14 Jan 2021, 1:00 pmClosed
SE ETC I MORADABAD
220 KV S/S CAMPUS MAJHOLA MORADABAD
WORK FOR COSTRUCTION OF 132 AND 33 KV BAYS FOR INCREASING CAPACITY FROM 1X63 PLUS 2X40MVA TO 1X63 PLUS 3X40 MVA AT 132 KV SUB STATION CHANDAUSI UNDER ELECTRICITY TRANSMISSION DIVISION SAMBHAL
2020_UPTCL_536295_2
E-T-97/ETCM/2020-21
Open Tender
Electrical Works
Fixed-rate
60 days
SAMBHAL
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE ETC MORADABAD
₹7,000
22 Jan 2021
4 Jan 2021
14 Jan 2021
4 Jan 2021
14 Jan 2021
4 Jan 2021
Amount
The following works are to be carried out at 132KV S/S, Chandausi under ETD-Sambhal.
145 KV CB with its structure.
145 KV CT 400/200/1A with junction box.
Erection & mounting of 145KV CT Junction Box
145 KV Bus Isolator with its mechanism
145 KV Tandem Isolator with its mechanism
120 KV LA with its base insulator and surge counter.
36KV VCB
36KV Isolator
132 KV Transformer & Control Relay Panel.
132 KV Post Insulator for support
33 KV Post Insulator for support
Erection of Main structure & Auxiliary structure
Sorting and stacking of main & auxiliary structure
Making hole in part of GI main auxiliary structure/cutting of GI angle drilling of hole existing / defective structure plate/ angle and grinding machine will be cost of men T&P etc.
Cutting straightening, bending, laying 700mm. below in side ground and above ground of following size of M.S. Flat.
Prepairing cable schedule of 132 & 33 KV Bay as per drawing.
Laying of following sizes of control cable :-
2Cx2.5 Sq. mm.
4Cx2.5 Sq. mm.
6Cx2.5 Sq. mm.
10Cx2.5 Sq. mm.
Termination of following sizes of cable :-
2Cx2.5 Sq. mm.
4Cx2.5 Sq. mm.
6Cx2.5 Sq. mm.
10Cx2.5 Sq. mm.
Stringing of 33 KV Main bus of R,Y,&B phases of Twin Zebra conductor
Complete interconnection of 132 and 33 KV T/F bay with ACSR Panther Conductor consisting of all the 132/33 KV T/F bay equipments & bus bar including cutting bending of associated works.
Preparation of Delta earthings of HV & LV LA s with 06 Nos. Of electrodes.
Painting of following old M.S earthing strip above ground level with one coat of red oxide primer and two coat of synthetic enamel paint including rubbing and cleaning including cost of all material, labour and T&P
Fabrication of protection wire mesh fencing of size 3x2 mtr. with 1”x1” square 10 SWG wire mesh including grouting by making plinth at 40 MVA, 132/33 KV T/F installed by cutting and fabrication of MS Angle 65x65x6mm. MS flat 50x6/25x6mm. installing 03 Nos. post insulator and with one coat of red oxide and two coat of bus green paint including all material labour and T&P except MS Angle, MS Flat, Post Insulator and P.G. Clamp which shall be supplied by the department free of cost.
Shifting work for spacing & installation of proposed 40MVA T/F
Dismantling of existing fire hut and shifting of dismantled material out side the switch yard. Construction of fire huts for keeping fire fighting equipmnet work involves as below:- Fixing of 02 No. 3.0 meter long and 06 Nos. 2.5 meter long vertical support from 65x65x5 mm GI angles and welding the piece of 10 cm angle from 65x65x5 mm in the bottom of support. Excavation of 08 Nos. pits of size 20x20x20 cm and concereting of 08 Nos. vertical supports with ratio of 1:2:4 of cement, coarse sand and 20 mm stone ballast in proper level and alignmnet. Fixing of top structure from 50x50x5 mm or 65x65x5 mm GI angle piece as per requirement. Welding theses pieces on vertical support to make the frame of hut type. Painting the stucture with two coats of red oxide synthetic enamels good quality paint. Supply and fixing of 6.0 mm thick grey color corrugated asbetos roofing in position with MS "J" nut & bolts including supply of required materials, labours and T&P etc. Flooring the complete hut by first class brick work in ratio 1:4 of cement and coarse sand with 12 mm thick plaster in ratio 1:2 of cement and coarse sand including these supply of related material and labour and T&P etc. (GI/MS angle iron will be provided by UPPTCL free of cost).
Dismantling of old & damaged 145 KV Isolator From old bay
Dismantling of 145 KV Breaker Old & Damaged with Mechanism & Structure From old Bay
SUPPLY
5- Bolted type double twin tension fitting for Zebra conductor for main bus .
Four bolted type P.G clamp made of aluminium alloy LM-6 suitable for Zebra to Zebra conductor complete with galvanized nuts, bolts spring & plain washers.
Four bolted type P.G clamp made of aluminium alloy LM-6 suitable for Zebra to Panther conductor complete with galvanized nuts, bolts spring & plain washers.
Three bolted type PG clamp made of aluminum alloy with spring washer and GI bolts, nuts suitable for Panther to Panther conductor.
Supply of Single post insulator clamp suitable for twin zebra conductor.
2 U Bolted type double suspension fitting made of aluminum alloy LM-6 suitable for single Panther conductor complete with hot dip galvanized nut, bolt and washer.
RAHUL AGRAWAL
QASIM ENGINEERING COMPANY
NAVEEN AND COMPANY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .