Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹60.0 LAccepted-AOC 13 29 304 3RD FLOOR EAST PATEL NAGAR OPP SIDDHARTHA HOTEL NEW DELHI 08 | NEW DELHI | NEW DELHI | DELHI | 110008 | 1st | Accepted-AOC Being Lowest | |
| 2 | 2nd₹67.4 L+₹7.4 L (12.4%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | 2nd | Rejected-Finance Being Not Lowest | |
| 3 | 3rd₹73.7 L+₹13.7 L (22.9%)Rejected-Finance A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | 3rd | Rejected-Finance Being Not Lowest |
Tender Value
Refer Docs
EMD Value
₹1.2 L
Closing Date
31 Jan 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CE RND DELHI
CE RND PROBYN ROAD DELHI-110054
PROVISION OF AUGMENTATION OF POWER SUPPLY AT CFEES UNDER GE (I) RND DELHI
2021_MES_497870_1
CE R and D /DLI-09/2021-2022
Open Tender
Civil Works
Item Rate
365 days
CE RND Delhi
Please refer tender documents
8 documents required · 8 mandatory
₹1,000
CE RND DELHI
₹1.2 L
Yes
23 Feb 2022
28 Dec 2021
3 Feb 2022
28 Dec 2021
31 Jan 2022
17 Jan 2022
60 days
Amount
Supply, installation, testing & commissioning of package type/unitised 11kV / 433 V Outdoor Compact secondary sub-station suitable for outdoor installation with natural cooling, having type tested equipments conforming to IEC 62271-202 only and relevant IS specifications including K-10 temperature class as applicable for the rating, Internal Arc of 21 KA/1 Sec, comprising of oil cooled (on an distribution transformer 1000 KVA phase, 1 AC AB SF6 ) insulated compact switchgear enclosed in robotically sealed stainless steel tank, low- voltage switchboard, interconnection between HT switchgear and transformer using cables and transfomer to LT-switchgear using copper busbars, factory built ready for connection type, internal GI earthing provided complete with other associated equipments as required conforming to IEC 62271-202 and relevant IS specifications, as regards to design, manufacturing, type-testing, routine-testing and operator safety (IAC AFLR), the enclosure shall have modular construction using G.I. Sheet installed on PCC1:2:4 type B-2 using 40 mm graded stone aggregate as in foundation of suitable size extending 500 mm all around the outdoor enclosure and 450 mm height (above natural ground level) complete with suitable sizes of GI Pipes for incoming/outgoing cables/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 50x50x6 mm duly painted all along the corner of the foundation. The transformer compartment should have IP-23 ingress protection, whereas the HT/LT compartment should have IP-54. protection (suitable terminal shall be given for body and neutral earthing, whereas cable entry shall be from bottom via trenches made in RCC plinth as per manufacturers recommendation ) Note :-CSS shall be from OEMs only,Licensed system Intigrators are not allowed to supply, Package Compact secondary substation shall have the following equipment :-
(A) HT SWITCHGEAR Shall comprise of 01 Nos:
Fixed- Type compact VCB of rated normal current 11kV 630Amps, 21KA/3 sec. 3 way non-extensible Ring Main Unit Compact switchgear consisiting of 630A, 2 Nos SF6 insulated fix manual fault making/load break switch and 0 Nos 630A fixed manual SF6 insulated vaccum circuit breker with IC-OG arrangement having copper bus bars, feeding to X'mer in CSS. VCB will be enclosed in tank made of robotically welded non- magnetic/non-ferritic Stainless Steel sheets, and filled with SF6 gas acting as insulating medium to suitable pressure and leakage rate less than 0.1% per-annum, whereas it shall be Arc-Proof design with Internal Arc criteria of 20KA/1-sec as per IEC 62271-200. The complete Compact Switchgear Unit should be a front-accessible design with associated Capacitive Voltage LED Indicators connected to site replaceable cable bushings, front-facia integrated handle for spring charging and semaphore mechanical indication for isolator/breaker ON/OFF/EARTH The VCB will be accompanied by Numerical Self Power Protection Relay, providing Over-current (min. pickup 10%), Earth-Fault (min. pickup 5%), Three Phase Inrush Detection, CB Control, TCS, 3P+N Current Measurement, Non-Volatile memory for 100-event log, five-fault record with time-stamp, Local HMI and user-programmable DI/DO for future deployment of inter-tripping scheme. CT-Ratio for protection and metering shall not be more than 50/1 of suitable VA burden and accuracy. VCB will be provided with suitable Tripping/Closing coils and battery + charger scheme of 24V DC. 230 V, AC supply for charging the batteries and misc. Space-heater/LED illumination etc. will be provided from transformer output. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. Interconnection between HT Switchgear and primary of transformer shall be done through manufacturers 1C x 3R x 95 sq.mm Aluminium wire/strip XLPE cable. - 1 No, RMU/VCB shal also have following provisions:-
Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil.
Capacitive voltage indication fixed type system with LED
SF6 Gas pressure indicator.
Padlocking facility.
Protection CT shall be minimum 60/1A ,2.5VA ,5P10. - 3 nos.
All modules of the RMU shall be suitable for cable termination of 3C x 300 sq.mm Aluminium conductor XLPE Cable, incoming cable termination is included within the scope of work - 01 Set, D.C supply through inbuilt 24 volt power pack for auxiliary power requirement purpose all internal control connection for transformer protection device with copper wire.
(B) 1000KVA 11KV/433V Dyn11 OIL COOLED (ONAN)TYPE DISTRIBUTION TRANSFORMER
01 No AC 3 phase 1000 KVA capacity transformer copper wound step down harmetically sealed 11 KV/433 volt at No load oil immersed naturally cooled corrugated wall design with external cooling tubes/fin core type delta connection on primary (HV side) in accordance with vector group, DYN 11 with neutral brought on secondary (LV side) and having taping plus 2.5%,±5% and +7.5% to be change by means of hand operative off load tape changer gear complete mounted inside compact sub station enclosure including testing and comprising all standard accessories for the rating of transformer as per IS/IEC and including followings:- (a) HT 11 KV bushing (b) LT 1100 V bushing (c) Digital type thermometer vapour pressure type range 0-120 degree celcious and having facility to set tempreature and beyond set point trip the supply with alarm (d) Rating plate (e) Earthing teminal as per IS (f) lifting hook (g) First filling transformer conforming to relevant IS of 40 KV die electric strength (h) Surge arrestor between transformer and VCB.
(C) LT PANEL shall be a totally enclosed, floor-mounted, dead-front access, IP4X protected panel fatory fabricated with 2 mm thick CRCA sheet duly painted with epoxy powder coated over a coat of red oxide zinc chrome primer and including accessories given here-in-after which has a temperature rise tested design, copper busbars, suitable switchgear configuration and indication scheme as described below/here-in-after:-
04 Nos of 200 Amps mounted on epoxy insulators.
(I) INCOMER FROM TRANSFORMER
1600 Amps 433V 4P 50Hz 50KA draw out Type Air Circuit Breaker (ACB) with thermal magnetic release as incomer from transfomer along with microprocessor based overload, short circuit and earth fasult (TDMT + instantaneous relay) cast regin type CT, control MCB, ON/OFF/TRIP, LED indication and termination of 240 sqmm 3.5 core aluminium armoured cable.
Multifunction meter of class 1 accuracy. - 1 No.
(II) OUTGOING
4 Nos. 630 Amps 433V, 3P, 50Hz, 36KA with microprocesser based thermal release for LSIG (long time short time instantaeous ground) protection for outgoing fedders Type Moulded Case Circuit Breaker (MCCB)
1 Nos. 400 Amps 433V, 3P, 50Hz, 36KA with microprocesser based thermal release for LSIG (long time short time instantaeous ground) protection for outgoing fedders Type Moulded Case Circuit Breaker (MCCB)
1 Nos. 100 Amps 433V, 3P, 50Hz, 36KA thermal releaseType Moulded Case Circuit Breaker (MCCB)
BLANK
(D) APFC (to installed out side CSS)
Following outdoor type (IP54) APFC panel (to be installed out side CSS), fabricated with 2.0 mm thick CRCA sheet duly painted with epoxy powder coated paint over a coat of red oxide zinc chrome primer and necessary arrangement to be made to connect LT panel main busbar and APFC panel. MPP capacitor of suitable rating alongwith power contactors and fuses/MCB are required.
300KVAR, Automatic power factor correction panel to maintain power factor 0.98 in 12 steps (30KVAR x 8+25KVAR x 2+ 5KVAR x 2) consisting of followings:-
(i) 1 no. 630Amps, 3P, 36KA, 433V, Fixed manual type MCCB with thermal magnetic release for over load and magnetic short circuit as main incomer for APFC banks.
(ii) 1 no.12 step APFC Relay
(iii) 8 nos. 30KVAR metallised polypropelene capacitor bank
(iv) 2 nos. 25KVAR metallised polypropelene capacitor bank
(v) 2 nos. 5KVAR metallised polypropelene capacitor bank
(vi) 8 nos. Capacitor duty contactor for switching on and switching off 30 KVAR bank
(vii) 2 nos. Capacitor duty contactor for switching on and switching off 25 KVAR bank
(viii) 2 nos. Capacitor duty contactor for switching on and switching off 5 KVAR bank
(ix) 8 nos. 63A 3P MCB for 30KVAR Capacitor protection
(x) 2 nos. 63A 3P MCB for 25KVAR Capacitor protection
(xi) 2 nos. 16A 3P MCB for 5KVAR Capacitor protection
(xii) Fan
All necessary Civil works such as PCC/RCC foundation, Plateform, Filling trench and pedestal etc are deemed to be included in scope of work .
(E) OUTDOOR ENCLOSURE
Outdoor type encloser of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of galvanised sheet steel in suitable design for better heat dissipation and providing robust construction. The enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure exterior shall be painted with epoxy based powder coated paint (colour RAL 7032). Structure of compact sub station shall be able to with stand the gross weight of all equipment and to transport from OEM work shop to site along with all equipment i.e. RMU, transformer and LT panel etc. Separate compartment shall be provided for each equipment and panel. Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitablly handling any arcing inside the compartment for providing better safety to the operator. The compartment illumination LED lamp with door operated switch shall be provided for each compartment.- 01 Each
(F) CIVIL WORKS
All necessary Civil works such as PCC/RCC in foundation, platform, steps, ducts, filling trench/ pedestal, plastering etc are deemed to be included in quoted rate. Foundation shall be constructed as per OEM drawings/recommendation with extending 500 mm all around site of platform. The drawing/sketch enclosed in the P.S is for guidelines may be vary as per OEM requirements/directions. Nothing extra shall be admissible on this account later on. Note:- (a) Make of transformer & RMU shall be same as CSS and as per OEM only. (b) LT panel & APFC panel shall be OEM make or if not manufactured by OEM then CPRI approved of make as shown in appendix 'B' to P.S. (c) If above equipment make are not manufactured by OEM only then make specified in list of makes will be incorporated only.
Supplying laying, connecting and testing XLPE insulated heavy duty, PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts grade (earthed) cross sectional area 3 core x120 sq mm conforming to IS 7098 (Part-2) laid in ground through trenches/ pipes/ on walls/ poles etc including necessary lugs, glands etc complete all as specified and directed.
Supply, laying, connecting and testing XLPE insulated heavy duty, PVC bedded galvanised steel strip armoured LT 1100 volt grade with aluminium conductor multi stranded conforming to IS-7098 cables laid in ground through trenches/ pipes/ on walls/ poles including necessary lugs at termination of cable size 240 Sqmm 3.5 Core complete all as specified and directed. Note for Item No 2 to 3 :Excavation, Earthwork, PCC cable cover, sand cushioning etc shall be measured and paid separately under relevant item of BoQ.
Supply, laying and making cable jointing kit for 11KV (earthed), grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 mm complete all as specifed and directed.
Excavation in trenches not exc 1.5 m wide and n. exc 1.5 m depth for foundation etc or laying/ cables or for shaft, pipes manholes etc not exceeding 10 Sqm on plan and not exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layer each not exceeding 25 cm thick in soft/loose soil complete all as specified and directed.
Removing excavated surplus soil to a distance exceeding 50 mtr and depositng where directed at a level n exc 1.5 m above the starting point complete all as specified and directed.
Supply and laying un-reinforced precast concrete (M-20) cable cover class LV type-I, flat size 250mmx150mmx40mm for LT cables protection in trenches complete all as specified and directed.
Supply & laying un-reinforced precast concrete(M-20) cable cover, class HV type1 flat size 300mmx180mmx40mm for cable protection in trenches complete all as specified and directed.
M&L for sand filling n. exc 25 cm thick in layers laid in trenches for cushion to underground cables with layer of sand (8cm and 15 cm deep before and after laying cable) respectively complete all as specified. Note :- Considation and punned down thickness will be considered for payment purpose in cushion to cable respectively.
M&L for boring of holes under road, pavement, hard standing by trenchless techonology using ultra sound technique/mannually/mechanically and necessary machine including supply and laying of 100mm dia HDPE pipe for cables complete all as specified and directed by Enginer-in-Charge
Supply and laying of 100 mm dia GI pipe light grade ISI marked including all necessary, fittings laid in trenches/surface for protection of underground cable complete all as specified and directed.
M & L for Earthing with Galvanised iron earth plate electrode 600 x 600 & 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal GL) with top of earth plate not less than 1.5 metre below GL connected to GI earth Strip 32 x 6 mm connected to earth plate electrode by means of GI nuts, bolts & washers earth strip protected with & including 20 mm dia medium grade ISI marked GI pipe not less than 7.5 metre long all as shown in electrical plate No 3 of MES Schedule Part I, with & including; PCC 1:3:6 type C1 pit with cover of RCC 1:2:4 B1 reinforced with welded steel wire fabric not less than 4 Kg per Sqm watering arrangements with 20 mm GI medium grade pipe ISI marked , GI funnel with GI mesh, filling with mixture of common salt & charcoal, necessary excavation and earth works in any type of soil, including test point, made of gun metal or phosporous 75x75x25mm testing & commissioning, complete all as specified and directed. Note:- Earth strip 32X6 mm and 20 mm dia GI medium grade 7.5 m only from the top of earth electrode provision are included under this item.
Supply and fixing of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x 6 mm galvanised iron strip complete all as specified and directed. Note: Excavation & earth work if required shall be measured & paid separetely under respective item of BOQ.
Commercial Traders
Ridhi engineers and builders
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .