Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.0 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹24.8 L+₹2.1 L (9.22%)Rejected-Finance FIRDOUS ABAD BATMALOO SRINAGAR PIN 190004 J K | SRINAGAR | SRINAGAR | J K | 190004 | L2 | Rejected-Finance Other than lowest bidder |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
4 Sept 2024, 6:00 pmClosed
GE 864 EWS
GE 864 EWS, C/o 56 APO
REPAIR / REPLACEMENT AND SERVICING OF PUMP SET OF VARIOUS CAPACITIES OF STP INSTALLATION AT BB CANTT SRINAGAR
2024_MES_661793_1
864/WS-47/2024-25
Open Tender
Miscellaneous Works
Item Rate
270 days
GE 864 EWS
As per NIT
7 documents required · 7 mandatory
₹500
GE 864 EWS
₹50,000
Yes
28 Oct 2024
25 Jun 2024
10 Sept 2024
25 Jun 2024
4 Sept 2024
9 Jul 2024
Amount
Supply only alumina ferric (Grade-4) suitable for purification of drinking water solid water in the form of solid lumps / slabs from the manufacturer having valid BIS certificate as specified in table 1 of IS: 299-2012. Note: Each consignment of alum supplied by the contractor should have a marking indicating weight of slab and manufacturing date and be in proper packing. The alum supplied by the contractor shall be got tested by the department for each lot from Government Approved Lab. The charges for testing shall be borne by the contractor and cost of the same shall deemed to be included in the unit rate quoted.The contractor shall deliver the material as per the site requirement and direction of Engineer-in-Charge.
Supply only bleaching powder stable Gde-I conforming to IS specification 1665/89 (Second revision) miniumum available chlorine percentage lay mass 34%+1% in 25 kg polythene HDPE bags duly marked date of manufacturing and batch No. of fresh lot. Note : The bleaching powder supplied by the contractor shall be got tested by the department for each lot from Government Approved Lab. The charges for testing shall be borne by the contractor and cost of the same shall deemed to be included in the unit rate quoted. The contractor shall deliver the material as per the site requirement and direction of Engineer-in-Charge.
Taking up or down unserviceable, damaged CI/ DI/ GI/ MS water tubing including all CI fittings of size 100/ 150 mm bore complete all as specified and directed.
S&F Galvanised steel water tubing medium grade 150 mm bore with screwed and socketed joints with all fittings such as tees, elbows, sockets, bends, unions, short pieces etc laid in trenches / walls / floors, complete all as specified and directed.
S&F MS Pipes heavy grade with all fittings laid in trenches etc of sizes 150 mm bore wall thickness 5 mm, conforming to IS-1239 Part-I, complete all as specified and directed.
S&F sluice valve long body type of cast iron both ends flanged and drilled holes of size 100 mm dia class I conforming to IS-14848 : 2000 with pressure rating PN 1.6 with spindle and iron wheel head with GI nuts, bolts and washers of suitable size including taking out old unserviceable sluice valve complete all as specified and directed.
S&F sluice valve long body type of cast iron both ends flanged and drilled holes of size 150 mm dia class I conforming to IS-14848 : 2000 with pressure rating PN 1.6 with spindle and iron wheel head with GI nuts, bolts and washers of suitable size including taking out old unserviceable sluice valve complete all as specified and directed.
S&F cast iron non return valve flanged ends heavy duty suitable for 100mm dia pipe including 6mm thick 2 Nos rubber insertion ring, including taking out old unserviceable non return valve complete all as specified and directed.
S&F cast iron non return valve flanged ends heavy duty suitable for 80mm dia pipe including 6mm thick 2 Nos rubber insertion ring, including taking out old unserviceable non return valve complete all as specified and directed.
S&F cast iron non return valve flanged ends heavy duty suitable for 150mm dia pipe including 6mm thick 2 Nos rubber insertion ring, including taking out old unserviceable non return valve complete all as specified and directed.
S&F cast iron strainer / foot valve of size 100/80 mm bore including taking out old unserviceable strainer / foot valve complete all as specified and directed.
S&F cast iron strainer / foot valve of size 150 mm bore including taking out old unserviceable strainer / foot valve complete all as specified and directed.
M&L for run lead joint to spigot and socket pipes of size 100 & 150 mm bore including provision of white lead & spun yarn etc, complete all as specified and directed.
M&L for dismantling, disconnecting and decoupling of 100 HP Electric Motor complete from the installation/ pump house with the help of man power / chain pully block after making temporary arrangment for hanging of chain pully block, incl shifting of motor to civil work shop for rewinding of motor in existing wire guage and size of supper enamelled copper wire and cleaning of all the parts internally & externally and applying warnish on winding and providing heat treatment for winding or heating in oven at appropriate temperature as per manufacture design (or as directed by Engineer-in-Charge) incl replacement of bearing of suitable size, oil seal, packing kit etc and transportation from civil work shop to site for refixing, coupling, alignment of Motor with pump using steel/rubber coupling and testing of Motor complete all as specified and directed.
Ditto all as per serial item No. 14.00 described here-in-before but capacities of motor 50 to 60 HP
Ditto all as per serial item No. 14.00 described here-in-before but capacities of motor 20 to 30 HP
Ditto all as per serial item No. 14.00 described here-in-before but capacities of motor 12.5 to 15 HP Note for serial item No. 14.00 to 17.00 The rates of spare parts such as oil seals, packing kit etc shall deemed to be included in quted rates. The burnt winding or damaged part of winding shall be replaced and the same is deemed to be included in the quoted rates. The necessary plant & machinary and transportation charges to civil work shop and back is also deemed to be included in the quoted rates.
Dismantling and disconnecting 100 HP centrifugal non clog pump set from the electric motor and reassembling the pump on existing foundation and complete with motor after repair /overhauling with following and testing, complete all as specified and directed:- (a) Remetalling the pump shaft made out of HCS- 01No (b) Fabrication of gland and replacement of gland cup made out of gunmetal (as per sample) - 01Set (Ecah set of two). (c) Fabrication & replaclement of gun metal shaft sleeves as per sample - 01No. (d) Fabrication and replacement of neck ring made out of gun metal as per sample - 02 Nos (e) Replacement of suction plates studs by taping new threads all as specified and directed -04 Nos
Ditto all as per serial item No. 18.00 described here-in-before but capacity of pump 60 HP
Ditto all as per serial item No. 18.00 described here-in-before but capacity of pump 50 HP
Ditto all as per serial item No. 18.00 described here-in-before but capacity of pump 20 to 30 HP
Ditto all as per serial item No. 18.00 described here-in-before but capacity of pump 7.5 to 15 HP
Gland packing soft type with lead wool metallic lined superior quality as per sample of size 10/12mm complete all as specified and directed
S&F in repairs single phase preventor suitable for 3 phase, complete all as specified and directed.
S&F in repairs fully automatic star delta stater with citiation M Contactor & pneumatic Timers for 35 HP 3 Phase Overload relay Range 23-32 Amp Contactor type No1N Contactor rating 32 Amp, complete all as specified and directed.
Supply and fixing in replacement of rubber coupling of size 016 or suitable for non clog Pumpset of capacity 100 HP, including alignment of pump with motor complete all as specified and directed.
Supply and fixing in replacement of rubber coupling of size 015 or suitable for non clog Pumpset of capacity 60 HP, including alignment of pump with motor complete all as specified and directed.
Supply and fixing in replacement of rubber coupling of size 013 or suitable for non clog Pumpset of capacity 25 to 30 HP, including alignment of pump with motor complete all as specified and directed.
Supply and fixing in replacement of rubber coupling of size 014 or suitable for non clog Pumpset of capacity 12.5 to15 HP, including alignment of pump with motor complete all as specified and directed.
Supply and fixing in replacement of rubber coupling of size 019 or suitable for non clog Pumpset of capacity 12.5 to15 HP, including alignment of pump with motor complete all as specified and directed.
S&F in replacement star coupling of any size of any pump set including alignment of pump with motor complete all as specified and directed.
S&F in replacement ball bearing for pump and motor, of bearing No: 6309 complete all as specified and directed.
S&F in replacement ball bearing for pump and motor, of bearing No: 6311 complete all as specified and directed.
S&F in replacement ball bearing for pump and motor, of bearing No: 3309 complete all as specified and directed.
S&F in replacement of pump impellor suitable for non clog pump set of capacity 20 to 30 HP complete all as specified and directed.
S&F in replacement of pump impellor suitable for non clog pump set of capacity 100 to 50 HP as per sample complete all as specified and directed.
Supply, fixing, testing and commissioning centrifugal nonclog pumping set with CI impeller, CI Casting SS shaft & SS sleeve Size:150X150 mm minimum discharge capacity 100 LPS at 20 mtr head coupled with 100 HP 3 Phase induction motor 415 volt 50 Hz 1450 RPM as per TEFC IE2 including foundation as per manufacturer design and electric connection with suitable size of cable and all necessary connection for suction and delivery pipes along with coupling with existing motor and all holding arrangements including dismantling old unserviceable pump set and deposited to E&M store yard complete all as specified and directed. Note: Pump set shall be mounted on a Metal steel base frame and cost for the same shall be included in the quoted unit rates nothing extra shall be admissible on this account.
Supply fixing, testing and commissioning centrifugal nonclog pumping set with CI impeller, CI Casting SS shaft & SS sleeve Size:150X150 mm minimum discharge capacity 76 LPS at 20 mtr head coupled with 50 HP 3 Phase induction motor 415 volt 50 Hz 1450 RPM as per TEFC IE2 including foundation as per manufacturer design and electric connection with suitable size of cable and all necessary connection for suction and delivery pipes along with coupling with existing motor and all holding arrangements including dismantling old unserviceable pump set and deposited to E&M store yard complete all as specified and directed. Note: (a) Pump set shall be mounted on a Metal steel base frame and cost for the same shall be included in the quoted unit rates nothing extra shall be admissible on this account.
Supply only Nuts & bolt with 2 No. washers of any size complete all as directed by Engineer-in-Charge
Supply only rubber gasket of 3 mm thickness of any size complete all as directed by Engineer-in-Charge
Supply only grease to lubricant the pump set complete all as directed by Engineer-in-Charge
S&F in replacement Fully Automatic Star delta stater with Citiation M Contactor & pneumatic Timers for 75 HP 3 Phase Overload relay Range 45-65.0 Amp Contactor type E Contactor rating 65 Amp complete all as specified and directed.
Supply, laying, testing & commissioning of LT XLPE insulated, PVC sheathed, armoured, heavy duty cable, 1100 volts grade using stranded aluminium conductor, cross-sectional area 185 Sqmm 3.5 Core, confirming to IS specification includaing taking out existing unserviceable cable, complete all as specified and directed.
Ditto all as per serial item No. 43.00 described here-in-before but cross-sectional area of cable 50 Sqmm 3.5 Core.
Ditto all as per serial item No. 43.00 described here-in-before but cross-sectional area of cable 16 Sqmm 4 Core.
M&L for copper conductor multistranded, FR, PVC sheathed, Single core, 25 Sqmm wire incluading copper thimble and dismantling old wire complete all as specified and directed .
M&L for copper conductor multistrained, FR, PVC sheathed, Single core, 50 Sqmm wire incluading copper thimble and dismantling old wire complete all as specified and directed .
M&L for FR, multistrained, PVC Unsheathed, 1100 volts grade cable, Single core, copper conductor of size 16 Sqmm wire including copper thimble and dismantling old wire complete all as specified and directed .
M&L for cross arms, bracing, supports, clamps, jalli cover, pit cover and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape and size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including dismantling old cross arms etc. complete all as specified and directed.
Excavation in trench not exc. 1.5 mtr wide and not exc. 1.5 mtr in depth for foundation of poles/ laying of underground cable/ laying of pipe etc. and getting out in hard/dense soil complete all as specified and directed.
Returing filling in inciuding sperading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed.
Removing of surplus soil to a distance not exc 50 mtr and deposting where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
M&L for clean dry sand, laid in trench/ ducts for bedding and cushioning to cable, including sperading and levelling, complete all as specified and directed.
Supply & laying bricks, old size, sub class 'B' for protection of cable, laid dry, flat over the cable, complete all as specified and directed.
M&L for 80mm bore GI pipe line, light grade for protection of cable along the pole/ across the road crossing/ passing through culvert etc. including dismantling old pipe complete all as specified and directed.
Dismantling of reduction gear rotor mechanism and replacement of aerator rotor mechanism shaft with MS framed work as per sample, replacement of rubber & steel coupling as per sample, dismantling and disconnecting 15 HP reduction gear set from the electric motor and re-assembling on existing foundation and complete with motor after repair/ overhauling including testing on completion, complete all as specified and directed.
Repair & maintenance of LT Pannel board indoor/ outdoor type comprising of MCCBs as in coming and outgoing with digital mettering and control wiring by disconnecting all incoming and out going connection, opening of LT cable incl refixing of cables after proper lugging and glands complete. Cleaning of all compartment from in side and out side including using anti rust spray and checking and repair of all controls, switches, meters. etc (if found diffective) and painting complete panel board with two coat of synthetic enamel paint over a coat of red-oxide primer, after necessary scrapping and denting (Tint of paint colour shall be approved by GE). Refixing of panel board upon angle iron frame of size 50x50x6mm and embeded in PCC concrete of ratio (1:3:6) B2 type complete.
M&L for rubber sheet of thickness 3.5 mm with fabric backing or insert and plain coloured or marbled topping, matt or glossy, laid in floors with approved adhesive, complete all as specified and directed. Make: KRISHNA TILES/ POLYFIN/ NEELKAMAL/ MARBLEX/ ACCURA POLY TECH PVT LTD AHEMDABAD/ BOHR INDUSTRIES
Testing of biochemical oxygen demand and chemical oxygen demand report from the approved lab.
Dismantling of scrubber trolley system & rewinding of electric motor of capacity 3 HP, 415V size existing super enmaled copper wire, repalcement of chain pully system with chain, repair of reduction gear system, complete replacement of worn out/ unserviceable parts of system and re-assemblaing the complete after repair and testing on completion, complete all as specified and directed. Note:- Cost of all worn out spare parts shall be included in quoted the rates.
S&F in replacement Fully Automatic Star delta stater with Citiation M Contactor & pneumatic Timers for 60 HP 3 Phase Overload relay Range 42-54 Amp Contactor type E Contactor rating 50 Amp complete all as specified and directed.
VEDA INFRASTRUCTURE (BID ID -3072351)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .