Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.5 LAccepted-AOC NO 83 THAMMAIAH GARDEN ABBIGERE CHIKKABANAVARA PO BANGALORE 560 090 | BENGALURU URBAN | KARNATAKA | 560090 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹13.5 L+₹95,973 (7.68%)Rejected-Finance | L2 | Rejected-Finance Not Being eligible | |
| 3 | L3₹13.6 L+₹1.1 L (9.14%)Rejected-Finance | L3 | Rejected-Finance Not Being eligible | |
| 4 | L4₹13.9 L+₹1.4 L (10.9%)Rejected-Finance NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L4 | Rejected-Finance Not Being eligible |
Tender Value
Refer Docs
EMD Value
₹29,000
Closing Date
16 Mar 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF SOUTH BANGALORE
Commander Works Engineers AF South Gangamma Circle Opp Guard Room 410 AFS Jalahalli Bangalore 560013
PROVN OF STANDBY POWER SUPPLY TO SECURITY SECTION AND PERIMETER LIGHTING OF AFTC JALAHALLI, BANGALORE
2021_MES_414201_2
85194
Open Tender
Civil Works
Item Rate
120 days
JALAHALLI
As per tender documents
7 documents required · 7 mandatory
₹500
GE (M) (AF) Jalahalli
₹29,000
Yes
2 Jun 2021
26 Feb 2021
18 Mar 2021
26 Feb 2021
16 Mar 2021
4 Mar 2021
27 Feb 2021 - 2 Mar 2021
60 days
Amount
Supply, installation, testing and commissioning of silent Diesel Engine driven generating set to given an output of 82.5 KVA at 415 Volts. 3 phase, 50 HZ, 4 wire directly coupled to diesel engine, water cooled, mounted on common base plate complete with fuel tank of adequate capacity, vibration damper, other accessories with acoustic enclosure and alternator with AMF Panel complete including PCC foundation etc complete all as specified by the manufacturer and as directed by Engineer-in-charge including comprising of followings :-
ALTERNATOR. The engine shall be coupled through flexible coupling to an Synchronus alternator mounted on a strong steel fabricated common base frame suitable for mounting on a permanent foundation. The alternator shall be 3 phase, 50 Hz, 1500 RPM, self excited, self regulating and Brushless type provided with suitable automatic voltage regulator and shall be confirm to BS : 2613 or BS : 5000 and generating 82.5 KVA output after derating with coupled to diesel engine at 0.8 power factor lag, 415 volts, 4 wire, AC supply under NTP conditions. The alternator will confirm the following feature. (i) IP 23 protection with H class insulation. (ii) Permissible overload of 10% for one hour in 12 Hour operations (iii) Automatic voltage regulator (AVR) - Fast response electronic Type. (iv) PMG fitted.
AUTO MAIN FAILURE (AMF) CONTROL PANEL : Microprocessor based cubical, outdoor type made out of CRCA sheet of 2 mm thick confirming to IS 8623 totally enclosed, dust and vermin proof with front and rear opening, 415 volts, 3 phase, 4 wire, AC 50 Hz having aluminium bus bar of capacity as required to carry current at 110% load of 82.5 KVA DG Set with three phase and half neutral colour coded, pre wired with aluminium cable of suitable size all as per standard practice of manufacturer specifications with the following accessories :- (i) MCCB 4 pole 160 Amps, 25 KA and 4 pole power contactor 160 Amps for alternator (ii) MCCB 4 pole 160 Amps, 25 KA and 4 pole power contactor 160 Amps for mains (iii) Combined digital type meter for AC Voltage/Amp/frequency (iv) Combined digital type meter for DC Voltage/Amp/frequency (v) Combined digital type meter for KW/Power Factor/KVA. (vi) Electronic KWH meter (counter display) (vii) Set of current transformers. (viii) Supply failure timer and restoration timer. (ix) 3 impulse automatic engine start/stop logic and engine fails to start lockout mains/sensor voltage and frequency sensing. (x) Automatic manual switch (xi) Hooter (xii) Earth fault relay (xiii) SMPS based battery charging unit with inbuilt auto/manual and float/boost facility.
BASE FRAME: Engine and Alternator directly coupled on a common channel iron fabricated base frame with predrilled holes.
FUEL TANK : Daily service fuel tank of capacity as per manufacturer recommended,fabricated from 14 SWG sheet metal and integrated in base frame of acoustic enclosure complete with drain valve, level indicator,lid with hinges including locking system,inlet and outlet connection.
ACOUSTIC ENCLOSURE: Enclosure be designed for reducing the sound level 75-5db (Average) as per ISO 8528 part 10 as per approved CPCB norms. The accoustic enclosure must consists of following :- (i) CRCA sheet as per CPCB approved design & drawing. (ii) Base frame be fabricated of ISMC channel or in sheet metal, base frame will be prime coated and painted. (iii) Enclosure be powder coated. (iv) Insulated rock wool fire retarded/non igniting and noise reduction type, properly clamped and shall be provided on all doors, roof and sides to absorb noise. (v) Special designed stainless steel door locks and door hinges.
NOTES : (i) The panel will be complete with internal wiring with suitable size of copper cable. (ii) The panel shall be duly tested and comply with CPRI test standard. (iii) DG set shall be placed on PCC Platform of suitable size, minium one meter extended all around the DG set. Height of platform from ground level shall be minimum 400 mm and depth below GL shall be minimum 200 mm. Platform shall be provided over 100mm thick hard core. Cost of PCC platform including hard core, finishing with plaster and earth work etc shall deemed to be included in quoted rate of item. (iv) Tools shall be supplied as per manufacturer instruction and cost thereof shall be included in the cost of DG set. (v) The DG set and acoustic enclosure shall be complete one unit and it shall be installed as one complete set. (vi) Fuel tank shall be inside the canopy. (vii) Exhaust fan shall be provided of suitable capacity, as approved for proper ventilation.(viii) Exhaust pipe shall be properly insulated. (ix) There shall be windows in the acoustic enclosure suitable located to read the meters of various controls from outside. (x) Necessary grouting mild steel nuts, bolts, washers etc and anti vibration pad shall be provided by the contractor.
Excavation in trenches in soft /loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of cables etc, getting out and forming bottom surface to required gradient complete all as specified and directed.
Returning filling in including spreading levelling watering and well ramming to excavated soil in layers not exc 25 cm thick complete all as specified and directed.
Removing excavated material not exc 50m and depositing where directed at a level not exc 1.5m above the starting point in soils complete all as specified and directed.
Sand (Tibba) cushioning to cables with a layer of sand 8 cm deep before laying the cable and 15 cm depth after laying of cable, complete all as specified and directed.
Brick protection cover on cable with sub class 'B' brick, laid dry and flat adjacent to each other complete all as specified and directed.
M & L for G.I. tubing light grade of size 80 mm bore with fittings for protection of cables to be laid under roads, crossings/culverts complete all as specified and directed.
M & L for G.I. tubing light grade of size 50 mm bore with fittings for protection of cables to be laid under roads, crossings/culverts complete all as specified and directed.
Material and labour for Cutting PCC / road 150mm thick for laying of LT UG cable complete all as specified and directed.
M & L for PCC (1:2:4) type B-1 using 20mm graded stone aggregate for making good the disturbed surfaces during cutting existing road/path/ hard standing for laying of cable to match the existing complete all as specified and directed.
Supply and laying XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable 1100 Volts with stranded aluminimum conductor of size 120 Sqmm 3.5 core laid in trenches/ducts/wall/under floor/GI pipe with suitable glands,clamps,brackets,nuts,bolts and making connections with suitable lugs complete all as specified and directed by Engr-in-Charge.
All as per ser item no.11 here-in-before but of size 95 Sqmm 3.5 core and making connections with suitable lugs complete all as specified and directed by Engr-in-Charge.
All as per ser item no.11 here-in-before but of size 25 Sqmm 4 core and making connections with suitable lugs complete all as specified and directed by Engr-in-Charge.
M&L for earthing complete with galvanised mild steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (Earth pit not less than 2.25m below ground level). The top edge of earth plate not less than 1.5 mtr below ground level connected to GI strip 32x6mm as earth lead by means of nuts, bolts, thimbles, check nuts, washer of GI or steel at two places including PCC (concrete chamber) shall be PCC 1:3:6 type C-I by using 20 mm grade stone aggregate with finish internal surface of concrete chamber shall be given 15 mm thick plasterin CM 1:4, funnel with wire gauge, 80 mm thick RCC pit cover, 320x320mm of RCC 1:2:4 type B-I using 20 mm graded stone aggregate reinforced with XPM jalli, charcoal dust and common salt bages all as shown in electrical plate no.3 of SSR Part-I 2009 and specified including provn of GI strip protected by 40mm dia med grade pipe and water pipe shall be 20 mm bore medium grade, including all excavation works, earth work and connecting the earthing lead to an earth test point/main switch/MCB DB's and testing after completion complete all as specified and directed by Engr-in-Charge.
S&F Change over switch 415V, 4 pole 63A in sheet metal enclosure including bolts,nuts,washers and connecting the cable with gland complete all as specified and as directed.
Material and labour for Busbar box outdoor type of size not less than 90 x 60 x 30 cm totally enclosed dust and vermin proof floor mounting with hinged doors and locking arrangement fabricated with 3.15 mm thick CRCA sheet including cable glands,cable connection with lugs,grouting the angle-04 Nos in below ground level PCC 1:3:6 of size 300 x 300 x 300 mm,over the PCC 1:4:8 of size not less than 400 x 400 x 150 mm,bolts,nuts,washers etc., all as specified and directed by Engr-in-Charge. Note: Busbar bar box comprises the following items: (a) Incomer - MCCB 4 pole,415 Volts,160 Amps,Fixed thermal and magnetic type with breaking capacity of 25 KA - 01 No (b) High grade aluminium busbar of capacity 250 Amps-04 Nos (c) LED lamps for RYB indication - 01 set.
Chandana Enterprises
MORESHWAR ELECTRICALS CORPORATION
devan enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .