| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 LAccepted-AOC | ₹1.6 L | L1 | Accepted-AOC Being L1 work is awaeded to Ankur |
| 2 | L2₹1.6 L+₹1,534.02 (0.96%)Rejected-AOC | ₹1.6 L+₹1,534.02 (0.96%) | L2 | Rejected-AOC Being L2, disqualified |
| Sl No | Description | Qty | Unit | Ankur Enterprises L1 | Raj electrials L2 |
|---|---|---|---|---|---|
| 1.01 | Servicing/overhauling of 400 KVA transformer No. 2 including cleaning of outer surface such as conservator tank, explosion vent pipe, neutral bushing etc. dismantling of top plate for inspection of core and winding, lifting of core and tightening of all nuts and bolts of core checking the tap changer, supply & fixing of gaskets for refixing of all dismantled accessories, testing and commissioning complete as required including repairing of faulty components except rewinding etc.complete as required. Precommissioning test to be performed after overhauling and repairing. (i) General inspection and cleaning of the assembly of transformer. (ii) Insulation resistance test by 2.5KV / 1.0KV megar between phase to phase and phase to earth. (iii) Ratio test. (iv) Short Circuit Test | 1 | Job | 9,350 ₹11,033 | 9,000 ₹10,620 Lowest |
| 1.02 | Supply & filling of transformer oil in both Transformers complete as required. | 40 | Ltr | 6,400 ₹7,552 Lowest | 10,000 ₹11,800 |
| 1.03 | Overhauling of 11KV 400A HT switch gear panel and removal of minor defects and greasing including overhauling of all fixed / moving contacts, tightening of all parts, adjustment of operation mechanism for smooth working of breaker, alignment of trolley checking of all connection of metering circuit of HT panel, testing, commissioning i/c testing & proper functioning of tripping system, IDMT relay, CT and its wiring by primary injection set complete as required. Following test shall be carried out after overhauling:- (i) Insulation resistance test of busbar between phase to phase and phase to earth. (ii) Insulation resistance between OCB bushing and contact. | 3 | Job | 24,510 ₹28,921.8 | 24,300 ₹28,674 Lowest |
| 1.04 | Replacement of burnt male contacts in 400 A HT switch gear panel no.2 i/c connection,providing gasket etc complete as reqd. | 6 | nos | 49,350 ₹58,233 | 48,600 ₹57,348 Lowest |
| 1.05 | Replacement of burnt female contacts in 400 A HT switch gear panel no.2 i/c connection, providing gasketetc complete as reqd. | 6 | nos | 39,900 ₹47,082 | 39,000 ₹46,020 Lowest |
| 1.06 | Servicing/repairing of capacitor panel with removal of minor defects ,tightening the connections of contactors,relays, fuses,meters etc and testing of capacitor banks for smooth functioning of panel to maintain the required power factor etc complete as reqd. | 1 | Job | 3,500 ₹4,130 | 3,400 ₹4,012 Lowest |
| 1.07 | Replacement of LED type indicating lamps in capacitor panl i/c connection etc complete as reqd. | 10 | Nos | 2,400 ₹2,832 Lowest | 2,410 ₹2,843.8 |
Tender Value
₹1.5 L
EMD Value
₹3,073
Closing Date
15 Apr 2024, 4:00 pmClosed
Executive Engineer (Electrical)
O/o Executive Engineer (Electrical) BSNL Electrical Division 1ST Floor, Bhopal House, Lalbagh Lucknow
Operation and Comprehensive Maintenance of electro-mechanical services at T.E. Bahraich . SH Rectification of handing over defects at the risk and cost of Ms Krishna Electricals Kanpur
2024_BSNL_193210_1
40/TEDL/BSNL/LKO/2023-24,Dated 26/03/2024
Open Tender
Electrical Works
Item Rate
30 days
Lucknow
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
ACCOUNTS OFFICER, (Cash), BSNL O/o PGMTD, LUCKNOW
₹3,073
17 Sept 2026
9 Apr 2024
16 Apr 2024
9 Apr 2024
15 Apr 2024
9 Apr 2024
Servicing/overhauling of 400 KVA transformer No. 2 including cleaning of outer surface such as conservator tank, explosion vent pipe, neutral bushing etc. dismantling of top plate for inspection of core and winding, lifting of core and tightening of all nuts and bolts of core checking the tap changer, supply & fixing of gaskets for refixing of all dismantled accessories, testing and commissioning complete as required including repairing of faulty components except rewinding etc.complete as required. Precommissioning test to be performed after overhauling and repairing. (i) General inspection and cleaning of the assembly of transformer. (ii) Insulation resistance test by 2.5KV / 1.0KV megar between phase to phase and phase to earth. (iii) Ratio test. (iv) Short Circuit Test
Supply & filling of transformer oil in both Transformers complete as required.
Overhauling of 11KV 400A HT switch gear panel and removal of minor defects and greasing including overhauling of all fixed / moving contacts, tightening of all parts, adjustment of operation mechanism for smooth working of breaker, alignment of trolley checking of all connection of metering circuit of HT panel, testing, commissioning i/c testing & proper functioning of tripping system, IDMT relay, CT and its wiring by primary injection set complete as required. Following test shall be carried out after overhauling:- (i) Insulation resistance test of busbar between phase to phase and phase to earth. (ii) Insulation resistance between OCB bushing and contact.
Replacement of burnt male contacts in 400 A HT switch gear panel no.2 i/c connection,providing gasket etc complete as reqd.
Replacement of burnt female contacts in 400 A HT switch gear panel no.2 i/c connection, providing gasketetc complete as reqd.
Servicing/repairing of capacitor panel with removal of minor defects ,tightening the connections of contactors,relays, fuses,meters etc and testing of capacitor banks for smooth functioning of panel to maintain the required power factor etc complete as reqd.
Replacement of LED type indicating lamps in capacitor panl i/c connection etc complete as reqd.
Raj electrials
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .