Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹18.5 L A36 ABUL FAZAL ENCLAVE JAMIA NAGAR NEW DELHI 10025 |
Tender Value
₹20.7 L
EMD Value
₹20,679
Closing Date
24 Feb 2025, 11:00 amClosed
Integration of AHU, VAV etc. with existing System
NSL/CEO/CERC/NIT/2025/730
NSL/CEO/CERC/NIT/2025/730
Open Tender-Domestic
Miscellaneous
South Delhi, Delhi
₹2,950
₹20,679
4 Jul 2025
12 Feb 2025
24 Feb 2025
24 Feb 2025
28 Feb 2025
BOQ for BMS Work
BMS Software: ( Client Software)
BMS Software shall be Web Based interface software based on
Windows Latest. The system should be accessible from anywhere on
LAN or WAN or Ethernet without additional licenses or Software. The
Communication protocol with the DDC, 3 Party Systems, etc,shall be
Industry Standard open platform/Software of MQTT/MODBUS. The
System shall include data points as per the project requirement and
shall be scalable by adding additional controller and data points
licenses. The software shall be open system architecture type which
facilitates interoperability with other system over MQTT with
complete control and monitoring functions. Software for AHU
operation , VAV monitoring , Energy Meter & UPS.
Supply, Installation, testing & Commissioning of Workstation / PC for
1.1 Software Installation Minimum requirement of I5, 16GB RAM, 500TB Lot 1 ₹ 1,73,965.71 ₹ 1,73,965.71
with USB port and 21" monitor.
IOT PANEL WITH ADVANCED APPLICATION CONTROLLERS -:
Supply of Smart I/O Controller Digital & Analog and Smart I/O
Module Digital & Analog the consisting of the following IOT Panel.
Panel Paint shadeInside/outside duly power coated with two of
synthetic enamel grey paint shade with galvanized mounting plate.
Sheet of thickness of door shall be 1.6MM CRCA sheet and
frameTop/bottom/side Cover shall be 1.8MM with removal gland
plates shall be 1.6MM.Degree of protection should be IP55.Door shall
be projected & removal type swing should be 100 to 120 degree.
Cable entry shall be from bottom.Panel shall be free standing type
and each panel have 4 nos romovable lifting hooks at top.cable
termination on either side shall be done with pin type lugs along with
identification ferrules.internal wiring shall be run through PVC
channel with covers.Tolerance 5mm of panel dimension.
SENSORS & FIELD DEVICES
Duct type temperature sensors for measuring Supply air
temperature at the Air Handling Units
Differential Pressure Transmitter for measuring the Duct Pressure
CO2 sensor for indicating CO2 level in AHU duct 6 ₹ 18,523.72
Duct type temperature & RH sensors for measuring Return air
temperature at the Air Handling Units
2 Core x 1 sqmm FRLS Al-Mylar Screened with drain wire, Cable for
control cabling
4 Core x 1 sqmm FRLS Al-Mylar Screened with drain wire, Cable for
control cabling
12-Port 1000Base-T + 4-Slot 1000Base-SX/LX Industrial Managed
Digitally signed by AMIT
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT CERC Integration.pdf
Tender Document
BoQ CERC electrical.pdf
Tender Document
SCC CERC integration.pdf
Tender Document
GCC PMC 2022 Upto Amendment 11.pdf
Tender Document
Instruction to Bidder for online Bid Submission.pdf
Tender Document
Forms.pdf
Tender Document
corrigendum-3548-Corrigendum-II.pdf
pdf • 0.43 MB
corrigendum-3517-Corrigendum-I.pdf
pdf • 0.74 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .