Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹21.8 L+₹14,948 (0.69%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹26.6 L+₹5.0 L (22.9%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹28.6 L+₹6.9 L (32.1%)Rejected-Finance NOT FOUND | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹28.6 L+₹7.0 L (32.5%)Rejected-Finance | L5 | Rejected-Finance Other than L1 |
| Sl No | Description | Qty | Unit | AMBIKA ENTERPRISES L2 | shiv shanker enterprises L4 | NISHTHA BUILDERS L1 | M/S GOYAL CONSTRUCTIONS L5 | M/S KAVYA ENTERPRISES L3 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, etc. (except light fittings), removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and directed. | 1,660 | PER POINT | 2 ₹3,320 | 5 ₹8,300 | 1 ₹1,660 Lowest | 2 ₹3,320 | 1 ₹1,660 Lowest |
| 2.00 | Taking down/out unserviceable Wires only from the existing Sub-main Wiring of any type and any description, without disturbing Existing Conduit, complete all as specified and directed. | 1,800 | RM | 2 ₹3,600 | 5 ₹9,000 | 1 ₹1,800 Lowest | 2 ₹3,600 | 1 ₹1,800 Lowest |
| 3.00 | Taking down carefully by unscrewing from boards/outlet boxes, unserviceable fittings and fixtures such as switches, sockets, ceiling roses, lamp holders, regulators, call bells, plug tops, etc. and removal from site complete all as specified and directed.
(NOTE: This item is to be measured only when only existing fitting/fixture is required to be replaced. Not to be combined with taking down of point wiring under Item No 01 here-in-before). | 1,200 | Each | 2 ₹2,400 | 5 ₹6,000 | 1 ₹1,200 Lowest | 2 ₹2,400 | 1 ₹1,200 Lowest |
| 4.00 | Taking down carefully by unscrewing from board / outlet boxes / walls, unserviceable internal light fittings & bulk head fittings, etc any type for reuse or removal from site complete all as specified and directed. | 1,915 | Each | 2 ₹3,830 | 5 ₹9,575 | 1 ₹1,915 Lowest | 2 ₹3,830 | 1 ₹1,915 Lowest |
| 5.00 | Taking down carefully unserviceable bldg security lights, gate lights, bollards & flood lights, of any type, after disconnecting electrical connectiosn and removal from site complete all as specified and directed. | 104 | Each | 5 ₹520 | 10 ₹1,040 | 1 ₹104 Lowest | 2 ₹208 | 1 ₹104 Lowest |
| 6.00 | Taking down of unserviceable Distrubution Boards, any type or size including MCCB/RCCB/MCBs and disconnecting the serviceable MCCBs/MCBs and keeping in safe custody for reuse or removal from site complete all as specified and directed.
(NOTE: Measurement shall be considered only for the DBs) | 128 | Each | 5 ₹640 | 10 ₹1,280 | 1 ₹128 Lowest | 2 ₹256 | 1 ₹128 Lowest |
| 7.00 | Taking down unsv MCBs, any type for reuse or removal from site complete all as specified & directed.
(NOTE: This item is to be measured only when only existing MCBs are required to be replaced. Not to be combined with taking down of DB under Item No 06 here-in-before). | 45 | Each | 5 ₹225 | 5 ₹225 | 1 ₹45 Lowest | 2 ₹90 | 1 ₹45 Lowest |
| 8.00 | Taking down unsv MCCBs, any type for reuse or removal from site complete all as specified & directed.
(NOTE: This item is to be measured only when only existing MCCBs are required to be replaced. Not to be combined with taking down of DB under Item No 06 here-in-before). | 15 | Each | 5 ₹75 | 5 ₹75 | 1 ₹15 Lowest | 2 ₹30 | 1 ₹15 Lowest |
| 9.00 | M&L for concealed type point wiring with FRLS-H PVC insulated and unsheathed, multi stranded copper conductor cable 1100 Volts grade, single core, laid in existing PVC conduit complete with all fittings and accessories, fixed to walls/ceiling, including mild steel terminal boxes 1.20 mm thick conforming to IS-5133 (Part-I) with 2.0 mm thick phenolic laminated sheet top cover (ISI Marked) for mounting switches / regulator / bell push / sockets, etc and including FRLS-H PVC insulated and unsheathed multi stranded copper conductor cable 1100 Volts grade, single core, earth continuity conductor connected to common earth dolly, complete all as specified and directed for the following :-
(NOTE: Wiring shall be done in existing PVC conduit. Quoted rate shall be excusive of the cost of pvc conduit) | - | - | - | - | - | - | - |
| 9.01 | for one light / bell / ceiling fan / exhaust fan point controlled by one way switch with 1.50 Sq. mm wire for mains & neutral | 180 | Point | 100 ₹18,000 Lowest | 205 ₹36,900 | 100 ₹18,000 Lowest | 220 ₹39,600 | 190 ₹34,200 |
Tender Value
₹38 L
EMD Value
₹76,000
Closing Date
7 Aug 2025, 6:00 pmClosed
GE (AF) SIRSA
GE (AF) SIRSA, HARYANA-125055
REPAIR/MAINT OF INTERNAL ELECTRIFICATION SYSTEM INCL REPLACEMENT OF UNSERVICEABLE LIGHT FITTINGS, DBs, METER PANELS, EARTHING, ETC FOR MARRIED ACCN OF DOMESTIC AREA AT AF STN SIRSA
2025_MES_720800_1
GE/SRA/T-37/2025-26
Open Tender
Miscellaneous Works
Item Rate
300 days
GE (AF) SIRSA
PLEASE REFER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (AF) SIRSA
₹76,000
Yes
27 Aug 2025
16 Jul 2025
8 Aug 2025
16 Jul 2025
7 Aug 2025
26 Jul 2025
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, etc. (except light fittings), removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and directed.
Taking down/out unserviceable Wires only from the existing Sub-main Wiring of any type and any description, without disturbing Existing Conduit, complete all as specified and directed.
Taking down carefully by unscrewing from boards/outlet boxes, unserviceable fittings and fixtures such as switches, sockets, ceiling roses, lamp holders, regulators, call bells, plug tops, etc. and removal from site complete all as specified and directed. (NOTE: This item is to be measured only when only existing fitting/fixture is required to be replaced. Not to be combined with taking down of point wiring under Item No 01 here-in-before).
Taking down carefully by unscrewing from board / outlet boxes / walls, unserviceable internal light fittings & bulk head fittings, etc any type for reuse or removal from site complete all as specified and directed.
Taking down carefully unserviceable bldg security lights, gate lights, bollards & flood lights, of any type, after disconnecting electrical connectiosn and removal from site complete all as specified and directed.
Taking down of unserviceable Distrubution Boards, any type or size including MCCB/RCCB/MCBs and disconnecting the serviceable MCCBs/MCBs and keeping in safe custody for reuse or removal from site complete all as specified and directed. (NOTE: Measurement shall be considered only for the DBs)
Taking down unsv MCBs, any type for reuse or removal from site complete all as specified & directed. (NOTE: This item is to be measured only when only existing MCBs are required to be replaced. Not to be combined with taking down of DB under Item No 06 here-in-before).
Taking down unsv MCCBs, any type for reuse or removal from site complete all as specified & directed. (NOTE: This item is to be measured only when only existing MCCBs are required to be replaced. Not to be combined with taking down of DB under Item No 06 here-in-before).
M&L for concealed type point wiring with FRLS-H PVC insulated and unsheathed, multi stranded copper conductor cable 1100 Volts grade, single core, laid in existing PVC conduit complete with all fittings and accessories, fixed to walls/ceiling, including mild steel terminal boxes 1.20 mm thick conforming to IS-5133 (Part-I) with 2.0 mm thick phenolic laminated sheet top cover (ISI Marked) for mounting switches / regulator / bell push / sockets, etc and including FRLS-H PVC insulated and unsheathed multi stranded copper conductor cable 1100 Volts grade, single core, earth continuity conductor connected to common earth dolly, complete all as specified and directed for the following :- (NOTE: Wiring shall be done in existing PVC conduit. Quoted rate shall be excusive of the cost of pvc conduit)
for one light / bell / ceiling fan / exhaust fan point controlled by one way switch with 1.50 Sq. mm wire for mains & neutral
for one 5/6 Amps socket outlet on independent board, with 1.50 Sq. mm wire for mains & neutral
for one 5/6 Amps Pin Socket Outlet on the same board, with 1.50 Sq. mm wire for mains & neutral
for one 15-20 Amps socket outlet on independent board, with 2.50 Sq. mm wire for mains & neutral
for one 25-32 Amps AC or geyser outlet, on independent board, with 4.0 Sq. mm wire for mains & neutral
M&L for concealed type point wiring with FRLS-H PVC insulated and unsheathed, multi stranded copper conductor cable 1100 Volts grade, single core, laid in existing PVC conduit complete with all fittings and accessories, fixed to walls/ceiling, including mild steel terminal boxes 1.20 mm thick conforming to IS-5133 (Part-I) for mounting MODULAR TYPE SWITCHES / REGULATOR / BELL PUSH / SOCKETS, ETC and including FRLS-H PVC insulated and unsheathed multi stranded copper conductor cable 1100 Volts grade, single core, earth continuity conductor connected to common earth dolly, complete all as specified and directed for the following :- (NOTE: Wiring shall be done in existing PVC conduit. Quoted rate shall be excusive of the cost of pvc conduit. Modular cover plate & frame shall be measured and paid seperately)
for one light / bell / ceiling fan / exhaust fan point controlled by one way switch with 1.50 Sq. mm wire for mains & neutral
for one 5/6 Amps socket outlet on independent board, with 1.50 Sq. mm wire for mains & neutral
for one 5/6 Amps Pin Socket Outlet on the same board, with 1.50 Sq. mm wire for mains & neutral
for one 15-20 Amps socket outlet on independent board, with 2.50 Sq. mm wire for mains & neutral
for one 25-32 Amps AC or geyser outlet, on independent board, with 4.0 Sq. mm wire for mains & neutral
M&L concealed Point Wiring with 1100 Volt PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable for main & neutral and 1100 Volt PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable (Green Colour) as Earth Continuity Wire, drawn through and including Rigid Non-metallic PVC Conduit 19/20 mm in size, medium grade, ISI marked and its Accessories in Concealed (Partly)/ Surface (Partly) with necessary grouting of required size and depth on Wall and Making Good in Cement Mortar 1:3, providing PVC Gang Box (minimum 2.0mm thick)/Sunk GI Terminal Box (1.2mm thick) of suitable size( as required) duly painted with Red Oxide Metal Primer with 2.0mm thick Phenolic Laminated Sheet Top Cover (as per Site requirement) for mounting Switches, Sockets, Fan Regulators, Sockets, etc with Earth Continuity Wire connected to Common Earth dolly complete all as specified and as directed for the folowing:- (NOTES :- (i) Where tube light fitting is to be fitted/ suspended, CI Circular boxes shall be provided with the PVC Pipes in the ceiling & the unit rate shall be deemed to be included for the same. (ii) Quoted rate shall be deemed to be inclusive of the cost of terminal box & laminate cover. (iii) Cost of cutting chases for concealed wiring and making good surfaces with cement plaster and putty shall be deemed to be inclusive in the quoted rates. No claim in this regard shall be entertained at a later stage)
for one light / bell / ceiling fan / exhaust fan point controlled by one way switch with 1.50 Sq. mm wire for mains & neutral
for one 5/6 Amps socket outlet on independent board, with 1.50 Sq. mm wire for mains & neutral
for one 5/6 Amps Pin Socket Outlet on the same board, with 1.50 Sq. mm wire for mains & neutral
for one 15-20 Amps socket outlet on independent board, with 2.50 Sq. mm wire for mains & neutral
for one 25-32 Amps AC or geyser outlet, on independent board, with 4.0 Sq. mm wire for mains & neutral
M&L concealed Point Wiring with 1100 Volt PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable for main & neutral and 1100 Volt PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable (Green Colour) as Earth Continuity Wire, drawn through and including Rigid Non-metallic PVC Conduit 19/20 mm in size, medium grade, ISI marked and its Accessories in Concealed (Partly)/ Surface (Partly) with necessary grouting of required size and depth on Wall and Making Good in Cement Mortar 1:3, providing Sunk GI Terminal Box (1.2mm thick) of suitable size (as required) for mounting MODULAR TYPE Switches, Sockets, Fan Regulators, Sockets, etc with Earth Continuity Wire connected to Common Earth dolly complete all as specified and as directed for the folowing:- (NOTES :- (i) Where tube light fitting is to be fitted/ suspended, CI Circular boxes shall be provided with the PVC Pipes in the ceiling & the unit rate shall be deemed to be included for the same. (ii) Quoted rate shall be deemed to be inclusive of the cost of terminal box. Modular cover plate & frame shall be measured and paid seperately (iii) Cost of cutting chases for concealed wiring and making good surfaces with cement plaster and putty shall be deemed to be inclusive in the quoted rates. No claim in this regard shall be entertained at a later stage)
for one MODULAR TYPE light / bell / ceiling fan / exhaust fan point controlled by one way switch with 1.50 Sq. mm wire for mains & neutral
for one MODULAR TYPE 5/6 Amps socket outlet on independent board, with 1.50 Sq. mm wire for mains & neutral
for one MODULAR TYPE 5/6 Amps Pin Socket Outlet on the same board, with 1.50 Sq. mm wire for mains & neutral
for one MODULAR TYPE 15-20 Amps socket outlet on independent board, with 2.50 Sq. mm wire for mains & neutral
for one MODULAR TYPE 25-32 Amps AC or geyser outlet, on independent board, with 4.0 Sq. mm wire for mains & neutral
S&F Sub-main Wiring with 2-Runs of 1.50 Sqmm (nominal area) 1100 Volt, PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable and 1-Run of 1.50 Sqmm (nominal area) 1100 Volt, PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable (Green Colour) as Earth Continuity Wire along with the Wiring drawn in PVC CONDUIT complete all as specified and as directed. (NOTE: The wires shall be provided in existing conduit. Quoted rates shall be exclusive of the cost of conduits. Three runs of wire shall be considered as one unit)
All as per item No 13 above, but sub main wiring with 2 runs of 2.50 sqmm wires for mains and one run of 2.50 sqmm wire for earth continuity drawn in PVC CONDUIT complete all as specified & as directed. (NOTE: The wires shall be provided in existing conduit. Quoted rates shall be exclusive of the cost of conduits. Three runs of wire shall be considered as one unit)
All as per item No 13 above, but sub main wiring with 2 runs of 4.0 sqmm wires for mains and one run of 4.0 sqmm wire for earth continuity drawn in PVC CONDUIT complete all as specified and as directed. (NOTE: The wires shall be provided in existing conduit. Quoted rates shall be exclusive of the cost of conduits. Three runs of wire shall be considered as one unit)
All as per item No 13 above, but sub main wiring with 2 runs of 6.0 sqmm wires for mains and one run of 6.0 sqmm wire for earth continuity drawn in PVC CONDUIT complete all as specified and as directed. (NOTE: The wires shall be provided in existing conduit. Quoted rates shall be exclusive of the cost of conduits. Three runs of wire shall be considered as one unit)
All as per item No 13 above, but sub main wiring with 2 runs of 10.0 sqmm wires for mains and one run of 10.0 sqmm wire for earth continuity drawn in PVC CONDUIT complete all as specified & as directed. (NOTE: The wires shall be provided in existing conduit. Quoted rates shall be exclusive of the cost of conduits. Three runs of wire shall be considered as one unit)
S&F in repairs PVC electrical conduit, 25 mm dia, MMS type, medium grade incl all fittings and accessories complete all as specified and directed.
S&F in repairs PVC Casing caping pipe, 25 mm size, MMS type, medium grade incl all fittings and accessories complete all as specified and directed.
S&F new Switch piano, flush type, 6 Amps, single pole, one way complete all as specified and directed.
S&F new Modular Switch 1 way 6 Amps, 1 module complete all as specified and directed.
S&F new Switch piano, flush type, 16 Amps, single pole, one way complete all as specified and directed.
S&F new Modular Switch 1 way, 16 Amps, 1 module complete all as specified and directed.
S&F new socket outlet, flush type, 6 Amps, 2-in-1, multi-purpose 5 pin type complete all as specified and directed.
S&F new Modular Socket, 6 Amps, 3 pin type, 2 module complete all as specified and directed.
S&F new socket outlet, flush type, 16 Amps, 2-in-1, multi-purpose 5 pin type complete all as specified and directed.
S&F new Modular Socket, 6/16 Amps, 2 module, 2/3 pin combined type complete all as specified and directed.
S&F new switch socket combination outlet, flush type, 6 Amps, 2-in-1, 5 pin type complete all as specified and directed.
S&F new switch socket combination outlet, flush type, 6/16 Amps, 2-in-1, 5 pin type complete all as specified and directed.
S&F new Bell push, flush type, 6 Amps complete all as specified and directed.
S&F new Modular Bell push 6A, 2 module complete all as specified and directed.
S&F new Fan regulator, 5 step, 120 watt, 230 volts, single pole complete all as specified and directed.
S&F new Modular Fan regulator, 5 step, 120 watt, 2 module, 230 volts, single pole complete all as specified and directed.
S&F new Modular Fan regulator, 5 step, 120 watt, 1 module, 230 volts, single pole complete all as specified and directed.
S&F new Call bell, ding dong type, AC 230/240 volts, single pole complete all as specified and directed.
S&F new Call bell, Musical type, AC 230/240 volts, single pole complete all as specified and directed.
S&F new Ceiling rose, 3 terminals, 230 volts, surface type, bakelite/polycarbonate, isolated body complete all as specified and directed.
S&F new lamp holder with back plate suitable for batten fittings or to be mounted on walls complete all as specified and directed.
S&F in repair Phenolic laimated Sheet, 2mm thick for mounting switches, sockets, fan regulator etc of size 200 x 150 x 50 mm including cutting for mounting of switches, sockets, etc complete all as specified and as directed. (NOTE: This item shall not be measured for new point wiring)
All as per Item No 43 above, but with 2 mm thick Phenolic laminated sheet cover of size 250 x 200 x 50 mm complete. (NOTE: This item shall not be measured for new point wiring)
All as per item No 43 above, but with 2 mm thick Phenolic laminated sheet cover of size 350 x 300 x 50 mm complete. (NOTE: This item shall not be measured for new point wiring)
S&F new Modular type White cover plate with frame 1/2 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 3 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 4 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 6 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 8 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 12 module complete all as specified and directed.
Supply, assembling & fixing in repairs Modular MCB protected Power Unit comprising of following accessories :- (i) Powder Coated Steel terminal box, 06 module - 01 No (ii) Modular Cover Plate with Frame, 06 Module - 01 No (iii) 16 Amps 3 Pin Modular Socket, 02 module - 01 No (iv) 16 Amps Plug Top - 01 No (v) 25 Amps Motor Starter, 02 Module - 01 No (vi) 25 Amps, Single pole Mini MCB, 10kA - 01 No
Supplying, assembling and fixing modular AC power unit comprising of 01 No 16 Amps socket and 01 No 32 Amps SP MCB, 3 modules along with GI metallic flush box, cover plate and frame duly concealed in wall incl dismantling of existing power unit complete all as specified and directed. NOTE: Quoted rate shall be deemed to include for the cost of MCB, socket, GI flush box, cover plate & frame. Concealed conduit wiring shall be measured seperately.
S&F in repairs 32 Amps modular motor starter with cover plate & frame, 2 modules along with GI metallic flush box duly concealed in wall complete all as specified and directed. NOTE: Quoted rate shall be deemed to include for the cost of cover plate & frame and GI flush box alongwith starter. Concealed conduit wiring shall be measured seperately.
Re-fixing of serviceable light fitting, any type, after minor repairs or replacement of drivers including necessary electric connection & testing complete all as specified and directed.
S&F LED Bulkhead fitting 09/10 watt, with IP65 degree of protection and with impact resistance of IK-08, mounted on wall /ceiling connected with insulated unsheathed flexible copper wire of suitable size complete all as specified and directed.
S&F wall light/fixture light made up of high grade engineering plastic material suitable for & incl 9 W LED lamp B22 base with all accessories complte all as required and directed. (MAKE: HAVELLS (FLORET) Cat No : LHFHCHE1TL1W020 or similar model in other makes specified in tender)
S&F wall light/fixture, stainless Steel brushed nickle finish fixture with opal Glass diffuser suitable for & incl 9 watt LED lamp B22 Base with all accessories complte all as required and directed. (MAKE- HAVELLS (Florentine WL 1LS B22 SS) Cat Part No-LHFOAJE1TZ1I060 or similar model in other makes specified in tender)
S&F surface mounted LED luminaire, 1 X 20 Watt in aluminium housing, 100 lumen/watt, operating voltage 180-270 V, with acrylic/polycarbonate difuser & integrated constant current electronic driver complete with all other accessories internally prewired and including connecting up with three core flexible copper wire of suitable size complete all as specified and directed.
-ditto- as per Item No. 73 but of 1 X 18/20 Watt capacity in polycarbonate housing with lumen output not less than 100 lumen per watt
-ditto- as per Item No. 73 but of 1 X 9/10 Watt capacity in polycarbonate housing with lumen output not less than 100 lumen per watt
-ditto- as per Item No. 73 but of 1 X 05 Watt capacity in polycarbonate housing with lumen output not less than 100 lumen per watt
S&F recess mounted slim-fit downlighter, round or square, having glare free frosted diffuser, operating voltage 180-270V, with constant current electronic driver complete with all accessories with and including 15 Watt LED and including all accessories, mounting frame etc and connecting up with three core flexible copper conductor wire of adequate size complete all as specified and directed.
-ditto- as per Item No. 76 but recess mounted LED downlighter of capacity 12 Watt
-ditto- as per Item No. 76 but surface mounted LED downlighter of capacity 15 Watt
-ditto- as per Item No. 76 but surface mounted LED downlighter of capacity 12 Watt
S&F recess mounted spot light, with pressure die cast aluminium heat sink, with COB LED, 05-07 Watt, 4000K, operating voltage 180-270V, with constant current electronic driver complete with all accessories and connecting up with three core flexible copper conductor wire of adequate size complete all as specified and directed. (MAKE: HAVELLS, CAT NO: LHEEASPDIB1W005 / HALONIX, CAT NO: HLDLR-27-06NW / JAQUAR, CAT NO: ICO-WHT-LERS05R007XN / CROMPTON, CAT NO: CDR-211-06-40-SL-NWH)
S&F recess mounted LED luminaire, of size 600 mm x 600 mm, 100 lumen/watt, in powder coated CRCA housing , having glare free diffuser, operating voltage 180-270V, with constant current electronic driver complete with all accessories with and including 36 Watt LED (Cool Day Light) and incl all accessories, mounting frame etc and connecting up with three core flexible copper conductor wire of adequate size complete all as specified and directed.
All as per Item No. 81 above, but 36 Watt recess mounted LED luminaire (Warm White) of size 600 mm x 600 mm complete
S&F LED Gate Light in aluminum die cast with modern artistic design and white PC diffuser, square/round, suitable with and including LED lamp B22, 7 watt complete all as specified and directed. (Make - Havells, Cat Part No: LHFOASE1TZ5W009 / LHFOASE1TN5W009 or equivalent model in other makes specified in particular specifications) NOTE: Wire for connection of luminaire shall be measured and paid seperately.
S&F Decorative gate light made up of high grade unbreakable polycarbonate material suitable for retrofit LED lamp B22 base with and including LED lamp 20 watt complete all as specified and directed. (Make - Havells, Cat Part No: LHFXBON1TN5Q014 or equivalent model in other makes specified in particular specifications) NOTE: Wire for connection of luminaire shall be measured and paid seperately.
S&F LED post top luminiare, 25 watt, with die cast aluminium spigot, spun aluminium powder coated top cover, with high power LED, IP 65 grade protection, designed with indirect symmetrical light distribution, with integrated constant current electronic driver complete all as specified an directed. (Make : BAJAJ, Cat No: BGCTN 25W LED WW / HALONIX, Cat No: HLPT-04-25CW / HAVELLS, Model: RUBY / ORIENT, Cat No: OSL-MARFICPT025W or equivalent model in other makes specified in tender) ) NOTE: Wire for connection of luminaire, if replaced, shall be measured and paid seperately.
S&F LED pathway luminare, 9/10 watt, in powder coated ERW MS tubular/square sections, with cylindrical diffuser on top complete, IP 65 grade protection, operating voltage 120-280V, with integrated constant current electronic driver incl all fittings and fixtures complete with PCC base (1:2:4 Type B1) complete all as specified and directed. NOTE: Wire for connection of luminaire shall be measured and paid seperately. Cost of PCC base is deemed to be included in the quoted rates.
S&F in repair Bracket/Arm suitable for street light fittings, made out of 25 mm bore (light grade) GI pipe length not exceeding 1.20 metre long, fixed with 02 sets of flat iron clamp of size 40mm x 6 mm, with bolts, nuts and washers of suitable size including applying two coats of aluminium/synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
S&F LED Building Security Light fitting (Warm White), of various capacity as mentioned under, in high pressure die cast aluminium housing with prismatic polycarbonate modular secondary lens optics with integrated constant current electronic driver, top opening driver cover, IP66 ingress protection, impact resistance of IK07 complete all as specified and directed and complying with the following specifications:-. (a) minimum system efficacy 100 lumen/watt (b) CRI not less than 70, (c) THD < 10% (d) Power Factor not less than 0.90 (e) having in built short circuit and surge protection upto 4 kV (f) having 10 KV external surge protection (for 45 watt & above) (g) colour temperature not less than 3000 degree K (h) life not less than 50000 hours of operation (NOTES: (1) List of approved makes has been provided in particular specifications. Contractor shall ensure that luminaire provided comply with the aforesaid specifications. No claim shall be entertained during currency of work. (2) Wire for electric connection shall be measured and paid separately)
25 Watt Luminaire
35/36 Watt Luminaire
45 Watt Luminaire
50 Watt Luminaire
S&F in repair PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 3 core, 2.50 sqmm, 1100 Volt, conforming to IS 694 all as specified and directed
S&F DB, VTPN, 4 way, vertical type, IP 43 protection, double door, 415 volts with provision for MCCB as incomer and MCB as outgoing and connecting up complete all as specified and directed.
S&F SPN DB, IP 43 protection, double door, 240 volts, 4 way, with 100 Amps copper Bus Bar complete all as specified and directed.
S&F SPN DB, IP 43 protection, double door, 240 volts, 8 way, with 100 Amps copper Bus Bar complete all as specified and directed.
S&F SPN DB, IP 43 protection, double door, 240 volts, 12 way, with 100 Amps copper Bus Bar complete all as specified and directed.
S&F Sheet Metal Enclosure, Single Door, 2 way with provision to mount MCBs complete all as specified and as directed.
S&F Sheet Metal Enclosure, Single Pole with a 2-Pin and Earth Plug and Socket with provision to mount MCB, 32 Amps, 240 volts and connecting up complete all as specified and as directed.
NOTE FOR ITEM NO. 73 to 78 :- (1) Incoming MCCB/RCCB/MCB and outgoing MCBs shall be measured and paid seperately. (2) Quoted rate is deemed to be inclusive of blanking plate for blank slots after fixing of MCBs. (3) DB, MCCB, RCCB & MCB shall be of the same manufacturer.
S&F MCCB, 4 pole, 100 Amps, 16 kA, 415 Volts, AC, 50 Hz with and including adjustable thermal and magnetic setting, fixed in DB complete all as specified and directed.
S&F MCCB, 4 pole, 63 Amps, 16 kA, 415 Volts, AC, 50 Hz with and including adjustable thermal and magnetic setting, fixed in DB complete all as specified and directed.
S&F MCCB, 4 pole, 160 Amps, 25 kA, 415 Volts, AC, 50 Hz with and including adjustable thermal and magnetic setting, fixed in DB complete all as specified and directed.
S&F MCCB, 4 pole, 200 Amps, 36 kA, 415 Volts, AC, 50 Hz with and including adjustable thermal and magnetic setting, fixed in DB complete all as specified and directed.
S&F MCB, 'B' Curve, TPN, 415 volts, 32 Amps, breaking capacity 10KA complete all as specified and directed.
S&F MCB, 'B' Curve, SPN, 40-63 Amps, breaking capacity 10KA complete all as specified and directed.
S&F MCB, 'B' Curve, single pole, 6 to 32 Amps, breaking capacity 10KA complete all as specified and directed.
Re-fixing of serviceable MCCBs, any type or capacity and in any position complete all as specified and directed.
Re-fixing of serviceable MCBs, any type or capacity and in any position complete all as specified and directed.
S&F in repair Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire, complete all as specified and as directed. NOTE: Cost of Screws, Saddles, Insulators, Nuts and Bolts, etc. shall be deemed to be included in Quoted Rate.
S&F in repair single phase KWH energy meter, Class 1 accuracy, tamper proof design, with 6 digit bright back-lit LCD display 05 to 30 Amps complete all as specified and directed and old unsv meter shall be deposited to MES store yard complete all as specified and directed. (MAKE - L&T, Cat No-WM101BC5DL0 or similar model in SECUREMETER / CONZERV / HPL / RISHABH)
S&F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM fabricated Meter Panel, made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistant, Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529 and the share panel assembled by OEM , channel partner or sister concerned assembly will not be accepted. The ASTA CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The gasket should be internally embedded made of polyurethane. The panel should pass glow wire test 960°C in accordance with 60695-2-11 [flame retardant and self-extinguishing] complete all as specified and directed. NOTES :- (1) Meter panel shall be designed for for fitment of 04 single phase meters. Existing meters shall be re-fixed in the panel. (2) The panel shall be provided with the following accessories :- (a) 04 Pole MCCB 100 A, 415 volts, 16 kA - 01 No (b) SPN MCB, 40 Amps, 10 kA. 'C' Curve - 04 Nos (3) The meter panel shall be wall mounted type. (4) MCCBs & MCBs shall be provided from the makes as specified in particular specifications. No claim shall be entertained at a later stage.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized steel earth wire 4 mm dia (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 15 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed.
GENERAL NOTES :- Light Fittings, Meter panel, MCCB, MCB, Modular fittings shall be procured from authorised dealers. Purchase Vouchers, e-way bills and manufacturer's test certifiactes shall be submited by contractor before claiming payment for the items.
AMBIKA ENTERPRISES (BID ID -3374258)
M/S KAVYA ENTERPRISES (BID ID -3373388)
shiv shanker enterprises (BID ID -3378449)
M/S GOYAL CONSTRUCTIONS (BID ID -3378901)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .