Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.7 LAccepted-Finance GF 3 F 12 KSSIDC BUILDING 5TH CROSS 1ST STAGE PEENYA INDUSTRIAL ESTATE BANGALORE | BENGALURU URBAN | KARNATAKA | 560058 | ₹35.7 L | L1 | Accepted-Finance Quoted lower rate |
| 2 | L2₹40.7 LRejected-Finance | ₹40.7 L | L2 | Rejected-Finance Quoted higher rate |
| 3 | L3₹45.0 LRejected-Finance FLAT 7 SRADHANJALI APARTMENT 393 3F 6 PRINCE ANWAR SHAH ROAD PODDAR NAGAR KOLKATA WEST BENGAL 700068 UDYAM WB 10 0011697 | KOLKATA | WEST BENGAL | 700068 | ₹45.0 L | L3 | Rejected-Finance Quoted higher rate |
| 4 | L4₹45.0 LRejected-Finance 97 RAJA RAMMOHAN ROY ROAD SIRITY KOLKATA WEST BENGAL 700041 WB10A0004871 | KOLKATA | WEST BENGAL | 700041 | ₹45.0 L | L4 | Rejected-Finance Quoted higher rate |
| 5 | Rejected-Technical 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | - | - | Rejected-Technical Insufficient Credential |
| Sl No | Description | Qty | Unit | switching avo Electro Power Ltd L4 | MEGHJIT POWER SOLUTIONS LLP L3 | POWER ONE MICRO SYSTEMS P LTD L1 | C. CHOWHDURY & CO. L2 |
|---|---|---|---|---|---|---|---|
| 1.00SITC OF True Modular UPS with Hot Swapable Units of different ratings having following specifications as mentioned below, | |||||||
| 1.01 | 60 KVA (3 Ph input& 3 Ph output) | 2 | Set | 15,50,945.34 ₹31,01,890.68 | 15,85,920 ₹31,71,840 | 12,17,106 ₹24,34,212 | 14,50,000 ₹29,00,000 |
| 1.02 | 20 KVA (3 Ph input& 1 Ph output) | 2 | Set | 7,00,824.87 ₹14,01,649.74 | 6,64,340 ₹13,28,680 | 6,10,218 ₹12,20,436 | 5,85,000 ₹11,70,000 |
| 2.00INPUT:- | |||||||
| 2.01Input voltage 415V, 3 phases, 3 or 4 wires | |||||||
| 2.02Input voltage tolerance 305 to 480Vac at 100% load | |||||||
| 2.03Input frequency 50 Hz | |||||||
| 2.04Input frequency tolerance 50HZ +/-10Hz(40hz to 60Hz) | |||||||
| 2.05Current THD <3% | |||||||
| 2.06Control Fully Digital, DSP PWM technology | |||||||
Tender Value
₹30.3 L
EMD Value
₹60,680
Closing Date
13 Jan 2025, 1:00 pmClosed
SE,KHEC,PWD
Kolkata Health Electrical Circle, P.W.Dte KIT Annex Building, 5th Floor KOLKATA-700 073
Proposed (G plus 9) storied Private cabin Building within the premises of IPGMER- SSKM Hospital Kolkta--- Electrical installation work and other utility services --- SITC of UPS system.
2024_WBPWD_787147_1
WBPWD/SEKHEC/KSHED /eNIT16/24-25/2nd Call
Open Tender
ELECTRICAL WORKS ORG
45 days
IPGMER- SSKM Hospital Kolkta
Please refer Tender documents.
7 documents required · 7 mandatory
₹60,680
Office of the SE,KHEC,PWD
10 Mar 2026
19 Dec 2024
15 Jan 2025
19 Dec 2024
13 Jan 2025
26 Dec 2024
24 Dec 2024
Amount
SITC OF True Modular UPS with Hot Swapable Units of different ratings having following specifications as mentioned below,
60 KVA (3 Ph input& 3 Ph output)
20 KVA (3 Ph input& 1 Ph output)
INPUT:-
Input voltage 415V, 3 phases, 3 or 4 wires
Input voltage tolerance 305 to 480Vac at 100% load
Input frequency 50 Hz
Input frequency tolerance 50HZ +/-10Hz(40hz to 60Hz)
Current THD <3%
Control Fully Digital, DSP PWM technology
Event Log The Event Log shall store up to 2000 in the front display panel
Topology Level 3 or better
Self-Capacity test Full load Capacity test of the UPS at site without connecting any external load.
Inbuilt or external Isolation Transformer and supply through UPS OEM only
OUTPUT:
Nominal Module full load rating KVA/KW A) 20KVA=18KW or better B) 10KVA= 9KW or better
Rated voltage 400V 3Ph /230v 1Ph
Output power factor range 0.9 lagging to unity without any KVA derating
Output voltage harmonics THDV 1.5% for liner load and 4.5% for non-liner load
Crest Factor 03:01:00
Overload rating 105% for 60 minutes 125% for 10 minutes 150% for 60 seconds
Successive Overloads sustainability: UPS System can withstand any number of repetitive/ multiple overloads occurring in quick succession of few seconds.
Inbuilt Manual by pass switch Required
Inbuilt Static by pass switch Required
Emergency Stop Emergency Stop Button on its Front panel.
Acoustic Noise (At 1 meter from UPS) Max 60 dbA(from 1 M)
DC CHARACTERISTICS
Nominal DC bus voltage Min 360V
Charge Current (Min.) Built-in min 12A (for 30/40KVA) 25A (60/80KVA) or better. External charger is not acceptable.
Battery Make EXIDE/AMARARAJA make
Type 12V SMF
Compatibility Compatible with SMF, Tubular, Ni-Cd, Li-Ion Battery
Battery block per string Maximum 50nos. Variable DC bus it can support at least variation of 10 nos of battery
Battery backup time 30min
Battery capacity
For 60 KVA, Min VAH capacity 57600, [required no of 12 V 120AH (mimimum) batteries]
For 20 KVA, Min VAH capacity 20160, [required no of 12 V 42AH (minimum) batteris]
Battery isolation Battery circuit breaker
Automatic Battery testing Automatic battery testing from front display
Battery cables and rack UPS to Battery bank, should be connected with suitably rated copper cables and suitable size of metal rack should be provided
SNMP/MODBUS communication facility Required
CONTROLS
Charger input Isolator
Battery circuit breaker (mounted separately in its own enclosure)
Inverter output Isolator
Bypass line Isolator
Maintenance Bypass Isolator
Alarm acknowledge / Reset button
Inverter On-Off Push button for Manual switching On/Off of the Inverter
Emergency off push button
MEASURING INSTRUMENTS
LCD panel for Measuring Output voltages, Output currents and Frequency, Battery Voltage and Charging / Discharging current.
LCD panel displays status of the Battery charge status (in %).
Display- Digital LCD HMI type touch screen
PROTECTIONS
RC surge suppressor
Sustained under voltage on input side
Phase loss on input side.
Negative sequence on input side & bypass
Semiconductor fuses in the lines for rectifier thyristors
Snubber circuit for device dv/dt protection
Charger input current limit
Battery current limit
DC over voltage
Low battery
Overload
Over temperature for the inverter
HRC fuses in the control circuit
INDICATIONS (ALARMS & Warnings)
Inverter Failure
Overload (if load exceeds 100%)
Overload shutdown
Emergency shutdown
Equipment over temperature
Maintenance Bypass ON
DC over voltage
Low battery
Battery circuit breaker open
Battery on load
Mains failure
Rectifier Failed or Off
Inverter Unsynchronized
Load on bypass
Output voltage error
Environmental Conditions:
Panel type Floor mounted front access only
Operating temperature 0 – 45 deg.C continuous
Relative humidity < 90 % ( 20 deg. C.) non-condensing type
Altitude 1500 m from MSL without derating
Storage temp. From 0 to + 70 deg. C.
Product Brochures Original product brochure of the UPS battery should be submitted along with offer. Proto type system is not acceptable.
Certification ISO 9001,ISO 14001,ISO 45001 certified
UPS make:- Numeric/ Vertiv/ Switching AVO/ Delta/ Fuji Electric/Power One
TERMS & CONDITIONS
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liability period 1 (One) Year
(Rates should be Quoted inclusive of all taxes & duities and L.W.C. @ 1% as applicable)
C. CHOWHDURY & CO. (BID ID -5966691)
MEGHJIT POWER SOLUTIONS LLP (BID ID -5948797)
switching avo Electro Power Ltd (BID ID -5935043)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid