| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.0 LAccepted-AOC NO 235 PSK ILLAM SANKARAN NAGAR CHINNAMMAN KOIL STREET AVADI CHENNAI 600 054 | CHENNAI | THIRUVALLUR | TAMIL NADU | 600054 | ₹21.0 L Quoted ₹21.3 L | L1 | Accepted-AOC L1 |
| 2 | L2₹23.2 L+₹1.9 L (9.13%)Rejected-AOC NO 3 JAMI JAM KHAN ROAD 1ST LANE ROYAPETTAH CHENNAI 600 014 | CHENNAI | CHENNAI | TAMIL NADU | 600014 | ₹23.2 L+₹1.9 L (9.13%) | L2 | Rejected-AOC L1 being accept |
| 3 | L3₹23.9 L+₹2.6 L (12.3%)Rejected-AOC | ₹23.9 L+₹2.6 L (12.3%) | L3 | Rejected-AOC L1 being accept |
| 4 | L4₹25.1 L+₹3.8 L (17.9%)Rejected-AOC | ₹25.1 L+₹3.8 L (17.9%) | L4 | Rejected-AOC L1 being accept |
Tender Value
₹25.0 L
EMD Value
₹49,980
Closing Date
23 May 2024, 6:00 pmClosed
CWE NAVY CHENNAI
Commander Works Engineers Navy Military Engineer Services Fort St George Rajaji Salai Chennai600 009
87693 REPAIR REPLACEMENT OF HT UG CABLE, FAULT FINDING WORKS AND HT JOINTS TO HT 11KV VCBs AND OTHER MAINT WORK AT VARIOUS SUB STATION UNDER GE(M) ARAKKONAM
2024_MES_650021_1
CWE/NAVY/ARK/87693/E8 OF 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Arakkonam
As per NIT
8 documents required · 8 mandatory
₹500
GE Maint Arakkonam
₹49,980
Yes
27 Jun 2024
26 Apr 2024
25 May 2024
26 Apr 2024
23 May 2024
10 May 2024
26 Apr 2024 - 3 May 2024
Amount
SCHEDULE 'A' PART-I [ E/M WORKS]
Material and labour to carryout test and identify exact location and nature of defect in 11 KV HT UG cable any size/type using cable fault locator/equipment including finding of cable route as per site requirement including transportation, testing after rectification and restoring of the supply in all respects and commissioning etc complete all as specified and as directed Note : Earth work, cable joints as per site requirement shall be measured and paid separately under relevant item of the schedule.
Material and Labour for meggering existing HT UG cable of any size to find out fault for rectification from any location at NAS INS Rajali station after disconnection of cable from both termination end including terminate both end after rectification of cable (Cable joint kit , excavation, relaying, will be measured and paid separately under relavant items) complete all as specified and as directed
Taking up old /existing unserviceable defective HT 11000V UG Cable of size 185 sqmm 3 core from the existing trenches/ near panels and keep a side carefully and segrigating serviceable portion of cable for Reuse complete including cutting vagitation from cable route before takingdown all as specified and as directed. Note: (i) Excavation/ earth work shall be measured and paid seprately under relavent items. (ii) Retrived serviceable cable cover from site be properly stacked and reused as protection to HT UG cable and shall be measured and paid separetely under relevent items. (iii) Serviceable portion of cable shall be relayed as directed and shall be measured and paid separetely under relevent items.
All as per item No 4 above but for size 95 sqmm 3 core complete all as specified and as directed
Supply, laying, testing for replacement against unserviceable part of item No 4 here-in- before XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 185 sqmm 3 core complete all as specified and directed.
Supply, laying, testing for replacement against unserviceable part of item No 5 here-in-before XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 95 sqmm 3 core complete all as specified and directed .
Relaying in trenches serviceable electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 185 sqmm 3 core retrieved from ground complete all as specified and directed.
All as per item no 8 above but for cross sectional area 95 sqmm 3 core complete all as specified and as directed
Taking up existing old/unserviceable/ burnt 240 sq mm 3.5 core under ground cable from the existing positions/ trenches etc. including testing with the help of megger, disconnecting and removing unserviceable portion of cable complete all as specified and as directed. Note: (i) Excavation/ earth work shall be measured and paid seprately under relavent items. (ii) Retrived serviceable bricks from site be properly stacked and reused as protection to UG cable and shall be measured and paid separetely under relevent items. (iii) Serviceable portion of cable shall be relayed as directed and shall be measured and paid separetely under relevent items.
Relaying in trenches serviceable electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 240 sq mm 3.5 core retrieved from ground complete all as specified and directed.
Supply, laying XLPE insulated, screen, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 240 sq mm 3.5 core with aluminium conductor of following size for replacement of unserviceable portion of cable including connecting up with proper size aluminium lugs, glands wherever necessary in LT panels/ bus bar chamber panel /joints etc., all as per site requirement including testing complete all as specified and as directed by Engr-in-charge. Note:(i) Rates includes supply and fix necessary glands,lugs,insulation tape etc., (ii) Excavation/ Earth work shall be measured and paid separately under relevent items.
M&L for HT Cable jointing kit for cable for outdoor termination heat shrink type end joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm complete all as specified and as directed
M&L for HT Cable jointing kit for cable for outdoor termination heat shrink type end joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 sqmm complete all as specified and as directed
M&L for HT Cable jointing kit for cable for straight through termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm complete all as specified and as directed
M&L for HT Cable jointing kit for cable for straight through termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 sqmm complete all as specified and as directed
M&L for Cable jointing kit for cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm complete all as specified and as directed
M&L for Cable jointing kit for cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 sqmm complete all as specified and as directed
M&L for Cable jointing kit for cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 240 Sqmm to 400 sqmm complete all as specified and as directed
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth for taking out /for laying under ground cables/pipes etc and getting out in soft/loose soil complete all as specified and directed
Spreading riddled earth as obtained from exvavation in cable trenches complete all as specified and directed.
Supply and laying unreinforced pre cast concrete cable cover class HV type 1 flat size 300 x 180 x 40 mm for cable protection complete all as specified and as directed
Relaying in trenches serviceable un-reinforced precast concrete cable cover, retrieved from item ground complete all as specified and as directed
Supply and lay standard size common burnt clay building bricks sub class 'B' for cable protection, laid dry complete all as specified and as directed.
Relaying of serviceable bricks as obtained from item ser No.20 here-in-before complete all as specified and as directed.
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed
Removing excavated soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed
Material and labour for cast iron cable route indicator of standard size circular/eleptical shaped incl 25 x 6 mm angle iron stud with slanting top duly embossed ' HT CABLE ' including and planted on PCC foundation 1:3:6 type C2(40mm aggregate) 300x300x100mm complete including taking out old damaged indicators and demolition of PCC near old indicators, necessary earth work, site clearance, painting and preparation of surface complete all as directed.
M & L cutting of road, hard standing made of concrete or premix carpet, WBM, soiling and morrum filling including excavation for laying of cable pipe all as directed and making good the road/hard standing by using all old/new materials and with PCC (1:2:4) etc, required to match with the existing surface complete all as specified and directed.
M & L Galvanised iron tubing 100 mm dia light grade laind in trenches/floors/walls for eath lead protection and cables at road crossing etc complete all as specified and directed.
Material and labour for servicing, overhauling HT VCB panel complete 11 KV 400-800 Amps, upto 500 MVA of various make/type and checking door lock system, checking for phase sequence, mechanical and electrical interlocking system, complete wiring checking of relays, trip coil, spring charge motor, closing coil etc, tightening all the mechanical and electrical joints complete and writing with paint the Feeder name and checking the functionality in position after servicing complete all as specified and as directed. Note: (i) Quoted rate includes S&F all minor spares and wires required during servicing. (ii) Replacement of unserviceable major spare parts shall be measured and paid separately as supply only under relevant items here-in-after however fixing charges/labour cost for the spares to be included in the quoted rate.
Material and labour for calibration of HT VCB panel complete 11 KV 400-800 Amps, upto 500 MVA of various make/type including relay,tripping mechanism etc as per standard/ specified/directed by OEM certified agency and submitting report all as specified and as directed.
Servicing of 11KV RMU 600 Amps SF6 KISOK circuit breakers outdoor type replacement of unservivable spare parts ,checking of mechanism, fixed and moving contacts, removing of carbon deposits on fixed and moving contacts, checking of control wiring, trripping circuit wiring, testing of CT insulation resistance values and testing of operation manual and remote all as directed by Engr-in-charge.
S&F Replacing of PCB in existing Battery Charger 230/30Volts of any make including testing and installing of battery Charger complete all as directed by Engr-in-charge.
Supply only the following spare parts for HT VCB panel complete 11 KV 400-800 Amps, upto 500 MVA of various make/typeall as specified and as directed NOTE : (i) labour cost for taking down old u/s item and fixing of following new items deemed to be included in quoted rate.
(a) Current Transformer 600 to 1250 Amp
(b) Closing spring
(c) Door lock handle with key
(d) Emergency push button
(e) Battery for Power pack,12 V,7AH
(f) Anticondensation space heater
(g) Thermostat
(h) DC Power Bank
(j) Under voltage relay
(k) Vaccum interrupter (bottle type)
Isolate, disconnect, dismantle the burnt out lugs from the main connections and crimping with proper new 120 Sqmm/150 Sqmm/185 Sqmm lugs and glands as per existing one including fixing insulation tape termination to main connections for the following sizes of HT/LT cables complete all as directed by Engr-in-charge.
All as per item No 46 but for 50/70/95 Sqmm Aluminium Lugs complete all as directed by Engr-in-charge.
Servicing of 11KV 3-Phase Gang Operated Device including replacing the defective items and applying mineral Jelly,oil, grease after proper removal of carbon deposits, refixing of Switch A/B Gang operated triple pole mechanically operated mounted on isolator and steel frame with operating mechanisam works from Ground level, complete all as directed by Engr-in-charge.
S&F for renewal of barrel fuse single pole 20 amps (suitable for 200 KVAR capacitor bank each of 100 KVAR capacity) complete all as directed by Engr-in-charge
Supply only Tinned Copper fuze wire of following for 30 Amp to 50 Ampcapacity complete all as directed by Engr-in-charge
Ditto all as per item No 50 but for Capacity 60 Amp complete all as directed by Engr-in-charge
Ditto all as per ser No 50 but for Capacity 100 Amp complete all as directed by Engr-in-charge
Supplying only insulation tape 16mmx7mtrx0.125mm, complete all as directed by Engr-in-charge Make: steelgrip, 3M, Kinjal,
Renewal of 11 KV burn out jumper with new Aluminium jumper with Aluminium jumper (existing size) with new aluminium clamp including bolt nuts and washers complete all as directed by Engr-in-Charge
Servicing of existing On Load Tap Changer of Power Transformer including opening nut bolt, gasket and repair/ replacement of wornout parts/ coils, moving contact and testing to founctioning properly complete all as directed by Engr-in-Charge
Testing of wiring including disconnection and reconnections from control panel to transformer buchauls relays, winding temperature, oil temperature, oil level temperature cutout relay, master trip relay, auxillary protection relay complete all as directed by Engr-in-Charge. Note :- The rates included with all spares parts.
Renewal of unserviceable burnt out HT support insulator 11 KV capacity all material including of SF-6 breaker with & including necessary fixing complete all as directed by Engr-in-Charge
M&L Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. or carrying to MES store (spare/components for replacement to be issued by department)
M & L switch air brake gang operated Triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 400 amps 11000 volts complete all as specified and as directed.
M&L Air break (switch) insulator for 11000 volts 400 amps complete all as specified and as directed.
M&L Lightning arresters polymer/expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp 11000 Volts complete all as specified and as directed.
Taking down the cracked/broken unserviceable HT 11 KV post top insulator and S&F post top polymer insulator vitrous brown with GI clamp nuts bolts etc suitable for HT 11000 Volts grade working pressure complete all as directed by Engr-in-Charge.
Taking down the unserviceable disc insulator and S&F new disc type polymer disc insulator vitreous brown 145mm height and 255mm dia ball and socket type single disc assembly with GI clamp nuts and bolts etc suitable for 11000 V grade working pressure complete all as directed by Engr-in-charge.
Taking down the unserviceable HT 11 KV, Pin insulator and S&F new Pin type polymer pin type insulator vitreous brown 150 mm dia,top groove 19mm with GI spindle and other accssoriesle suitable for 11000 V grade working pressure complete all as directed by Engr-in-charge.
Supply and fix danger notice plate of 1.6mm thick size HT 25 x 20 cm of mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamp, bolts and nuts of approved of size including taking down rusted danger plates complete all as specified and as directed
M&L Cement concrete in foundations, filling & mass concrete type D2 1:4:8 using 40mm graded aggregate complete all as specified and as directed
Material and labour for PCC for coping /road cutting/earth pit chamber for existing poles/location whereever necessary, 1:3:6 type C-1 (Using 20mm graded stone aggregate) complete all as specified and as directed.
M&L for rendering 15mm thick in CM 1:6 on fair faces of brick work or concrete surfaces, rendering is to be finished even and smooth without using extra cement complete all as specified and as directed
Supply and spread grade stone aggregate of 40mm size in 2/4 poles structure yard complete all as directed by Engr-in-Charge.
M&L for cleaning the 2 Pole structure of any height including Cross arm and Angles, fitting of any description clean thoroughly with cleaning agent including scrapping up of old corroded paint dirt/dust/ rust carefully and applying two coat of synthetic aluminium paint (From copping to GOD) and two coat of Red postal colour Paint from GOD to above of pole and sturcture, over one coat of red oxide metal primer paint before 01 Day of aluminium & Red painting, and marking of Strip (01 to 03) by Fluroscent Paint as per KV Grading up to a height of 1.5m above, the PCC coping painted with 02 coats of black synthetic enamel paint including writing of pole numbers complete all as directed by Engineer-in-Charge. Note :- Zebra Strip size & Colour of painting as directed by Engr -in-Charge at the time of execution.
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or buried in ground or fixed to poles or any other indicated situated for loop earthing etc. as required GI earth strip of size 32x6mm complete all as directed by Engr-in-Charge.
Material and labour for repairing the existing eart pit chamber, before removing the existing twisting earth pit sink into the ground, broken rcc cover etc. with replacement of new RCC cover of existing size and improve the earth value with added water and salt and findout the earth value using digital earth tester after disconnection of earth electrode from earth chamber for maintaining the record and fill the data in earth test register incl writing the earth value on earth pit with date of measurement complete all as specified and as directed
Material and labour for Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly in ground vertically to a depth of not less than 2.25 m deep below normal ground level, with top edge of the earth plate at a depth of not less than 1.5 mtr below ground connected to GI earth strip 32 x 6mm by means of GI bolts and nuts, washers and GI earth strip protected by GI pipe light grade 40mm bore upto 7.5 mtr and connecting to HT/ LT switch gear etc as per site requirement including necessary excavation, earth work in any type of soil, PCC 1:3:6 type C-1 earth chamber, 40mm thick RCC cover with 6mm dia MS bars 10cm C/C on both ways as reinforcement complete all as shown in electrical plate No 3 of MES Schedule Part 1 (2009) connected to earthing test points complete all as specified and as directed by Engineer-in-Charge. Note :- (i)Quoted rate deemed to include necessary earth work, PCC chamber, RCC cover, reinforcement, removal of surplus soil, site clearance etc. (ii) GI earth strip 32 x 6mm, GI tubing light grade 50mm dia upto 7.5 mtr deemed to be included the rate quoted by the contractor. (iii) Beyond 7.5 mtr the GI earth strip 32 x 6mm & GI pipe light grade 50mm dia shall be measured under relevant item of the schedule.
G.L.THIRUMALAI NAIDU AND COMPANY
Green Ray Technologies
EASHWAR ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .