Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.0 LAccepted-AOC | L1 | Accepted-AOC Reasonable | |
| 2 | L2₹34.4 L+₹4.2 L (14.1%)Rejected-Finance OPPOSITE J K BANK BAROO NH1 HAIDERY COMPLEX BAROO KARGIL BAROO KARGIL LADAKH 194103 | KARGIL | LADAKH | 194103 | L2 | Rejected-Finance Rates quoted on higher side | |
| 3 | L3₹34.4 L+₹4.3 L (14.2%)Rejected-Finance | L3 | Rejected-Finance Rates quoted on higher side |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
4 Mar 2021, 6:00 pmClosed
CWE AF PANAGARH
HQ CWE AF PANAGARH MILITARY ENGINEER SERVICES AIR FORCE STATION ARJAN SINGH PO BIRUDIAH DIST BURDWAN WEST BENGAL PIN 713148
SPL REP TO LT DISTRIBUTION AND CONTROL SYSTEM AT CERTAIN TECH AND NON TECH AREA AND REPAIR TO EM SAFETY EQUIPMENTS AT AFS ARJAN SINGH AT AFS ARJAN SINGH PANAGARH
2021_MES_413465_1
82334/PAN/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
PANAGARH
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
Yes
GE AF PANAGARH
₹94,000
Yes
24 Mar 2021
18 Jan 2021
6 Mar 2021
18 Jan 2021
4 Mar 2021
9 Feb 2021
18 Jan 2021 - 15 Feb 2021
Amount
M & L disconnecting the electric connection and dismantling the existing old LT panel board including its accessories , any size and description, keeping aside in safe custody / transporting and depositing to MES stores yard of GE for obtaining credit from contractor all as directed by Engineer-in-Charge.
Supply, installation, testing and commissioning LT panel board suitable for operation on 415 Volts, AC, 3 phase 4 wire, 50 Hz electric supply system, indoor, cubical type, factory made out of MS/CRCA sheet 2 mm thick, dust and vermin proof construction, powder coated, internally externally pre-wired complete with angle iron base frame, with insulated Aluminium bus-bar of suitable capacity mounted on insulators , rear and front operated hinged door with locking arrangement, CPRI approved, complete with suitable aluminium busbar and fixed on angle iron base for pedestal mounting of size 60x60x5 mm for connecting cable on both sides complete all as specified and as directed by Engineer-in-Charge.
Supply, installation, testing and commissioning of Feeder pillar , totally enclosed, cubicle type, weather, dust and vermin proof construction, outdoor type, factory made, with rear and front operated hinged door with locking arrangement, IP55 protection, CPRI approved, having canopy fabricated from MS sheet 3.15 mm thick, powder coated, suitable for operation on 415 Volts, AC, 50 Hz, 3 phase supply system, mounted on PCC pedestal with the following switchgears & control gears and accessories complete all as specified and as directed by Engineer-in-Charge. (Notes: 1. Cost of cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate) platform for mounting the feeder pillar of suitable size shall be deemed to be included in the unit rate quoted. 2. Suitable size of panel mounting the following accessories with working space and wiring with copper cable of suitable size complete as required and as per SLD & specification. 3. Installation /commissioning height of feeder pillar box should not be less that 0.5 meter above normal ground. 4. Contractor must have arranged the temporary supply at site before taking out & refixing the new panel. 4. The unit rate shall deemed to be inclusive of all the items as mentioned here-in-after complete all as specified and indicated.) :- (a) Basic Automatic Transfer controller unit with integrated dual power supply suitable for 630 Amp rating motorised changeover -01 (Make: L&T/Legrand/ Siemens/ABB) (b) Motorised Changeover 630 Amps Rating, 4 pole -01 (Make: L&T/Legrand/ABB/Siemens) (c) INCOMING : (i) MCCB 400 Amps, 4 pole 50 kA with LSIG Protection- 01 Nos (Incoming) (d) OUTGOINGS :- (i) MCCB 320 Amps, 4 pole 36 kA with thermal magnetic release - 01 Nos (out going) (ii) MCCB 200 Amps, 4 pole36 kA with thermal magnetic release - 01Nos (out going) (iii) MCCB 125 Amps, 4 pole, 36 kA thermal magnetic release - 01 Nos (out going)
(d) OUTGOINGS (Contd...) :- (iv) MCCB,415 V, AC, 50 Hz, 100 Amps rating, 4 pole, 36 kA having thermal magnetic release - 01 No. (v) MCCB,415 V, AC, 50 Hz, 63 Amps rating, 4 pole, 36 kA having thermal magnetic release -03 Nos. (vi) MCCB,415 V, AC, 50 Hz, 40 Amps rating, 4 pole, 36 kA having thermal magnetic release - 02 Nos. (vii) MCCB,415 V, AC, 50 Hz, 32 Amps rating, 4 pole, 36 kA having thermal magnetic release -02 Nos (e) Astronomical Time switch ,60 Amps, 24 hour programming type with ML-4 Contactor 100A, 415 Volt, AC, three phase, coil operating voltage 230 Volts, three point Auto manual switch 15 Amps for by-pass system with 63A, 4 Pole MCCB adjustable( 40 % to 100 %) Microprocessor release , 35 kA complete including necessary connection by using copper wire of size 25 sq. mm - 1 set (Make: L&T) (f) Digital Multi-functional Meters for measuring current, voltage and frequency including CTs of suitable rating and class. (g) Indicator lamps RYB, LED type (Make : ABB/Legrand/Schneider/Other makes as specified in Appendix 'D' to Particular Specifications here-in-after.)
Supply, installation, testing and commissioning of Feeder pillar , CPRI approved, totally enclosed, cubicle type, weather, dust and vermin proof construction, outdoor type, factory made, with rear and front operated hinged door with locking arrangement, IP55 protection, having canopy fabricated from MS sheet 3.15 mm thick, powder coated, suitable for operation on 415 Volts, AC, 50 Hz, 3 phase supply system, mounted on PCC pedestal with the following switchgears & control gears and accessories complete all as specified and as directed by Engineer-in-Charge. (Notes: 1. Cost of cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate)platform for mounting the feeder pillar of suitable size shall be deemed to be included in the unit rate quoted. 2. Suitable size of panel mounting the following accessories with working space and wiring with copper cable of suitable size complete as required and as per SLD & specification. 3. Installation /commissioning height of feeder pillar box should not be less that 0.5 meter above normal ground 4. The unit rate shall deemed to be inclusive of all the items from sl no (a) to (m) as mentioned here-in-after complete all as specified and indicated.) :- (A ) INCOMING : MCCB, 415 V, AC, 50 Hz, 400 Amps, 4 Pole 50 kA with LSIG Protection- 01 No. (B) OUTGOINGS :- (a) MCCB,415 V, AC, 50 Hz, 250 Amps rating, 4 pole, 36 kA having thermal magnetic release - 01 No. (b) MCCB,415 V, AC, 50 Hz, 200 Amps rating, 4 pole, 36 kA having thermal magnetic release - 02 Nos. (c) MCCB,415 V, AC, 50 Hz, 125 Amps rating, 4 pole, 36 kA having thermal magnetic release - 02 Nos d) MCCB,415 V, AC, 50 Hz, 100 Amps rating, 4 pole, 36 kA having thermal magnetic release - 02 Nos. (e) MCCB,415 V, AC, 50 Hz, 63 Amps rating, 4 pole, 36 kA having thermal magnetic release - 03 Nos (f) MCCB,415 V, AC, 50 Hz, 40 Amps rating, 4 pole, 36 kA having thermal magnetic release -02 Nos
(B) OUTGOINGS (Contd...) :- (g) MCCB,415 V, AC, 50 Hz, 32 Amps rating, 4 pole, 36 kA having thermal magnetic release - 02 Nos. (h) Astronomical Time switch, 60 Amps, 24 hour programming type with ML-4 Contactor 100A, 415 Volts, three phase, coil operating voltage 230 Volt, three point Auto manual switch 15 Amps for bypass system AC with 63A, 4 Pole MCCB adjustable( 40 % to 100 %) Microprocessor release , 35 KA complete including necessary connection by using copper wire of size 25 sq. mm - 1 set (j) Digital Multi-functional Meter for measuring current, voltage and frequency including CTs of suitable rating and class (k) Indicator lamps RYB, LED type -01 Set (Make : ABB / Legrand/Schneider/Other makes as specified in Appendix 'D' to Particular Specifications here-in-after.)
Supply, installation, testing and commissioning of Feeder pillar , CPRI approved, totally enclosed, cubicle type, weather, dust and vermin proof construction, outdoor type, factory made, with rear and front operated hinged door with locking arrangement, IP55 protection, having canopy fabricated from MS sheet 3.15 mm thick, powder coated, suitable for operation on 415 Volts, AC, 50 Hz, 3 phase supply system, mounted on PCC pedestal with the following switchgears & control gears and accessories complete all as specified and as directed by Engineer-in-Charge. (Notes: 1. Cost of cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate)platform for mounting the feeder pillar of suitable size shall be deemed to be included in the unit rate quoted. 2. Suitable size of panel mounting the following accessories with working space and wiring with copper cable of suitable size complete as required and as per SLD & specification. 3. Installation /commissioning height of feeder pillar box should not be less that 0.5 meter above normal ground 4. The unit rate shall deemed to be inclusive of all the items from sl no (a) to (m) as mentioned here-in-after complete all as specified and indicated.) :- :- (a) Basic Automatic Transfer controller unit with integrated dual power supply suitable for 630 Amp rating motorised changeover -01 (b) Motorised Changeover 630 Amps Rating, 4 pole -01 (c) ACB, 630 Amp, Microprocessor based, breaking capacity 50 KA, draw out version type- 01 No. (d) INCOMING : MCCB, 415 Volts, AC, 50 Hz, 400 Amps, 4 pole, 50 kA with LSIG Protection- 01 Nos (e) OUTGOINGS : (i) MCCB,415 V, AC, 50 Hz, 250 Amps rating, 4 pole, 36 kA having thermal magnetic release - 01 No. (ii) MCCB,415 V, AC, 50 Hz, 200 Amps rating, 4 pole, 36 kA having thermal magnetic release - 02 Nos. (iii) MCCB,415 V, AC, 50 Hz, 100 Amps rating, 4 pole, 36 kA having thermal magnetic release- 02 Nos.
(e) OUTGOINGS : (iv) MCCB,415 V, AC, 50 Hz, 63 Amps rating, 4 pole, 36 kA having thermal magnetic release- -03 Nos. (v) MCCB,415 V, AC, 50 Hz, 40 Amps rating, 4 pole, 36 kA having thermal magnetic release- -03 Nos. (vi) MCCB 32 Amps, 4 pole, 36 kA thermal magnetic release -02 Nos. (vii) Astronomical Time switch 20 Amps 24 hour programming type with ML-4 Contactor 70A, 415 Volt, three phase, coil operating voltage 230 Volt, three point Auto manual switch 15 Amps for bypass system with 63A 4P MCCB adjustable( 40 % to 100 %) Microprocessor release , 35KA comple incl necessary connection by using copper wire of size 25 Sqmm - 1 set (viii) Digital Multi-functional Meters for measuring current, voltage and frequency including CTs of suitable rating and class (ix) Indicator lamps RYB, LED type (Make : ABB/Legrand/Schneider/Other makes as specified in Appendix 'D' to Particular Specifications here-in-after.)
M&L providing PCC 1:2:4, type B-1 (using 20mm graded stone aggregate) for pedestal coping including use of necessary formwork to achieve fair finished surfaces complete all as specified and directed by Engineer-in Charge..
Supply, installing, testing and commissioning APFC panel of 70 KVAR with 6 steps (2x25+10+5+2+2+1) rating in different steps capacitor rating contactors switched through MCCBs of suitable rating, auto/manual switching arrangement complete all as specified and directed by Engineer-in Charge.
Supply and fixed in repairs 3 Phase Digital Multi-function Meter for measuring current, voltage and frequency including CTs of suitable rating and class, square shape, fixed to existing LT Panels complete all as specified and as directed.
M&L Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below normal ground level ) with the top edge of plate not less than 1.5 mtr below normal ground level, connected to GI wire 4mm by means of GI nuts, bolts, check nuts and washers, earth lead protected by 15mm dia GI pipe (light grade) and connected to main distribution board/earthing test point all as shown in Electrical Plate No 3 of SSR Part -I , including testing on completion all as specified and directed by EIC. (Notes: The unit rate quoted for the item shall deemed to include the following :- (i) Excavation & earth work in any type of soil strata;(ii) Plain cement concrete 1:3:6 , type C1 in pit/chamber; (iii) 80mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm c/c both ways ;(iv) PGI sheet funnel with wire mesh ; (v) GI watering pipe (medium grade) 20mm dia ; (vi) G.I. pipe 15mm dia for protection of earth lead including earth lead upto 7.50m length.(vii) charcoal dust and common salt 15 cm thick packed in alternate layers alround the earth plate electrode.)
M&L Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below normal ground level ) with the top edge of plate not less than 1.5 mtrs below normal ground level, connected to GI strip of size 32 x 6mm by means of GI nuts, bolts, check nuts and washers ; earth lead protected by 40mm dia GI pipe (light grade) and connected to main distribution board/earthing test point all as shown in Electrical Plate No 3 of SSR Part -I , including testing on completion all as specified and directed by EIC. (Notes: The unit rate quoted for the item shall deemed to include the following :- (i) Excavation & earth work in any type of soil strata;(ii) Plain cement concrete 1:3:6 , type C1 in pit/chamber; (iii) 80mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm c/c both ways ;(iv) PGI sheet funnel with wire mesh ; (v) GI watering pipe (medium grade) 20mm dia ; (vi) G.I. pipe 40mm dia for protection of earth lead including earth lead upto 7.50m length.(vii) charcoal dust and common salt 15 cm thick packed in alternate layers alround the earth plate electrode.)
M&L Chemical earthing (Compound Based earthing) having advance encapsulated compound based, CPRI tested , maintenance free , pipe in -pipe technology upgraded ( Zinc and alloy coated - Zinc coated (80-100) microns with pure zinc (99.9%) & alloy coating (200-250 microns) having the following features/characteristics and compliance. (Make : ASHLOK, MODEL-ASEEL-39- ZC & AC (76.3 mm Dia), 3 M LENGTH with back fill compound ELECTRODITE/ ABB or its equivalent specifications in other make as specified and directed) :- (a) Earthing system shall be confirming to IS :3034. The outer and inner pipe should be 76.2mm & 41.9 mm dia, 3 metre length, Zinc coated with additional special alloy coating 300 mm on the top side for additional protection of the terminal. The annular space between the pipes filled up with compact fill (CF) of crystalline conductive compound) . (b) The compact fill (CF) mixture which is machine pressed in the pipes should not disintegrate or collapse when outer pipes corrodes. The inner pipe should be extended with terminals for connectivity. (c ) The job includes digging the pit to a depth not less than 3 metre and refilling the same by Electrodite. (d) Back fill compound(Ground Enhancer) :The BFC should be eco-friendly. It should not contain environmentally hazardous material/metal having RoHS certification from NABL accredited lab . (e) The Earth pit should be provided with FRP earth pit cover for protection and safe guard of terminals. Complete all as specified and directed by Engineer- in- Charge. (f) In areas where soil condition is bad, good earth is to be filled in the excavated pit by mixing the same with BFC 2 or 4 bags extra per pit/unit. (g) The earthing values obtained shall be less than 1 ohm. (h) The manufacturer shall provide minimum 05 years warranty on each earth pit in terms of ohmic value. (j) Extra BFC bag will be measured and paid separately (j) The excavation, removing excavated material shall be deemed to be included in the unit rate quoted for the item
Supply only Back Fill Compound (BFC) Electrodite , 25 kg to a Bag complete all as specified and as directed.
Supply and fixing Galvanized iron strip 32X 6 mm burried in ground including connecting at ends & jointing complete all as specified and as directed.
Supply and fixing steel tubing (light grade), galvanised, 40mm bore size complete with all fittings , laid in floor or on wall for protection of earth strip complete all as specified and directed by Engineer-in-Charge.
M&L Earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level, connected to copper strip earthing lead of size 20 x 3 mm by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel , GI pipe (light grade) 40 mm bore for protection of earthing lead , connected to control board or main switch or as directed by Engineer -in-Charge including the following :- (i) Excavation & earth work in any type of soilstrata;(ii) Plain cement concrete 1:3:6 , type C1 in pit/chamber; (iii) 80mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm c/c both ways ;(iv) PGI sheet funnel with wire mesh ; (v) GI watering pipe (medium grade) 20mm dia ; (vi) G.I. pipe 25mm dia for protection of earth lead including earth lead upto 7.50m length; (vii) charcoal dust and common salt 15 cm thick packed in alternate layers alround the earth plate electrode.) ( NOTE : The earthing pit should be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed in AF Station.)
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep for taking out / laying of under ground cable, foundation of electric pole or stay and getting out in soft/loose soil complete all as specified and as directed..
Excavation in trenches not exceeding 1.5 mtr wide and exc. 1.5 mtr deep & n.exc 3.00 m deep for taking out / laying of under ground cable, foundation of electric pole or stay and getting out in soft soil complete all as specified and as directed...
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm in any type of soil (soft/loose or hard/dense) complete all as specified and directed by Engineer-in-Charge.
Removing excavated materials (soils) not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as directed by Engineer-in-Charge.
Dismantling and taking down including disconnecting unserviceable aluminium conductor steel reinforced (ACSR) from the pole/cross arm of any size, dia, type etc. complete all as directed by Engineer-in-Charge
M&L electric cable XLPE insulated, PVC sheathed, screened, PVC bedded, galvanized steel strip or wire armoured, heavy duty, LT 1100 volts grade with stranded aluminium conductor, laid in trenches/on wall/poles or laid in ducts/ drawn through protection pipe etc of the following cross-sectional area ,including provision of necessary cable glands, lugs and suitable size of M.S. saddle clips (wherever cable laid in ceilings / walls without cable duct) all as specified and directed by the Engineer-in-Charge :-
240 sq. mm x 3.5 core
150 sq. mm x 3.5 core
120 sq. mm x 3.5 core
95 sq. mm x 3.5 core
70 sq. mm x 3.5 core
50 sq. mm x 3.5 core
25 sq. mm x 3.5 core
16 sq. mm x 4 core
M&L for clean, dry river sand of approved quality for cushioning of electric cable laid in trenches / ducts all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, brick, common burnt clay, sub-class 'B' , designation 75 for cable protection all as specified and directed by the Engineer-in-Charge.
Supply and fixing on pole/wall or laid in trenches in replacement GI pipe (light grade), 40 mm bore size, for cable protection including all necessary fittings complete all as specified and directed by Engineer-in-Charge.
Supply and fixing on pole/wall or laid in trenches in replacement GI pipe (light grade), 50 mm bore size, for cable protection including all necessary fittings complete all as specified and directed by Engineer-in-Charge.
M&L providing PCC 1:2:4, type B2 (using 20mm graded stone aggregate) for pedestal, coping etc including necessary formwork, finished even and fair using extra cement all as specified and directed by Engineer-in-Charge.
M&L boring holes under road, pavement, hard standing etc by trenchless technology using ultra sounding technique and including necessary machine etc as per site requirement complete all as specified and directed by Engineer-in-Charge.
M&L in replacement Galvanised steel wire 4mm dia complete all as specified and directed by Engineer-in-Charge.
M&L for fixing in replacement cradles, hexagonal / rectangular, fabricated with galvenised steel wire 3.15 mm or 4 mm dia. all as specified and directed by Engineer-in-Charge..
M&L providing in replacement insulated synthetic mat suitable for 1.1 KV working pressure , size 2m x 1m x 12mm thick , including taking down old worn out insulated mat from various locations of E/M installations all as specified and directed by Engineer-in-Charge.
S&F in repairs Glow Sign board fabricated with aluminium frame and LED T/L for illumination, frame size 1800mm x 1200mm, 20mm thick complete for electric supply installations with alpha-numeric (words and letters) description written on it complete all as specified and as directed by Engineer-in-Charge..
S&F in replacement lightening Surge Arrestors (Expulsion type) complete with all fittings such as bolts, nuts, washers etc , transmission class, discharge capacity 65 kilo-amp all as specified and directed. (Make : Elpro/ Alstom/Oblum/Rastriya/ Atlas/Pactil)
Supply, install, testing and commissioning in replacement of 11KV outdoor type Polymer based Gang Operated Air Break (GOAB) switch, triple pole, suitable for vertical mounting complete with expulsion fuses, operating rod of GI pipe of suitable dia. and length as operating mechanism worked from ground level complete in both OFF and ON positions, for current rating upto 200 Amps, each pole consist of galvanised steel base HT insulators as per BSS / ISS, non-ferrous knife and spring loaded contacts, arcing horns of adequate section to brake magenetizing current of the transformers. All ferrous parts hot dip galvanised and non-ferrous parts heavily tinned to withstand weather complete all as specified and directed.. ( Make: Pactil / Southern Switchgear/ Universal/ BHEL/ ELPRO/ Rastriya).
All as per item No. 33.00 here-in-before, but Polymer based Gang Operated Air Break (GOAB) switch of current rating 400 Amps.
S&F in replacement dropout fuse unit complete set, suitable for 11 KV, HT outdoor and dropout type of capacity 200 Amps, including jumper connections with copper flexible designed jumper and testing and commissioning complete all as specified and directed by Engineer-in-Charge.
All as per item No. 35.00, but dropout fuse unit of current rating 400 Amps
S&F in replacement insulator pin type, porcelain, vitreous, white, brown or green including one galvnised mild steel spindle, two nos. galvanised iron washer and one galvnised iron nut, 150mm dia , 150mm height for 11000 volts grade all as specified and directed by Engineer-in-Charge.
S&F in replacement Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green; 'Two-in-series' assembly for tension with tension clamps for conductors, working pressure 11000 volts all as specified and directed by Engineer-in-Charge.
M/S Ali Trading Co
M/S BISWAS AND KUNDU CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .