| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹1.6 L+₹3,350 (2.10%)Rejected-Finance | L2 | Rejected-Finance 1st. lowest | |
| 3 | L3₹1.7 L+₹7,200 (4.50%)Rejected-Finance | L3 | Rejected-Finance 2nd. Lowest |
Tender Value
Refer Docs
EMD Value
₹4,200
Closing Date
30 Jun 2023, 5:00 pmClosed
AE AHESD
West Bengal Legislative Assembly South Annex Building Gr Floor Kolkata 700 001
SITC of 2 nos Air conditions for 24 X 7 in the Server Room at 2nd Floor of the Library Building Golden Jubilee Building Assembly House Kolkata under Assembly House Elect Section Part I Air conditions
2023_WBPWD_543862_1
eNIQ No. - 07 /WBPWD/AE/AHESD of 2023-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Assembly House
Please refer Tender documents.
6 documents required · 6 mandatory
₹4,200
8 May 2025
23 Jun 2023
3 Jul 2023
23 Jun 2023
30 Jun 2023
24 Jun 2023
Amount
Dismantling of existing old Window Type Air conditioner carefully and deposit to Section Office and cover the wall cut out with 20 mm Heavy Duty Ply and painting.
Supplying of 2.0 TR capacity concealed type split air conditioner of rated cooling capacity of 24000 BTU/hr with Rotary compressor of rated power supply 230V-1ph-50Hz , and 1 nos. 2.0 TR IDU, air flow/per IDU - 800 CFM of rated power supply 230V-1ph-50HZ. (Make- Hitachi/Diakin/Mitsubishi Heavy)
Supply, installation, testing and commissioning incl. vaccumiazation and nitrogen testing as required of following nominal sizes of soft/hard drawn copper refrigent piping for above ac complete with fitting with suitable adjustable ring type hanger supports, jointing/brazing incl. accessories insulated with XPLE class-O tubular insulation with / class O closed cell elastromatric nitrile rubber tubular sleeves section of specified thickness as given below for suction and liquid line all accessories as per specification etc as required. (Make: Ryoku/Totaline/Jobu/Godrej)
15.9mm (5/8") OD (with 13mm insulation) or suitable size as per manufacturer advice.
6.35mm (1/4") OD (with 13mm insulation) or suitable size as per manufacturer advice.
Supplying & drawing of 4 core x 2.5 sq.mm. PVC insulated copper cable for interconnecting the indoor & outdoor unit.
Installation the outdoor & indoor unit, after making holes in wall by expert labour, also mending good after complete the work, Connecting the pipe line testing the leack by gas pressure (minimum 400 PSI ) and vacuuming the unit properly (Minimum -30 PSI), hold the vacuum up to 48 hours, after release the gas testing the Split type Room Air conditioner with supply & fitting adjustable powder coated painted heavy duty iron bracket.
Supplying, fitting and fixing PVC pipes of approved make (medium duty) conforming to ASTMD - 1785 and threaded to match with GI Pipes as per IS: 1239 (Part - I). with all necessary accessories, specials viz. socket, bend, tee, union, cross, elbow, nipple, long screw, reducing socket, reducing tee, short piece etc. fitted including cost of all materials ,jointing materials, cutting pipes, making threads ,etc as directed complete in all respect.
CPWD Item-P-59/16.16: Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
SUPER COOLING AGENCY
aswirbad infra co
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .