| Sl No | Description | Qty | Unit | NORBU DHENDUP BHUTIA L1 | SATEN LAMA L2 | M/S NARAYAN THAPA L3 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing and Commissioning of 40 KVA Silent D.G set at Residence of ADMs and SDO at Kalimpong (Job No. K/OW/04 of 25-26) | ||||||
| 2.00 | Supply,Installation,Testing & Commissioning of Silent Type 40 KVA, 415 Volts (3-Phase) 50 Hz DG Set with AMF Panel confirming to CPCB-IV emission norms as per following specification(Make-Cummins make engine modelX2.7TAA-G2 / Equivalent kirloskar green/ Ashoke layland/ Valvo Icher developing 56 BHP and 40 KVA) Diesel Engine: Liquid Cooled Diesel Engine, developing 1500 rpm having blower fan of adequate capacity, ganguard, fan belts etc. the Diesel Engine shall be vertical,No. of cylinder: 03, Electric Start, compression ignition, continuous run at 1500 rpm conforming to IS 10002, ISO-3046, BS5514 standard with an permissible over load capacity of 10% for one hour in 12 hour in every 12 hours of operation complying present CPCB norms.B) Alternator: make Alternator suitable to deliver rated outpot of 40 KVA at 1500 rpm, 415V, 0.8 Pf (lag), 50HZ, 3 Phase, in SPDP Enclosure, self excited & self regulated, brushless. The alternator should be IS: 4722/BS EN 60034-1 & will be suitable for tropical condition having full load efficiency above 90%. Class of Insulation shall be H and enclosure shall be IP23. Supports Auto-Mains-Failure(AMF) function and Manual-Control-Panel (MCP) function In-build AMF Control Panel suitable for 40 KVA DG Set consists of- microprocessor based AMF control unit, it monitors the engine safety parameters and alarm/ trip condition will be displayed on the front panel. Special alarm conditions include LLOP, HWT, overload, under/over speed, low fuel level. Specific indication includes various conditions of operations such as Load on mains, load on DG, Mains healthy, DG ON, Auto & Manual mode. The control panel consist of multi function meter which displays AC current/Voltage, Frequency, Power factor, KWh etc.
(Make- Cummins Engines_X2.7TAA-G2/ Kirloskar Engines_Model No: 3R1190E TA 4G1) Terms and Conditions:
1) Agency must procure the materials/DG Set from the manufacturer/OEM or from their authorized sales and channel so that the standard warranty/support of the manufacture/OEM becomes applicable to the products to be delivered and installed by them.
2) Documents that authenticates such procurement from the manufacturer /OEM or from their authorized sales channel and standard warranty/support should be send from the e-mail of the manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-charge and hard copy of it to be submitted during executive of work/ submission of bill.
3) If any refurbished materials is supplied and installed, penal action will be taken as per existing rules. | 1 | Item | 8,59,000 ₹8,59,000 Lowest | 8,96,000 ₹8,96,000 | 9,03,000 ₹9,03,000 |
| 3.00 | Supply and Installation of 415 V,160 A 4 Pole Automatic Transfer Switch,Solenoid operated,Build-in Microprocessor Controller,Phase Indicating Lights set R-Y-B,Phase Indicating Lights in Incoming and Output of ATS,Indicating Lights for On/Off/Trip, Manual Change Over Provision,Conforming to IEC60947-6-1 ( Make- L&T / Schnerider/ABB or Equivalent as per EIC.) | 1 | Item | 76,260 ₹76,260 Lowest | 79,360 ₹79,360 | 79,980 ₹79,980 |
| 4.00 | Supply & Laying 12 core 2.5 sq. mm. (As meter loop/ Incomer to the main panel) PVC inculated armoured Copper. cable.Make- Polycab/ Havells/ KEI (For Control Panel to DG Set) incl. Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry and Finishing the end by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials | 10 | Mtr. | 1,574 ₹15,740 Lowest | 1,639 ₹16,390 | 1,652 ₹16,520 |
| 5.00 | S & F of Exhaust piping shall be held from silencer onwards to the terrace for discharging entire exhaust gas. The piping and silencer shall be insulated fiber glass white wool. The insulation shall be held in position with galvanized steel wire mesh and neatly finish with 26 SWG Al. cladding M.S. Pipe (65 mm dia) shall be class - B. S & F flanges , MS Clamps vertically | 4 | Mtr. | 1,599 ₹6,396 Lowest | 1,664 ₹6,656 | 1,677 ₹6,708 |
| 6.00 | Supply & Laying 4 core 35 sq. mm. size PVC insulated armoured Al. cable.Make- Polycab/ Havells/ KEI (For Power Supply from WBSEDCL to DG & From DG to Panel.,Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry incl. Finishing the end of armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials | 100 | Mtr. | 1,100 ₹1,10,000 Lowest | 1,152 ₹1,15,200 | 1,161 ₹1,16,100 |
| 7.00 | Supply & Laying of 4 core 16 sq. mm. size PVC insulated armoured Al. cable.Make- Polycab/ Havells/ KEI (For Power Supply from WBSEDCL to DG & From DG to Panel.,Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry incl. Finishing the end of armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials | 60 | Mtr. | 861 ₹51,660 Lowest | 896 ₹53,760 | 903 ₹54,180 |
| 8.00 | Supplying and fixing 100A Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc (Make- L&T / HPL/ Havells) | 1 | Set | 12,423 ₹12,423 Lowest | 12,928 ₹12,928 | 13,029 ₹13,029 |
| 9.00 | Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers 415 V 100A Dimension of Al. bars 4 x 25x5mm, Dimension of Sheet Metal Box 500x150mm on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991) | 1 | Rate / Mt. of complete chamber | 3,444 ₹3,444 Lowest | 3,584 ₹3,584 | 3,612 ₹3,612 |
| 10.00 | Supplying and fixing Sheet steel 100 A Main Switches on angle iron frame on wall (Make- L&T / HPL/ Havells) | 1 | Set | 9,102 ₹9,102 Lowest | 9,472 ₹9,472 | 9,546 ₹9,546 |
Tender Value
Refer Docs
EMD Value
₹25,000
Closing Date
29 Aug 2025, 6:55 pmClosed
Executive Engineer , Kalimpong Electrical Division
Government of West Bengal Office of the Executive Engineer, PWD Kalimpong Electrical Division Upper Cart Road, Near DM Bungalow Kalimpong-734301
Supply, Installation, Testing and Commissioning of 40 KVA Silent D.G set at Residence of ADMs and SDO at Kalimpong.
2025_WBPWD_889840_1
WBPWD/EE/KED/e-NIQ- 04 of 2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Kalimpong
Please refer Tender documents.
4 documents required · 4 mandatory
₹25,000
7 Sept 2026
11 Aug 2025
1 Sept 2025
11 Aug 2025
29 Aug 2025
11 Aug 2025
Amount
Supply, Installation, Testing and Commissioning of 40 KVA Silent D.G set at Residence of ADMs and SDO at Kalimpong (Job No. K/OW/04 of 25-26)
Supply,Installation,Testing & Commissioning of Silent Type 40 KVA, 415 Volts (3-Phase) 50 Hz DG Set with AMF Panel confirming to CPCB-IV emission norms as per following specification(Make-Cummins make engine modelX2.7TAA-G2 / Equivalent kirloskar green/ Ashoke layland/ Valvo Icher developing 56 BHP and 40 KVA) Diesel Engine: Liquid Cooled Diesel Engine, developing 1500 rpm having blower fan of adequate capacity, ganguard, fan belts etc. the Diesel Engine shall be vertical,No. of cylinder: 03, Electric Start, compression ignition, continuous run at 1500 rpm conforming to IS 10002, ISO-3046, BS5514 standard with an permissible over load capacity of 10% for one hour in 12 hour in every 12 hours of operation complying present CPCB norms.B) Alternator: make Alternator suitable to deliver rated outpot of 40 KVA at 1500 rpm, 415V, 0.8 Pf (lag), 50HZ, 3 Phase, in SPDP Enclosure, self excited & self regulated, brushless. The alternator should be IS: 4722/BS EN 60034-1 & will be suitable for tropical condition having full load efficiency above 90%. Class of Insulation shall be H and enclosure shall be IP23. Supports Auto-Mains-Failure(AMF) function and Manual-Control-Panel (MCP) function In-build AMF Control Panel suitable for 40 KVA DG Set consists of- microprocessor based AMF control unit, it monitors the engine safety parameters and alarm/ trip condition will be displayed on the front panel. Special alarm conditions include LLOP, HWT, overload, under/over speed, low fuel level. Specific indication includes various conditions of operations such as Load on mains, load on DG, Mains healthy, DG ON, Auto & Manual mode. The control panel consist of multi function meter which displays AC current/Voltage, Frequency, Power factor, KWh etc. (Make- Cummins Engines_X2.7TAA-G2/ Kirloskar Engines_Model No: 3R1190E TA 4G1) Terms and Conditions: 1) Agency must procure the materials/DG Set from the manufacturer/OEM or from their authorized sales and channel so that the standard warranty/support of the manufacture/OEM becomes applicable to the products to be delivered and installed by them. 2) Documents that authenticates such procurement from the manufacturer /OEM or from their authorized sales channel and standard warranty/support should be send from the e-mail of the manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-charge and hard copy of it to be submitted during executive of work/ submission of bill. 3) If any refurbished materials is supplied and installed, penal action will be taken as per existing rules.
Supply and Installation of 415 V,160 A 4 Pole Automatic Transfer Switch,Solenoid operated,Build-in Microprocessor Controller,Phase Indicating Lights set R-Y-B,Phase Indicating Lights in Incoming and Output of ATS,Indicating Lights for On/Off/Trip, Manual Change Over Provision,Conforming to IEC60947-6-1 ( Make- L&T / Schnerider/ABB or Equivalent as per EIC.)
Supply & Laying 12 core 2.5 sq. mm. (As meter loop/ Incomer to the main panel) PVC inculated armoured Copper. cable.Make- Polycab/ Havells/ KEI (For Control Panel to DG Set) incl. Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry and Finishing the end by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
S & F of Exhaust piping shall be held from silencer onwards to the terrace for discharging entire exhaust gas. The piping and silencer shall be insulated fiber glass white wool. The insulation shall be held in position with galvanized steel wire mesh and neatly finish with 26 SWG Al. cladding M.S. Pipe (65 mm dia) shall be class - B. S & F flanges , MS Clamps vertically
Supply & Laying 4 core 35 sq. mm. size PVC insulated armoured Al. cable.Make- Polycab/ Havells/ KEI (For Power Supply from WBSEDCL to DG & From DG to Panel.,Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry incl. Finishing the end of armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
Supply & Laying of 4 core 16 sq. mm. size PVC insulated armoured Al. cable.Make- Polycab/ Havells/ KEI (For Power Supply from WBSEDCL to DG & From DG to Panel.,Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry incl. Finishing the end of armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
Supplying and fixing 100A Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc (Make- L&T / HPL/ Havells)
Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers 415 V 100A Dimension of Al. bars 4 x 25x5mm, Dimension of Sheet Metal Box 500x150mm on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991)
Supplying and fixing Sheet steel 100 A Main Switches on angle iron frame on wall (Make- L&T / HPL/ Havells)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. l ong and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S &F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:l ( ISI-Medium GI pipe)
Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt. long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment, incl. providing masonery enclosure on the top of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56x35.56cm with locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode
Excavation of soil for installation of Earth Electrode and filling & ramming. (Soft Soil) (for Earthing & DG Foundation) [PWD/GS Page: G-1 Item:1]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe [PWD/GS Page: G-2 Item: 3/a]
Extra for treatment of soil by using salt & charcoal or coke for plate electrode [PWD/GS Page: G-2 Item: 3/b]
S&F earth busbar of 40X6mm galvanized (Hot Dip) MS flat on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required [PWD/GS Page: G-2 Item: 4/a]
Connecting the equipments body to earth busbar including S&F 25X6mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [PWD/GS Page:G-3 Item: 5/d]
Cutting RCC floor by special tools and tackles very carefully without any damaging and removing the shifted rubbish & levelling up and restoring the surface for 8nos. earth pit as per direction of EIC.
Supply and pour of H.S. Diesel oil for necessary commissioning of new DG incl. transportation cost.
Supply & delivery PVC 200Ltr. Oil Barrel of thickness 6mm.
Hand operated Oil Pump
PVC pipe suitable for oil pumping to DG of length 10Mtr.
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary. (With 1:6 cement mortar, 20 mm thick plaster) [including cost of chipping over concrete surface]
Neat cement punning about 1.5mm thick in wall, dado, window sill, floor etc. NOTE:Cement 0.152 cu.m per100 sq.m. (PWD Building Schedule Page: 192 Item: 15)
Single Brick Flat Soling of picked jhama bricks including ramming and dressing bed to proper level, Laying of Brick and filling joints with local sand. (PWD Building Schedule Page No.: 14 Item: 1,2)
Controlled Cement concrete with well graded stone chips (20 mm graded nominal size) excluding shuttering and reinforcement with complete design of concrete as per IS : 456 and relevant special publications, submission of job mix formula after preliminary mix design after testing of concrete cubes as per direction of Engineer-in charge. Consumption of cement will not be less than 300 Kg of cement with Super plasticiser per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula. In ground floor and foundation. [using concrete mixture: M 20 Grade, Pakur Variety] (PWD Building Schedule Page No.: 24 Item: 5)
Controlled Cement concrete with well graded stone chips (20 mm nominal size) excluding shuttering and reinforcement with complete design of concrete as per IS : 456 and relevant special publications, submission of job mix formula after preliminary mix design after testing of concrete cubes as per direction of Engineer-in charge. Consumption of cement will not be less than 300 Kg of cement with Super plasticiser per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula. In ground floor and foundation. [using concrete mixture: M 25 Grade, Pakur Variety] (PWD Building Schedule Page No.: 25 Item: 6)
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. [For works in foundation and upto roof of ground floor/upto 4 m] Tor steel/Mild Steel (PWD Building Schedule Page No.: 25 Item: 6)
M.S. structural works in roof trusses with tubular sections conforming to IS: 806-1968 & IS: 1161- 1998 cnnected to one another with bracket, gusset cleats as per design, direction of Engineer-in-charge complete including cutting to requisite size, fabrication with necessary metal arc welding conforming to IS: 816- 1969 & IS: 9595 using electrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting & erection and painting with two coats RO & two coats of synthetic paint, all complete. (PWD Building Schedule Page No.: 100 Item: 2)
Suppling, fitting and fixing single skin colour trapezoidal profile for wall cladding, Roof shall be made of 0.45mm BMT (Base Metal Thickness) (0.50mm TCT (Total coated thickness excluding paint), G550 (min 550 yield strength),m of Zincalume metallic coating (IS15965) with high Solar Reflectance Index (SRI) value for better colling as per thermatech technology, 1000-1015mm effective cover width with five major corrugation, 28mm high rib spaced at 203mm c/c with subtle square fluting in the pan and the end rib shall have anti-capillary groove and return leg. The steel sheet shall be fastende withe 40 micron zinc coated or 25 micron zinc-tin alloy coated, hex head, self-drilling screw as per IS 3566-2002 Class 3 fastener. The base steel shall be coated with zinc-aluminium alloy Zincalume (AZ150) (i.e. 55% Al, 43.4% Zinc, 1.6% Si) minimum of 150g/m2 coating total on both sides, pre-painted with colorbond XRW (xterior roofing, walling) paint system of 35 micron Super Durable Polyester paint (SDP) with stable inorganic pigment with no lead contents confirming IS15965. The sheet shall be free from defects and have brand marking of the manufacturer giving product details on the back of the sheet at regular interval confirming genuinity of the material.
SATEN LAMA (BID ID -6874007)
M/S NARAYAN THAPA (BID ID -6874037)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .