Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹2.6 LAccepted-Finance | L-1 | Accepted-Finance L-1 | |
| 2 | L-2₹3.2 L+₹56,570 (21.4%)Rejected-Finance | L-2 | Rejected-Finance L-2 | |
| 3 | L-3₹3.7 L+₹1.1 L (42.0%)Rejected-Finance | L-3 | Rejected-Finance L-3 | |
| 4 | L-4₹4.1 L+₹1.4 L (54.5%)Rejected-Finance | L-4 | Rejected-Finance L-4 |
Tender Value
₹4 L
EMD Value
₹5,000
Closing Date
2 Dec 2024, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE
400 KV S/S SARNATH VARANASI
WORK
2024_UPTCL_967913_1
E-TENDER No. 11 ETC-II(VNS)2024-25
Open Tender
Electrical Works
Lump-sum
90 days
GHAZIPUR
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ETD GHAZIPUR
₹5,000
20 Dec 2024
25 Oct 2024
3 Dec 2024
31 Oct 2024
2 Dec 2024
10 Nov 2024
Amount
Following work is required to be carried out for replacement of gasket of 40 MVA, 132/33 KV, IMP make T/F-I installed at 220 KV S/S Bhadaura.
Carriage of 20 KL Oil tank from 400 KV S/S Kasara-Mau/ 400KV S/S Sarnath or 60 No's empty oil drum from 132 KV S/S Zamania/Ghazipur or other substations under ETD-Ghazipur to 220 KV S/S Bhadaura (Approx. Distance 100 Km) of capacity 209 Ltr. With the help light/heavy vehicle arrange by the contractor on his own cost. The work involve loading and unloading of empty oil drum. including cost of labour and T&P charges.
Complete draining out the transformer oil up to required level from existing 40 MVA, 132/33 KV, IMP make T/F-I into empty oil tank or oil drum including opening of drain valves. (Approximate 18.50 KL)
Dismantling of HV/LV & Neutral bushing turret from T/F main tank, Radiators, conservator tank, PRV, buccholz relay, oil pipe line, OLTC cap, cooling fans, opening of electrical connection and proper blanking of open space for replacement of gaskets with the help of hydra. and other all associated work to complete the job.
Providing & replacement of old & damaged gasket of 40 MVA, 132/33 KV, IMP make T/F-I as per required size of good quality rubberised cork sheet of new KONIKA/TRABROZE make of standard quality at following place of transformer.
Top cover gasket replacing involving the work of opening nut-bolts of the top cover plate (lifting the cover plate with core and winding by 20 cm.) from its present level, cleaning the oil and damaged gaskets and its removal from surface by scraping and cleaning the top surface, fabrication of top cover gaskets as per top surface made from corksheet, jointing & punching holes, fitting on top surface, fitting the top plate cover and tightening the nut and bolts for proper completion of work.
145 KV bushing gaskets
LV/Neutral bushing top portion oil seal
LV/Neutral bottom gaskets
HV/LV side Neutral bushing top portion gasket
HV/LV/ side Neutral bushing bottom portion gasket
Buccholz relay
Valve gaskets
Radiator flange gaskets
Radiator air plug gaskets
OLTC top/bottom gaskets
OLTC gear mechenism gaskets
OLTC breather gaskets
Conservator plate gaskets
Equiliser pipe line gaskets
Explosionvent/ PRV gaskets
OTI/WTI port gaskets
Drain valve gaskets
Inpection cover HV/LV side gaskets
Sampling valve gaskets
OLTC indication glass gaskets
Busing indication plate gaskets
MOG gaskets
Flashing of main tank core and winding by hot centrifused T/F oil
Performing the Vaccume stand test. The scope of work involve creating the vaccume inside the T/F up to -760 mm of Hg for evacuation of moisture from core & winding and maintaining the pressure at least for 72 hours.
Complet erection of T/F original position and complete of all respect to operation.
Refilling of T/F oil up to required level & complete Centrifusing of old T/F oil of 40 MVA, 132/33 KV, IMP make T/F-I by connecting centrifusing pipe to circulate the T/F oil through centrifising machine which will be provided by the contractor and taking the BDV and megger of T/F of the oil periodically up to required value, PPM & DGA test is also to be conducted and achieve as per direction of supervisory engineer.(Taking Oil sample in bottel & send to lab for oil testing by contractor his won cost)
Spray painting of 40 MVA, 132/33 KV, IMP make T/F-II with one coat of red oxide primer and two coats of standard make Asian/Burger/Nerolac smoke gray synthetic enemel of 1st quality.
Repairing & servicing of cooling fan of T/F including the work opening of cooling fan from stand, opening fan body, replacing damaged bearing/bush, rewinding of cooling fan if required, oiling, greasing of motor, replacing if required its protective MCBs, switches, contractor, overload relay etc. to complete the job for proper & smooth Auto operation.
SATKAR TRADERS (BID ID -4739276)
Meena Elect & Engg. Works (BID ID -4739710)
Perfect Power Transformer Associates (BID ID -4739729)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .