Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.9 CrAccepted-Finance | ₹42.9 Cr | L1 | Accepted-Finance opened |
| 2 | L2₹43.5 CrAccepted-Finance | ₹43.5 Cr | L2 | Accepted-Finance opened |
| 3 | L3₹45.4 CrAccepted-Finance | ₹45.4 Cr | L3 | Accepted-Finance opened |
| Sl No | Description | Qty | Unit | Ms MAhesh Chand Gupta L1 | MS ANKIT CONSTRUCTION L3 | DHARIWAL TRADERS PRIVATE LIMITED L2 |
|---|---|---|---|---|---|---|
| 1.00 | Construction and commissioning of RCC INTZE type Over Head Service Reservoir of following capacity and staging as per the Scope of work and Technical specifications, consisting of the following main activities: - a) Topographic survey, preparation of site contour plan, conducting SBC test and its approval from department before construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc. c) OHSR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR. The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil. d) Providing and applying two coats of food grade epoxy paint on the inside surface on the top dome, edge beam and 600 mm height of the vertical wall. e) Conducting successfully hydro test and water tightness test as per I.S. code. f) Providing and applying three coats of anti-carbonation paint on the top surface of the Top Dome. g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc.. h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder from top dome/Slab to bottom dome/Slab inside container. i) Providing and fixing of MS section ladder from the last landing to balcony having railing all around it and MS ladder with safety cage from balcony to top dome/slab. j) Providing and fixing water level indicator (float type). | 1,50,000 | Litre | 2 ₹3 L | 35 ₹52.5 L | 25 ₹37.5 L |
| 2.00 | Supply of Painted/ Powder coated galvanized steel Flush Fire doors of Pacific make of 2 hrs. Fire rating and tested in accordance with IS 3614 Part 2 & BS 476 Part 22 as per prototype tested and certified at CBRI Roorkee or equivalent laboratory. Door frames to be double rebate profile of 143 x 57mm manufactured from 1.6mm galvanized steel sheet, profile to have bending radius of 1.4 mm supplied in assembled form ready to install at site. Door Shutter in 46mm +2 mm thick manufactured from 1.2mm galvanized steel sheets, lock seam jointed at stile edges to form a double skin fully flush shell. Infilled honeycomb insulation material to be provided for structural rigidity & additional reinforcements & sound Insulation, The internal construction of the door should be appropriate for all hardware fixtures (SS Ball BearingHinges-4"x3"X3mmGeze,Door Closer, Dead LockWith 70mm EPC,Handle-300X19mm, Vision Panel,Flush Bolt etc.) as required, vision panel grooves wherever applicable shall be provided as per recommendations with beading and screw. (Hardwares to be paid seperately as per your requirement.) Size: 1500 x 2100mm- Double Leaf Size: 1500 x 2100mm- Double Leaf Hardwares SS Ball Bearing Hinges- 4" x 3" x 3mm- Geze make Door Closer- Geze make Dead Lock with 70mm EPC- Geze make Handle- 300 x 19mm- Geze make Vision panel- 6mm (2 hour fire rated)- 200 x 300mm- schott/ pyroguard make Flush Bolt- 300mm- Geze make Fastener | 12 | Each | 30,000 ₹3.6 L | 50,000 ₹6 L | 30,000 ₹3.6 L |
| 3.00 | Desisigning Development providing and fixing of Acrylic Sandwich way signages in different building. The various different sized signages like building directory,facilties, room nos. etc. are made out of A grade Acast or equivalent brands 5mm thick transparent acrylic sheet at back and 3mm thick on front side. The eco-print on 3M IJ 15-10 monomeric calandared Vinyl film sheet of approved colour pattern and shade is sandwich between two acrylic sheets with required number and size of stainless steel studs and fittings, The outer edges are tapered and finished smooth. The developer has to design the signages for different buildings as per requirement of the client and got the design and sample approved from competent authority before going in to actual execution at site. Basic dataa for clients requirement would be provided by the department. | 835.5 | Sqft | 150 ₹1.3 L | 880 ₹7.4 L | 100 ₹83,550 |
| 4.00 | This should be a hermetically sealed, single sliding door of 2.1 (H)X 1.8 m(W), The controller should be capable of being operated by elbow switches/foot switches as well as touch less sensor.The track should be of Aluminum and the running surface for the top rollers should be suitably angled to reduce resistance to movement. The door leaf should be hung by means of hard plastic rollers of high quality with double bearing at the top. Rollers should be provided under the Aluminium track to enable smooth and noiseless movement. Opening and closing of the door should be microprocessor controlled electromechanical movement. The door material should be of HPL Color should match the interior and care should be taken to make the leaf strong and light weight. One should be able to open and close the door effortlessly incase of failure of automatic mechanism. Door opening handle should be strong and sturdy. Material should be of SS (gloss finish). Should be provided with high quality cylindrical lock. Door leaf should have high quality synthetic rubber gasket with long life to ensure hermetic sealing (to maintain air pressure differential). Air tightness 99.99% at a pressure of 100Pa.The finished floor on either side of the door should be perfectly level (maximum permissible difference +1mm). The overall thickness of the finished door should be 60mm. The inner part of the door should be filled with CFC free polyurethane foam thickness of 52 mm nearby. (Sealed airtight to prevent further ingress of any microbial organism). The door and controls should comply with IEE regulation. SDA04 automation with battery backup PMDC motor. Door should be with vision window 300 mm x 300 mm with double glazed panels and hermetically sealed. Door movement should have minimum noise. The starting time after receiving the signal should be adjustable between 0.5 to 20 seconds. Test certificate for hermetically sealed door frame (factory test certificate) should be enclosed with the pre dispatch documents. | 6 | Nos | 1,50,000 ₹9 L | 55,500 ₹3.3 L | 35,000 ₹2.1 L |
| 5.00 | Supply, installation, testing and commissioning of UPS with isolation transformer & battery for backup, having three phases input three phase output. Online double conversion VFI-SS-111 technology, with sinusoidal wave form, architecture (standalone of distributed parallel up to 8 units), having input characteristics i.e. input voltage (380v, 400v, 415v, 3Ph+N+PE), input frequency (45 -65 Hz), input voltage range (Ph - Ph) : (half load 208v -467v/ full load 312v - 467v), total harmonic distortion of input current < 3% (at full linear load), compatibility with diesel generators configurable for synchronization between the input and output frequencies even for high frequency variations, input power factor > 0.99, having output characteristics i.e. output voltage (380v, 400v, 415v, 3Ph+N (adjustable from front panel), efficiency up to 96%, efficiency in ECO mode up to 98.5%, output frequency (nominal) 50 /60 Hz 0.01% free run (adjustable from front panel), crest factor 3 : 1, total harmonic distortion of output voltage < 2 % (at full linear load), output power factor 0.9, output voltage tolerance ± 1%, built in automatic and maintenance bypass, inbuilt isolation transformer, battery type (VRLA - AGM maintenance free). Communication & management i.e. 50 KVA (3 phase input & 3 phase output) For 30 minute backup, min. 30000 VAH | 1 | Each | 6,50,000 ₹6.5 L | 4,35,000 ₹4.3 L | 12,00,000 ₹12 L |
| 6.00 | Supply, installation, testing and commissioning of EPABX system consist, no. of extension, no of junction, no. of expandable eport, operating console, current on max. load with ISDN compatible of approved make and labor as required as per specifications. EPABX system consists of 64 nos. extensions, 16 nos of junction & upto 128 nos. of expandable eport, with one operating console, 3 Amp max. current | 1 | Each | 1,80,000 ₹1.8 L | 1,55,000 ₹1.6 L | 2,50,000 ₹2.5 L |
| 7.00 | Supply, installation, testing and commissioning of telephone instrument as approved by architect (Siemens/ Panasonic/ Tata/ BPL) | 100 | Each | 1,950 ₹1.9 L | 2,500 ₹2.5 L | 1,000 ₹1 L |
Updated dates
Tender Value
₹46.5 Cr
EMD Value
₹93 L
Closing Date
10 Nov 2025, 6:00 pmClosed
Chief Engineer M and H Jaipur
Chief Engineer M and H Jaipur
Construction of New District Hospital (100 Bed) at Bali, District Pali (Including Internal Electrical Work)
2025_MEDIC_505860_3
CE NIT No. 18/2025-26 of CE M and H Jaipur
Open Tender
Civil Works - Buildings
720 days
Pali
Please refer Tender documents.
5 documents required · 5 mandatory
₹5,000
NEFT/RTGS/Any Other Money Transfer
₹93 L
24 Nov 2025
18 Oct 2025
11 Nov 2025
18 Oct 2025
10 Nov 2025
18 Oct 2025
Amount
Construction and commissioning of RCC INTZE type Over Head Service Reservoir of following capacity and staging as per the Scope of work and Technical specifications, consisting of the following main activities: - a) Topographic survey, preparation of site contour plan, conducting SBC test and its approval from department before construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc. c) OHSR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR. The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil. d) Providing and applying two coats of food grade epoxy paint on the inside surface on the top dome, edge beam and 600 mm height of the vertical wall. e) Conducting successfully hydro test and water tightness test as per I.S. code. f) Providing and applying three coats of anti-carbonation paint on the top surface of the Top Dome. g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc.. h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder from top dome/Slab to bottom dome/Slab inside container. i) Providing and fixing of MS section ladder from the last landing to balcony having railing all around it and MS ladder with safety cage from balcony to top dome/slab. j) Providing and fixing water level indicator (float type).
Supply of Painted/ Powder coated galvanized steel Flush Fire doors of Pacific make of 2 hrs. Fire rating and tested in accordance with IS 3614 Part 2 & BS 476 Part 22 as per prototype tested and certified at CBRI Roorkee or equivalent laboratory. Door frames to be double rebate profile of 143 x 57mm manufactured from 1.6mm galvanized steel sheet, profile to have bending radius of 1.4 mm supplied in assembled form ready to install at site. Door Shutter in 46mm +2 mm thick manufactured from 1.2mm galvanized steel sheets, lock seam jointed at stile edges to form a double skin fully flush shell. Infilled honeycomb insulation material to be provided for structural rigidity & additional reinforcements & sound Insulation, The internal construction of the door should be appropriate for all hardware fixtures (SS Ball BearingHinges-4"x3"X3mmGeze,Door Closer, Dead LockWith 70mm EPC,Handle-300X19mm, Vision Panel,Flush Bolt etc.) as required, vision panel grooves wherever applicable shall be provided as per recommendations with beading and screw. (Hardwares to be paid seperately as per your requirement.) Size: 1500 x 2100mm- Double Leaf Size: 1500 x 2100mm- Double Leaf Hardwares SS Ball Bearing Hinges- 4" x 3" x 3mm- Geze make Door Closer- Geze make Dead Lock with 70mm EPC- Geze make Handle- 300 x 19mm- Geze make Vision panel- 6mm (2 hour fire rated)- 200 x 300mm- schott/ pyroguard make Flush Bolt- 300mm- Geze make Fastener
Desisigning Development providing and fixing of Acrylic Sandwich way signages in different building. The various different sized signages like building directory,facilties, room nos. etc. are made out of A grade Acast or equivalent brands 5mm thick transparent acrylic sheet at back and 3mm thick on front side. The eco-print on 3M IJ 15-10 monomeric calandared Vinyl film sheet of approved colour pattern and shade is sandwich between two acrylic sheets with required number and size of stainless steel studs and fittings, The outer edges are tapered and finished smooth. The developer has to design the signages for different buildings as per requirement of the client and got the design and sample approved from competent authority before going in to actual execution at site. Basic dataa for clients requirement would be provided by the department.
This should be a hermetically sealed, single sliding door of 2.1 (H)X 1.8 m(W), The controller should be capable of being operated by elbow switches/foot switches as well as touch less sensor.The track should be of Aluminum and the running surface for the top rollers should be suitably angled to reduce resistance to movement. The door leaf should be hung by means of hard plastic rollers of high quality with double bearing at the top. Rollers should be provided under the Aluminium track to enable smooth and noiseless movement. Opening and closing of the door should be microprocessor controlled electromechanical movement. The door material should be of HPL Color should match the interior and care should be taken to make the leaf strong and light weight. One should be able to open and close the door effortlessly incase of failure of automatic mechanism. Door opening handle should be strong and sturdy. Material should be of SS (gloss finish). Should be provided with high quality cylindrical lock. Door leaf should have high quality synthetic rubber gasket with long life to ensure hermetic sealing (to maintain air pressure differential). Air tightness 99.99% at a pressure of 100Pa.The finished floor on either side of the door should be perfectly level (maximum permissible difference +1mm). The overall thickness of the finished door should be 60mm. The inner part of the door should be filled with CFC free polyurethane foam thickness of 52 mm nearby. (Sealed airtight to prevent further ingress of any microbial organism). The door and controls should comply with IEE regulation. SDA04 automation with battery backup PMDC motor. Door should be with vision window 300 mm x 300 mm with double glazed panels and hermetically sealed. Door movement should have minimum noise. The starting time after receiving the signal should be adjustable between 0.5 to 20 seconds. Test certificate for hermetically sealed door frame (factory test certificate) should be enclosed with the pre dispatch documents.
Supply, installation, testing and commissioning of UPS with isolation transformer & battery for backup, having three phases input three phase output. Online double conversion VFI-SS-111 technology, with sinusoidal wave form, architecture (standalone of distributed parallel up to 8 units), having input characteristics i.e. input voltage (380v, 400v, 415v, 3Ph+N+PE), input frequency (45 -65 Hz), input voltage range (Ph - Ph) : (half load 208v -467v/ full load 312v - 467v), total harmonic distortion of input current < 3% (at full linear load), compatibility with diesel generators configurable for synchronization between the input and output frequencies even for high frequency variations, input power factor > 0.99, having output characteristics i.e. output voltage (380v, 400v, 415v, 3Ph+N (adjustable from front panel), efficiency up to 96%, efficiency in ECO mode up to 98.5%, output frequency (nominal) 50 /60 Hz 0.01% free run (adjustable from front panel), crest factor 3 : 1, total harmonic distortion of output voltage < 2 % (at full linear load), output power factor 0.9, output voltage tolerance ± 1%, built in automatic and maintenance bypass, inbuilt isolation transformer, battery type (VRLA - AGM maintenance free). Communication & management i.e. 50 KVA (3 phase input & 3 phase output) For 30 minute backup, min. 30000 VAH
Supply, installation, testing and commissioning of EPABX system consist, no. of extension, no of junction, no. of expandable eport, operating console, current on max. load with ISDN compatible of approved make and labor as required as per specifications. EPABX system consists of 64 nos. extensions, 16 nos of junction & upto 128 nos. of expandable eport, with one operating console, 3 Amp max. current
Supply, installation, testing and commissioning of telephone instrument as approved by architect (Siemens/ Panasonic/ Tata/ BPL)
Bidder Name
Amount
Ms MAhesh Chand Gupta (GSTN-08AAQFM8282Q1Z3) BID ID -3349684
MS ANKIT CONSTRUCTION (GSTN-08ABLFA3541Q1ZY) BID ID -3361268
DHARIWAL TRADERS PRIVATE LIMITED (GSTN-08AAGCD7338F1ZK) BID ID -3361315
DHARIWAL TRADERS PRIVATE LIMITED (BID ID -3361315)
MS ANKIT CONSTRUCTION (BID ID -3361268)
DHARIWAL TRADERS PRIVATE LIMITED (BID ID -3361315)
MS ANKIT CONSTRUCTION (BID ID -3361268)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 16.30 MB
Tendernotice_2.pdf
PDF • 1.59 MB
Tendernotice_3.pdf
PDF • 0.59 MB
Tendernotice_4.pdf
PDF • 3.40 MB
Tendernotice_5.pdf
PDF • 2.92 MB
9.pdf
Tender Documents • 11.57 MB
BOQ_901257.xls
BOQ • 1.01 MB
Download all tender documents and submit your bid