijaya Puram
GE, Minniebay, Sri Vijaya Puram
Repair/replacement of defective AHU motors, serving of AHU units, cooling tower and descaling of condenser units of central AC plant at HQ 34 WEU
2025_MES_732412_1
3031/Eqtn/RFP/07/2025-26/E3
Open Tender
Civil Works
Item Wise
GE, Minniebay, Sri Vijaya Puram
As per tender documents
13 documents required · 13 mandatory
₹100
GE, Minniebay
₹5,114
10 Nov 2025
24 Sept 2025
17 Oct 2025
24 Sept 2025
15 Oct 2025
1 Oct 2025
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .