Loading…
Loading…
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
7 Oct 2026, 6:55 pm
GE (East) Agra
Garrison Engineer (East) Agra, Military Engineer Services, Gwalior House, 62 Taj Road Agra Cantt-282001
REPAIR/REPLACEMENT OF ACB, MCCBS, VOLTAGE STABLIZER, INDOOR PANEL, CONTROL SWITCH GEAR, COD, PAINTING OF FOUR POLE STRUCTURE AND CONNECTED ACCESSORIES OF WEST SIDE AREA UNDER GE (EAST) AGRA
2026_MES_789562_1
9927/E8
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
Agra Cantt
Please refer tender Documents
10 documents required · 10 mandatory
₹500
Yes
GE (East) Agra
₹60,000
Yes
16 Sept 2026
16 Sept 2026
15 Oct 2026
16 Sept 2026
7 Oct 2026
30 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for dismantling the cable connection of four pole ACB of capacity upto 1250 Amp, 415V 50Hz of as per existing make, strip opening the ACB, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance:- (a) Cleaning the insulation parts including bushing with with CTC solution. (b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer’s instructional manual. (c) Check the bolts,nuts,washers,cotter pins and all terminal connections are in place and tightening and replacement of the worn out parts. (d) Check arc chutes for damage. (e) Clean and lubricate the operating mechanism with a non-hardening grease for the wearing surfaces, Adjust breaker operating mechanism all as per manufacturer’s instructional manual. (f) Checking/inspecting shunt trip coil for serviceability and replacing the same if required. (g) checking control device free for operation. (j) Check after servicing the circuit breaker to verify the contacts move to fully opened and fully closed positions, that ther is an absence of friction and that the electrical operation is functional. Note: The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like shunt release & trip coil etc will be measured & paid separately under relevant schedule items. | 4 | Each | - | - |
| 2 | Supply only spring charging motor suitable for ACB of 630 A to 1250 Amps as all per existing make. | 2 | Each | - | - |
| 3 | Supply only arcing contacts (fixed/moving) suitable for ACB of 630 A to 1250 Amps as all per existing make. | 1 | Each | - | - |
| 4 | Supply only closing coil (for 415 V) suitable for ACB of 630 A to 1250 Amps as all per existing make. | 2 | Each | - | - |
| 5 | Supply only shunt trip coil (240/415V AC) or suitable for ACB of 630 A to 1250 Amps as all per existing make. | 1 | Each | - | - |
| 6 | Supply only cluster contact suitable for ACB of 630 A to 1250 Amps as all per existing make. | 1 | Each | - | - |
| 7 | Supply only trip coil or suitable for ACB of 630 A to 1250 Amps as all per existing make. | 3 | Each | - | - |
| 8 | M&L for fault detection through machine to detect and rectify underground LT/HT cable fault including disconnecting the cable and rectify the fault including necessery earth work and reconnected to the existing postion complete all as specified and directed.
Notes.
(i) All T&P and other acceseries required for checking and finding of fault in cable shall be provided by the Contractor.
(ii) Charges/rent of the fault locating mobile machine, operator, engineer,electricians etc shall be deemed to included rate quoted by Contractor. | 8 | Each | - | - |
| 9S&F MCCB thermal magnetic adjustable type 80 to 100 % of the following sizes on existing LT panel board including dismantling and taking out of old unserviceable MCCB from the LT panel board complete all as specified and as directed :- | |||||
| 9.01 | (a) MCCB 4 pole , 630 amp rating of 36 KA | 3 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
Tender9927.pdf
Tender Documents • 0.84 MB
PS9927.pdf
Additional Documents • 0.70 MB
BOQ_885074.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .