Executive Engineer Machinery Division Jammu
Executive Engineer Machinery Division Jammu
Fire Detection and Alarm System for Proposed VYOM Institution for Multiple Disabilities at RS Pura, Jammu.
2026_PWDJK_316460_1
MDJ/Tech/e-NIT/2026-27/46
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
R S Pura
Please refer Tender documents.
2 documents required · 2 mandatory
₹200
Executive Engineer Machinery Division Jammu
₹4,605
16 Jul 2026
16 Jul 2026
31 Jul 2026
16 Jul 2026
30 Jul 2026
16 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Supplying, installation, testing & commissioning of smoke detector with built in LED and mounting base complete with all connections etc. as required | - | each | 100 | - |
| 2.01 | Supplying, installation, testing & commissioning of manual call boxes of M.S construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. | - | each | 101 | - |
| 3.01 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. | - | each | 102 | - |
| 4.01 | Supplying, installation, testing & commissioning of main control and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation, locking arrangement, audio and visual indication for fire alarm and public address system, monitoring system including connections, interconnections etc. complete as required.6 zone panel for fire alarm system 100 watt amplifier racks suitable for operation on 230V AC/24V DC supply conforming to IEC-268-3 complete with all accessories as required – 2 Nos. (One to act as standby).Talk back master station with LED PTT (press to talk) push button for operation on 230V AC/24V DC supply
conforming to IEC-268 for simplex mode of operation/communication suitable for 20 Nos. talk back unit – 1 set. Announcement control desk suitable for selection of different zones selectively and ON ALL CALL switch with visual indication etc., complete as required – 1 set.
Amplifier change over switch for inter changing amplifier – 1 No. Monitor panel for loudspeaker complete output selector ON/OFF switch, fuse visual indications etc. complete as required – 1 No. Gooseneck microphone with stand and ON/OFF switch – 1 No. Mains ON/OFF switch, fuse indication lamps, DC and AC voltmeters & ammeters terminal blocks etc. complete as required – 1 set. Battery charger trickle cum boost to take complete load of fire alarm & PA system complete with all accessories including providing & fixing of 2 Nos. 12 volt, 30 AH each sealed maintenance free batteries – 1 set. | - | each | 103 | - |
| 5.01 | Supplying and fixing 25 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. | - | rmt | 104 | - |
| 6.01 | Supplying and drawing 2 x 1.5 sq mm FRLS/HTFR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required. | - | rmt | 105 | - |
| 7.01 | Supplying and Fixing of Powder Portable ADC with MAP 90 Fire Extinguisher 4.0 Kg | - | each | 106 | - |
| 8.01 | Supplying and Fixing of Portable CO2 Fire Extinguisher 4.5 Kg | - | each | 107 | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.46 MB
BOQ_1031665.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].