Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.8 LAccepted-AOC 150 BC LINE MALL ROAD MEERUT CANTT 250001 | MEERUT | UTTAR PRADESH | 250001 | L1 | Accepted-AOC Due to lowest and quoted rates is reasonable | |
| 2 | L2₹5.0 L+₹18,678 (3.92%)Rejected-Finance | L2 | Rejected-Finance higher site quoted amount |
Tender Value
Refer Docs
EMD Value
₹10,655
Closing Date
13 Apr 2024, 6:00 pmClosed
GE(West)Pathankot
GE(West)Pathankot
PROVN OF SPLIT AC AND PROVN OF GEYSERS UNDER GE (WEST)PATHANKOT
2024_MES_646413_1
GE/PKT-75/2023-24
Open Tender
Miscellaneous Works
Item Rate
90 days
Pathankot
As per tender and NIT doc
9 documents required · 9 mandatory
₹500
GE(West)Pathankot
₹10,655
6 Jun 2024
14 Mar 2024
15 Apr 2024
14 Mar 2024
13 Apr 2024
29 Mar 2024
Amount
Supply, installation and testing all weather split AC units indoor and outdoor of 2 Ton capacity BEE 3 star rating with EER not less than 3.2 complete with cordless remote control unit, inbuilt anti-microbial air filtration for better indoor air quality including copper piping of suitable size with insulation, PVC drain pipe, mounting plate for indoor unit and brackets of powder coated GI steel for outdoor units and mounting with suitable size of anchor bolts and nuts including making hole of suitable size on wall for passing wire and copper pipes complete all as specified and as directed.
S&F single phase voltage stabilizer of capacity 05 KVA for automatic operation, copper wounded air cooled indoor type & designed for input variation between 170V to 270V with output voltage stabilized at 230 with accuracy + 5% including 3 core flexible wire of suitable size drawn through and including concealed PVC conduit medium grade from stabilizer to power point and making good the disturbed surface complete all as specified and as directed Note:- Cutting chasing the wall for concealing conduit and making good the disturbed surface deemed to be included in the quoted rates.
M&L for point wiring any length with 4 sqmm PVC insulated unsheathed multistrand copper conductor FRLS cable with in and including PVC concealed conduit heavy duty 20mm dia having thickness not less than 1.8 mm with all fitting suitable for one AC power point including 4 sqmm PVC insulated unsheathed multistrand copper conductor FRLS cable as earth continuity conductor connected to common earth dolly in and including cutting chiselling for concealed piping and making good disturbed surface finishing the surface to match with the existing surface complete all as specified and directed.
M&L for point wiring with 2.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS cable with in and including PVC concealed conduit heavy duty 20mm dia having thickness not less than 1.8 mm with all fittings including anodise pressed steel sunken box having thickness not less than 2mm with 3mm thick bakelite laminated sheet ISI marked suitable for 5 pin 15 amps socket outlet ,including 2.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS cable as earth continuity conductor connected to common earth dolly in and including cutting chiselling for concealed piping and making good disturbed surface finishing the surface to match with the existing surface complete all as specified and directed.
S&F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 32 Amp, 10 kA complete all as specified and as directed.
S&F sheet metal enclosures distribution boards, double door three phase 415 volts 4 ways vertical TPN DB for comprising three phase four wire copper strip bus bar of appropriate capacity complete all as specified and directed and comprising of the following (a)MCCB FOUR POLE 100 AMPS AC 415 VOLTS 25 KA=01 NO as incoming and 6 nos. MCB SP 32 Amps, C series as outgoing (Note :- (i) The DB shall be flush fixed ,and making good the disturbed surface matching with existing specifications shall be part of job at no extra cost.(ii)connection of theMCCBs/ MCBs with cable shall be made through appropriate size pin /bottle type thimble -properly crimped.(iii) all the vacant holes of the DB shall be provided with blank plates of appropriate size. (iv) double continuous earth wire shall be provided for each three phase DB from earthing mains dolly (v)MCCB's and MCB's should have a same make as of DB.
Supply, laying and testing LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 16 sq. mm 4 core complete all as specified
Excavation in trenches, not exceeding 1.5 m wide and not exc 1.5 m in depth for laying of cable etc and not exceeding 10 sqm on plan for manholes etc and getting out in any type of soil, complete all as specified. and directed by Engr-in-Charge.
Returning filling in including spreading, levelling, watering and well remming in layers not exceeding 25cm thick in hard/dense soil complete all as specified.
Removal to excavated material (Soil) to a distance not exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed by Engr-in-Charge.
Sand cushioning with fine sand to under ground cables in trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable as specified in clause 19.75 of SSR Part-I complete all as specified and as directed by Engr-in-Charge. Note:-Punned thickness will be measured and paid
M&L for brick covering with equal to length of brick as mechnical protection to cable with well burnt5 sub class 'B' bricks laid as directed.
M&L for tube light grade galvanised of 40 mm bore with all fittings laid in tranches/trough wall/pole under road/floor by means of suitable size FI clamps, nuts bolts and washers complete all as specified and as directed.
M&L for cuting the PCC floor/road/wall not less than 15cm in depth and 15 cm in width for insurting GI pipe upto 40mm dia for cable protection and making good the disturbed surface and matching with the existing surface by suing the PCC of 1:2:4 type B-1 complete all as specified and as directed.
M&L for earthing complete with galvanised steel earth plate electrode , 600 x600 x 6mm thick burried directly in the ground (earth pit not less than 2.25 mtr deep below ground level)with top edge of the plate not less than 1.5mtr below ground level connected to galvanised iron wire 4mm dia as earth lead by means of bolts, nuts and washers of GI up to test point , GI tubing 15 mm bore light grade protection pipe , GI watering pipe 20mm bore light grade with funnel and wire mesh , charcoal ,salt packed around the earth plate and precast PCC 1:2:4 (Nominal mix ) reinforced with XPM having weight not less than 4 kg /sqm including suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover including earth work in any type of soil , removal of surplus soil to a distance n.exc 50m and connecting , testing on completion complete all as shown on electric plate No 03 of SSR -2009 Part I and connecting to existing earth test point complete all as specified and directed or including testing on completion.(Note: Excavation and earth work is deemed to be included in the rates quoted).
Supply and installation of the electric water storage heater of ABS body type, 25 ltr capacity with rated power 2KW, 5 star rated, vertical type, thermally insulated mild steel tank with glass line coating inside the tank alongwith glass lined incoloy heating element with anti corrosive magnesium anode, NRV, thermostat, indicators and temperature adjustable knob including steel braided flexible connection for pipe of size 15mm bore with GI hexagonal adopters/nuts on both sides for inlet (cold water supply) & outlet (hot water supply) and including provision of wall mounting arrangements and mounting on wall with suitable size of anchor bolts with complete connection of water including testing after installation complete all as specified and as directed.
S&F 15mm bore Angle valve heavy duty cast copper alloy polished bright CP fancy type screwed down high pressure with crutch handle screwed down for iron pipe with brass furrele complete all as specified and as directed.
S&F 15mm dia Bib taps, heavy duty polished bright cast copper alloy fancy type chromium plated with crutch handle, screwed down, screwed for iron pipe or for brass ferrule complete all as specified and as directed.
M&L for GI tubing medium grade 15mm bore on floor/wall including fittings complete including all necessary fittings to hold the pipe along the wall like hook, bolts, etc complete all as specified and as directed.
M&L for cutting including screwing existing steel tubing for alteration or addition including tee/nipple upto 25-32mm dia complete all as specified and as directed.
S&F S&F 5Amp/16Amp witch socket combination flush type complete all as specified and as directed.
Malpotra Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .