Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.1 LAccepted-AOC | L1 | Accepted-AOC AOC Awarded | |
| 2 | L2₹23.6 L+₹73,690 (3.22%)Rejected-Finance 96 1 HIMMATGANJ BEHIND UNANI MEDICAL COLLEGE PRAYAGRAJ 211001 | PRAYAGRAJ | UTTAR PRADESH | 211001 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹26.7 L+₹3.8 L (16.8%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹27.9 L+₹5.0 L (21.8%)Rejected-Finance 218 D 1A JYANTIPUR NEAR SHYAM PIPE FACTORY SULEM SARAI PRAYAGRAJ UP | PRAYAGRAJ | PRAYAGRAJ | UP | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹29.7 L+₹6.8 L (29.6%)Rejected-Finance | L5 | Rejected-Finance Other than L1 |
Tender Value
Refer Docs
EMD Value
₹99,680
Closing Date
15 Oct 2022, 6:55 pmClosed
GE WEST ALLAHABAD
GE WEST ALLAHABAD NEW CANTT ALLAHABAD
REPAIR AND MAINT OF DG SETS, REPAIR AMF PANEL, LAUNDRY PLANT AND REPAIR TO TURBO CHARGER, SELF STARTER, BATTERY CHARGER, REPLACEMENT OF BATTERY AND ITS ASSOCIATED WORK AT NEW CANTT ALLAHABAD
2022_MES_552643_1
8591/E8
Open Tender
Civil Works
Item Rate
270 days
NEW CANTT ALLAHABAD
Please refer tender documents
7 documents required · 7 mandatory
₹500
GE WEST ALLAHABAD
₹99,680
Yes
1 Dec 2022
17 Sept 2022
17 Oct 2022
17 Sept 2022
15 Oct 2022
1 Oct 2022
Amount
M&L periodical servicing of diesel engine driven Gen set 3 phase 415 volts 50 c/s AC supply by cleaning thoroughly and replacing fuel filters ,air filters, oil filters draining out engine oil etc. and replacing with new oil, tightening of all gaskets , connection of battery terminals, electric cable connections foundation bolts, coupling bolts etc including test running and tappet setting of alternator by checking and setting of voltage and frequency all as directed by Engr-in-charge. MAKE OF DG SET : Kirloskar/ Crompton greaves/Cummins. Make of filters : kirloskar/CG/Fleet guard/MICO Note:Engine oil, Fuel filters, Air filters, oil filters replaced will be measured and paid separately under respective item of sch 'A' . for following capacities of DG set
320/380 KVA DG SET
250/200 KVA DG SET
100 KVA DG SET
63/62.5 KVA DG SET
40/50 KVA DG SET
25/30 KVA DG SET
7.5/20 KVA DG SET
Supply and fixing in replacement of maintenance free battery with initially charged capacity 180 AH , 12 Volt complete all as specified and as directed. Make :- Exide/Amron
Supply and fixing in replacement of maintenance free battery with initially charged capacity 150 AH , 12 Volt complete all as specified and as directed. Make :- Exide/Amron
Supply and fixing in replacement of maintenance free battery with initially charged capacity 90 AH , 12 Volt complete all as specified and as directed make :- Exide/Amron
Supply, fixing & testing in replacement of Radiator of 320 KVA DG Set water cooled of kirlokar make withcopper tubings including replacement of connected items such as inlet & outlet rubber hoses & all other connected items
Supply, fixing & testing in replacement of Radiator of 62.5 /100 KVA DG Set water cooled of kirlokar make withcopper tubings including replacement of connected items such as inlet & outlet rubber hoses & all other connected items
M&L for replacement of UNSV radiator hose pipe set complete as per sample of D G set of following capacity
320/380 KVA DG SET
250/200 KVA DG SET
100 KVA DG SET
63/62.5 KVA DG SET
40/50 KVA DG SET
25/30 KVA DG SET
7.5 /15 KVA DG SET
M & L for replacement of UNSV fan belts as per sample for DG sets of following capacity. MAKE: Fenner/ Grip/ Dunlop
Fan belt for 320/380 KVA DG Set
Fan belt for 250/200 KVA DG Set
Fan belt for 100 KVA DG Set
Fan belt for 63/62.5 KVA DG Set
Fan belt for 40/50 KVA DG Set
Fan belt for 25/30 KVA DG Set
Fan belt for 7.7/15 KVA DG Set
M&L in replacement of stranded copper conductor battery lead for 24 volts D C grade red for (+)ve terminal and black for (-)ve terminal fitted with battery terminal at one end & battery lug at other end complete length 1.5 mtr.
M & L for cleaning of radiator by cleaning agent/Radiwash (make:fleetguard/coolguard) including removal/ dismantling of radiator from engine transporting to work shop or cleaned at site , soldering / brazing,testing for any leakage , remounting to its original position as per entire satisfaction of Engr - in-charge for following capacity of DG Set.
DG Set 320/380 KVA DG Set
DG Set 200/250 KVA DG Set
DG Set 100 KVA DG Set
DG Set 63/62.5 KVA DG Set
DG Set 40/50 KVA DG Set
DG Set 25/30 KVA DG Set
DG Set 7.5/15 KVA DG Set
M & L for replacement of set of hose clips for DG sets of following capacity
DG Set 320/380 KVA DG Set
DG Set 200/250 KVA DG Set
DG Set 100 KVA DG Set
DG Set 63/62.5 KVA DG Set
DG Set 40/50 KVA DG Set
DG Set 25/30 KVA DG Set
DG Set 7.5//20 KVA DG Set
M&L for coolant radicool SFO premix of Castrol or equivalent of Shell/volvoline
M&L to drain out the old used engine oil from sump of DG sets& cleaning & refilling with new engine oil 15 W 40 up to required level including topup Make : Castrol/ HP or equivalent of shell
M&L for replacement of defective self starter assembly by new self starter assembly 12/24 volts make: lucas / Bosch
-ditto – all as per item No. 13 above but alternator assembly
M&L in for replacement of PCB card Procom R E L-7-1.0 for 250/100 KVA AMF pannel
M&L in for replacement coil Relay-24 volts,5 Amp 240 volt AC 5Amp 30 volts DC model HJQ 22 F –VZ make YOI/ Siemens for 160/100 KVA AMF pannel
M&L in for replacement coil Relay-24 volts,5 Amp 240 volt AC 5Amp 30 volts DC model HJQ 22 F –VZ make YOI/ Siemens for 62.5/40 KVA AMF pannel
M&L in for replacement of timer switch 0 to 80 seconds Make Siemens for 160/100 KVA AMF pannel
M&L for servicing of DG set 200/250 KVA AMF panel,setting of time delay switch ,tightening of all electrical incoming & outgoing connections including replacement of cable lugs& adjustment of solenoid switches& Relays
M&L for servicing of DG set 100 KVA AMF panel,setting of time delay switch ,tightening of all electrical incoming & outgoing connections including replacement of cable lugs& adjustment of solenoid switches& Relays
M&L for servicing of DG set 62.5/40 KVA AMF panel,setting of time delay switch ,tightening of all electrical incoming & outgoing connections including replacement of cable lugs& adjustment of solenoid switches& Relays
M & L for painting of Generating set of capacity 100 KVA to 320 KVA complete in existing colour with two coat of synthetic enamelled paint by spray machine over one coat of primer after preparation of surfaces installed at Hisar Mil Stn complete all as specified and as directed.
M & L for painting of Generating set of capacity 7.5 KVA to 63 KVA complete in existing colour with two coat of synthetic enamelled paint with spray machine over one coat of primer after preparation of surfaces installed at western & eastern pocket drainage pump House complete all as specified and as directed.
Supply and replacing in repair Euroload four pole change over with advance Neutral On load change over switch I-O-II ,Current Rating 100 Amps, 415 Volts complete all as specified and directed.
Supply and replacing in repair Euroload four pole change over with advance Neutral On load change over switch I-O-II ,Current Rating 200 Amps,415 Volts complete all as specified and directed.
Supply and replacing in repair Euroload four pole change over with advance Neutral On load change over switch I-O-II ,Current Rating 400 Amps, 415 Volts complete all as specified and directed.
Supply only Diesel Filter suitable for 7.5 KVA to 100 KVA DG set Make - Kirloskar/CG/KG/Cummins
Supply only Diesel Filter suitable for 200 KVA to 320/380 KVA DG set Make - Kirloskar/CG/KG/Cummins
Supply only Lub Oil filter suitable for 7.5 KVA to 100 KVA DG set Make - Kirloskar/CG/KG/Cummins
Supply only Lub Oil Filter suitable for 200 KVA to 320/380 KVA DG set Make - Kirloskar/CG/KG/Cummins
Supply only Air filter suitable for 7.5 KVA to 100 KVA DG set Make - Kirloskar/CG/KG/Cummins
Supply only Air Filter suitable for 200 KVA to 320/380 KVA DG set Make - Kirloskar/CG/KG/Cummins
Supply & fixing spare parts & accessories of original make for repair of DG set under serial items No 1.02 to 1.03 here-in-before all as directed by Engr-in-Charge :- 01 Nos DG sets Notes :- All spares & accessories shall be fixed in the DG set only after prior inspection & Approval of Engineer-in-Charge for which these shall be produced by the contractor at store yard of AGE E/M New Cantt
Kit Fuel filter
Kit Lub oil filter
Kit bypass filter
Kit Air cleaner
Air filter
Upper Gasket set (Cylinder head)
Valve exhaust
Valve inlet
Valve seat Exhaust
Valve seat Inlet
Guide valve
Collet Volve
Spring valve
Kit turbo charging
Collar thrust
Kit injector
Kit Piston and ring set
Kit Cylinder liner
Kit Sump Gasket
Gear pump assembly (Fuel pump FIP)
Weight & carrier
Barrel sleave
Gasket Set
Sexen filter
Governor Pressure valve (Hydraulic Governor)
Gear assembly
Ball bering
Head gasket
Nozzle
Block
Liner
Battery terminal
Packing Kit
Crank
Main bearing
CR bearing
Came bush
Connecting Rod
Rod balancing
Third washer
Valve seal
Supply & fixing spare parts & accessories of original make for repair of DG set under serial items No 1.04 & 1.05 here-in-before all as directed by Engr-in-Charge :- 03 Nos DG sets Notes :- All spares & accessories shall be fixed in the DG set only after prior inspection & Approval of Engineer-in-Charge for which these shall be produced by the contractor at store yard of AGE E/M New Cantt
Kit Fuel filter
Kit Lub oil filter
Kit bypass filter
Kit Air cleaner
Air filter
Upper Gasket set (Cylinder head)
Valve exhaust
Valve inlet
Valve seat Exhaust
Valve seat Inlet
Guide valve
Collet Volve
Spring valve
Kit turbo charging
Collar thrust
Kit injector repair
Kit Piston and ring set
Kit Cylinder liner
Kit Sump Gasket
Gear pump assembly (Fuel pump FIP)
Weight & carrier
Barrel sleave
Gasket Set
Sexen filter
Governor Pressure vlave (Hydraulic Governor)
Gear assembly
Ball bering
Head gasket
Nozzle
Block
Liner
Battery terminal
Packing Kit
Crank
Main bearing
CR bearing
Came bush
Connecting Rod
Rod balancing
Third washer
Valve seal
Dismantling of DG Set Alternator of cap 63/62.5/ KVA carefully and carry to authorised workshop for repair and re-fixing the same in its original position after repair and testing the same up to satisfaction of AGE E/M complete all as direted.-04 Nos
Cutting out old burnt winding of alternator, cleaning the slot of stator and rewinding the same with super enamelled copper winding wire of appropriate gauge complete with all insulating materials, Nomex paper, cotton tape, glass sleeve, soldering rod, Grease etc complete.
Repairing of armature shaft both side by depositing metal on it, grinding & polishing to make appropriate size of the shaft complete.
Supply and replacing Ball bearing at DE (Driven End) side of No.6310 Make-NBC/SKF-01 No for 63/62.05 KVA
Supply and replacing rectifier Diod for 63/62.5 KVA
Supply and replacing AVR (Automatic Voltage Regulaotr) for 63/62.5 KVA
Supply and replacing connetion plate of suitable size for 63/62.5 KVA
Dismantling of DG Set Alternator of cap 100/200/250 KVA carefully and carry to authorised workshop for repair and re-fixing the same in its original position after repair and testing the same up to satisfaction of AGE E/M complete all as direted.-01Nos
Cutting out old burnt winding of alternator, cleaning the slot of stator and rewinding the same with super enamelled copper winding wire of appropriate gauge complete with all insulating materials, Nomex paper, cotton tape, glass sleeve, soldering rod, Grease etc complete for 100/200/250 KVA size.
Repairing of armature shaft both side by depositing metal on it, grinding & polishing to make appropriate size of the shaft complete for 100/200/250 KVA size.
Supply and replacing Ball bearing at DE (Driven End) side of No.6310 /6311/6312/6314 Make-NBC/SKF-01 No for 100/200/250 KVA size.
Supply and replacing rectifier Diod for 100/200/250 KVA size.
Supply and replacing AVR (Automatic Voltage Regulaotr) for 100/200/250 KVA size.
Supply and replacing connetion plate of suitable size.
Dismantling of DG Set Alternator of cap 15/25/40 KVA carefully and carry to authorised workshop for repair and re-fixing the same in its original position after repair and testing the same up to satisfaction of AGE E/M complete all as direted.-02 Nos
Cutting out old burnt winding of alternator, cleaning the slot of stator and rewinding the same with super enamelled copper winding wire of appropriate gauge complete with all insulating materials, Nomex paper, cotton tape, glass sleeve, soldering rod, Grease etc complete for 15/25/140 KVA
Repairing of armature shaft both side by depositing metal on it, grinding & polishing to make appropriate size of the shaft complete for 15/25/140 KVA.
Supply and replacing Ball bearing at DE (Driven End) side of No.6310 /6311/6312/6314 Make-NBC/SKF-01 No for 15/25/140 KVA.
Supply and replacing rectifier Diod for 15/25/140 KVA.
Supply and replacing AVR (Automatic Voltage Regulaotr) for 15/25/140 KVA.
Supply and replacing connetion plate of suitable for 15/25/140 KVA size.
Supply and fixing (in repair) MCCB 100 Amps, 415 Volts, 4 Pole, breaking capacity 16/25 KA, ISI Marked, Fix type, Make- C&S/ L&T/Indo-Asian/Havells
Supply and fixing (in repair) MCCB 200 Amps, 415 Volts, 4 Pole, breaking capacity 25KA, ISI Marked, Fix/ Adjustable type, Make- C&S/ L&T/Indo-Asian/Havells
M&L for repair/overhauling of existing starter panel board of any size/type including cleaning with compressed air tightening of all electric connections to switces including repair/replacment of existing MCB/ switch fuse disconnector units each of any rating including testing complete with fixing of door (front & backside) with proper fixing & locking arrangement replacement of wornout lugs, nut, bolts, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire and llugs, proper connention to main earth lead, to be provided/replaced as required at cable entries, fixing of door front & back with copper locking arrangement as requred as site and painting with spary machine with super eanameled paint light grey paint in outer/ inner side of pannel after cleaning and prepaing surface including sign writing complete all as spcified and directed Note : spares part to be repalaced shall be measured and paid sparately as supply only
(a). Contractor TF 34 make siemns or equivalent approved
(b). Supply only Conactor TF 30 Make Siemens or equivalents approved
(c). Supply only Conactor TF 31 Make Siemens or equivalents approved
(d). Supply only PVC Connector
(e). Supply only Over Load Relay capacity 20-30 amp Make Siemens or equivalents approved
(f). Supply only Over Load Relay capacity 10-20 Make Siemens or equivalents approved
(g). Supply only MCB TPN 63 amps 'C' series 415 Volt
(h). Supply only MCB TPN 32 amps 'C' series 415 Volt
S & F in replacement of Exhaust silencer complete with muffler of 100 KVA/62.5 KVA DG set complete connects engine and DG silencer to drive away hot gases generated during operation of DG to atmosphere through silencer complete.
Dismantling and taking out the self starter,12 Volt DC fitted in 15 to 62.5 KVA 3 phase 50 HZ of DG sets and strip opening of Self starter 12 Volt DC for carrying out repair/ servicing /overhauling mechanically ,cleaning, oiling/greasing/varnishing, fixing of serviceable parts in position, removing & replacement of defective / unserviceable parts with new parts, complete and re-assembling of Self starter 12 Volt DC after repair/ servicing /overhauling and fixing the same in position and testing complete all as specified and directed . Notes :- (i) Repairs/servicing / reassembling and testing of Self starter 12 Volt DC shall be carried out through a authorised service center .(ii) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers, shim, small springs, screws/gaskets/ packing /studs etc. (iii) The quoted rates of contractor are deemed to be included cost of transportation to and fro authorized service centre.
Supply only the following items/spare parts suitable for self starter, 12 Volt DC fitted in 15 KVA to 62.5 KVA 3 phase 50 HZ of DG set , dismantled/fixed under Sch `A` item No 43 here in above complete all as specified and directed. Note :- (i) Fixing element of these items is included under the rates quoted by the contractor for Schedule `A' item No 16 here in above. (ii) Contractor shall have no claim on account of variation of quantities of any item or non execution of any item.
(a). Solenoid switch suitable for self starter, 12 Volt DC
(b). Commutator suitable for self starter, 12 Volt DC
(c). Carbon brush suitable for self starter, 12 Volt DC
(d). Field coils suitable for self starter, 12 Volt DC
(e). Bendix pinion assembly suitable for self starter, 12 Volt DC
(f). Bushe suitable for self starter, 12 Volt DC
Supply & fixing of micro processer start/stop control PCB panel for 250/100/62.5 KVA DG set by taking out unserviceable relay complete with following parameters Make: Kirlosker/ Greaves /Cummins (a) Individual phase current (Amps) (b) Phase voltages (V) (c ) Generator output frequency (Hz) (d) Engine water temperature (Deg.C) (e) Lube oil pressure (kpa) (f) Working hours (g) Push button (Starter) & (stop) (h) LED indications for main function
Material & labour for replacement of unserveceable interconnection wiring and its interlocking system in AMF electric control panel for DG set with using and including PVC insulated and unsheathed stranded copper conductor cable, single core, minimum 1.5 Sqmm size or as required 1100 Volts grade cable for making functional controls of the DG set, auxiliary contactor, push buttons, indicator, amps meter, volt meter complete as required at site for functioning of DG set in auto and manual mode, checking AC/DC circuits and removing & replacement of defective / unserviceable parts with new parts, complete all as specified and directed . Notes : (i) The complete panel shall be checked and tested on full load after necessary repairs and replacement of unserviceable wiring. for its smooth functioning and proper interlocking including shutt down on high water tempreture and low Oil pressure. (ii) All control wires shall be properly bunched, tied, ferruled for proper identification and crimped with adequate size of copper lugs. the cost of same are deemed to include under these items. (iii) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers, shim, small springs, screws/gaskets/ packing /studs etc.
Supply only the following items/spare parts suitable for AMF pannel of DG set , dismantled/fixed under Sch `A` item No 46 here in above complete all as specified and directed. Note :- (i) Fixing element of these items is included under the rates quoted by the contractor for Schedule `A' item No 46 here in above. (ii) Contractor shall have no claim on account of variation of quantities of any item or non execution of any item.
(a). Electronic timer,on delay type, dual range, suitable of 220 Volts/ 24 Volts, 2NO+2NC, 50 Hz, AC supply/ DC supply , for 0-60 seconds .
(b). Power contactor 3 pole with 2NO + 2NC auxiliary contacts, coil voltage 220 volts, AC 3 rating 300/325/330 Amps. Complete all as specified and directed .
(c). Power contactor 3 pole with 2NO + 2NC auxiliary contacts, coil voltage 220 volts, AC 3 rating 400 Amps. Complete all as specified and directed .
(d). Power Contactor No volt coil suitable for 400Amp Contactor
(e). Power Contactor No volt coil suitable for 300/325/330 Amp Contactor
(f). Auxilliary relay 8 pin, 24 Volts ,DC , 2 change over.
(g). Auxilliary relay 8 pin, 220 Volts , AC , 2 change over.
(h). Bimetal under volt / over volt relay suitable for 3 phase, 3 wire with 2 NO+2NC auxiliary contacts
(j). Engine starting relay with sequence timer & Master timer suitable for 12 / 24 Volts DC supply.
(m). Indicating lamps LED type with holder for 12 / 24 volts DC supply
(o). Digital electronic volt meter 0-50 V range suitable for 12 / 24 volt DC supply panel flush pattern square type size 96mmX96mm
(p). Digital electronic volt meter 0-500 V range suitable for 415 Volts panel flush pattern square type size 96mmX96mm
(r). HRC fuse DIN type with base for AC circuit 415 volts having rating of 400 Amps .
M & L for Cleaning of MS fuel tank of DG sets of 100 to 380 ltr capacity by collecting the fuel in cleaned barrels and removing sludge deposited/accumulated inside the tank of and disposal of sludge at a distance not exceeding 100 metre and cleaning the tank with kerosene oil , replacement of fuel tank strainer and unserviceable fuel gauge with new PVC fuel level indicator fixed with clips to the tank and marking levels for every 10 litre by marking and numbering on the side of fuel tank with synthetic enameled paint and refilling the collected fuel after filtration complete all as specified and directed.
Section 'B' ( Mechanical Loundary)
S&F in replacement on load change over switch (side handle) in sheet enclosure 415 V AC 50 Hz 100 Amps capacity includimg necessary connections with suitable size aluminuium conductor cable and lugs complete all as specified and directed
S&F in replacement on load change over switch (side handle) in sheet enclosure 415 V AC 50 Hz 200 Amps capacity includimg necessary connections with suitable size aluminuium conductor cable and lugs complete all as specified and directed
S&F in replacment of DOL Starer three phase 415 V suitable for 5 HP motor including connection and fixing completed all as specifed and directed
Quarterly Periodical, preventive and comprehensive maintenance of hydraulic pump of steam boiler for lifting of water to steam coil and overhauling of hydraulic pump of steam boiler including replacment of head valve seat, fibre gland copper bush, repairing of connecting rod, replacement of bearing and bush of required size complete in all respect all as specified and directed. Note;- Repair & maintencance work to be carried out by OEM i.e. FABCARE/FABTECH Engg
Quarterly Periodical, preventive and comprehensive maintenance by de-scaling of boiler with high pressure descaling pump of 600 Kg/hour boiler capacity by using suitable chemical powder including necessary T&P arrangement as required at site complete all as specified and directed
S & F in replacement of FRP Vessel pentair of capacity 1000 ltrs per hours including connetion with existing system complete all as specified and directerd.
Quaterly periodical and preventive servvicing of indstrial RO Plant disconnecting piping arrangement including cleaning wasing completed all as speicifed and directed
M & L for Opening the vessel paintier and taking out old filter media and filling for new sand and carbon filter media all as directed.
S& F in replacement of Membrane filter for 500ltr/hrs capacity RO plant
S & F inreplacement of pump 1/2 HP 230 volts complete with inlet & out let valve 20/25 mm dia .
S & F inreplacement of Anti scalent filter for 500ltr/hrs capacity RO plant
S & F jambo housing
S & F soloniod valve 20/25 mm dia
S & F inreplacement High pressure vertical pump for RO plant 1000ltr/hrs complete
Material & labour in replacement of steam coil of boiler of material of BS 3059 including re-fixing cover plate, photocell, nozzle, hose connection, pipe line etc of oil fired boiler incl all connection complete all as specified and directed
Checking & repairing of sealed unit of HT transformer & replacement of transformer core, refixing and sealing of transformer control panel complete all as specified & directed.
Supply & replacement of all hoses of fuel pump, calibration of fuel pump, setting of valve for proper delivery of fuel to the nozzle complete all as specified & directed
Checking & repairing of 30 Kg/cms air compressor, by oiling, greasing and servicing including painting with one coat of synthetic ennamalled paint complete all as specified and directed.
Material and labour for rewinding of 3 HP motor 3 phase, 415 volt incl painting with one coat of synthetic ennamalled paint complete all as specified and directed.
Opening, checking, repairing & cleaning of boiler economiser, decorbonising of tubes, brushing, flushing of outer dia and inner dia of tubes and refixing incl replacement of wornout gasket, nut, bolts etc. at both end, cleaning of chimney complete all as specified & directed.
Quarterly Periodical, preventive and comprehensive maintenance of 30 Kg washer extractor for proper functioning, repair/replacement of temperature controller, sensor, limit switch, hydraulic locking device, electrical locking device, V belt ribbed type incl adjustment of bush after replacement of belt, oiling/greasing and alignment of motor with proper tighting of belts complete all as specified & directed
Quarterly Periodical, preventive & comprehensive maintenance by disconnection, dismantling & taking out all mechanical/electrical/electronic circuit connections old steam roller ironer, removing of hot iron steam plate, taking out roller from machine, repairing of uneven surface of base material and damage sheet cover cloth, refixing of base material/parts incl replacement of new cloth cover as per sample of 20 mtrs length on roller base material, stiching of convas cloth & refixing of pedestal roller on machine & re-fixing of all electrical/electronic/mechanical connection & testing of machine complete all as specified & directed
S & F in replacement of CR steel scrap for wrapping surrounding the roller complete all as specified and directed.
Repair, servicing, calibration and programing of variable frequency drive including replacement of minor parts as required and rewiring of control wiring complete all as specified & directed. Note for item No. 1 to 12: Repair & Maintenance work to carried out by OEM i.e. FABCARE/FABTECH Engg .
Repair and replacement of PLC unit suitable for washer extractor
Repair and replacement of HMI unit suitable for washer extractor (touch screen type)
S & F inreplacement of industrial ironining machine complete with ironing table and piping arrangemet complete
S&F in reoair fire hydrant landing valve type A Single headed outlet of63mm dia conforming to is 5290
S&F in reoair fire hydrant landing valve type B double headed outlet of 63mm dia conforming to is 5290
S&F in repair hose pipe box for keeping 2 nos hose pipe of length 15 mtr each branch pipe nozzel coupling etc of MS sheet of thickness 2mm
S&F in repair 63mm dia hose 15 mtr long hose coforming to IS-636 complete with maie and femaie coupling cnforming to IS-903.
S&F in repair fire hydrant stand post with provn of single outlet conforming to IS-908
Repair and replacement of wornout parts after taking out from installation shifting to civil wksp rewinding motor cleaning greasing and refitting at installation to electric driven jockey motor with pumps delivering 180 LPM upto 70 mtr head
Repair and replacement of wornout parts after taking out from installation shifting to civil wksp rewinding motor cleaning greasing and refitting at installationto electric driven jockey motor with pumps delivering 180 LPM above 70 mtr head upto 90 mtr.
S&F in repair 63mm dia gun metal branch pipe with 12.5 mm nozzel conforming to IS-903.
Repair&maint of diesel engine driven fire pump horizontal end suction,complete servicing/overhauling and replacement of all warn out parts centrifugal ci casing and bronze impellar stainless steel shaft suitable for delivering 1620 LPM 70 mtr head, 1800RPM.
Repair&maint of booster motor and pump15 HP30 mtr head discharge 450 LPM complite taking out and refixing after rewinding of motor complite.
Supply and replacement of 80 mm bore MS flanged heavy duty pipe for multi storied bldg duly painted complete all as specified and directed
All as per item No-113 above but 150mm bore pipe
S&F in repair 80 mm bore hand operated butterfly valve pressure not less than 15kg/sqcm with complete set
S&F in replacement of pressure gause 100 mm dia with ball valve of pressure 25 KG/sqcm
S&F in replacement of CI wafer type check valve 80mm bore tested to pressure of 15 KG/sqcmcomplite set.
S&F in replacement of CI wafer type check valve 100mm bore tested to pressure of 15 KG/sqcmcomplite set.
S&F in repair 150 mm bore hand operated butterfly valve pressure not less than 15kg/sqcm with complete set
Supply, installation, testing and commissioning in replacement of indoor type cubical panel board suitable for 3 phase, 4 wire, 415V, 50 Hz and CPRI approved manufacturer factory fabricated with CRCA sheet not less than 3 mm thick having modern fabrication process powder coating in approved shade provided with suitable gaskit to make it dust and varmin proof and general constructions conforming to IS : 8623/93. The LT panel shall be front and back openable and duly compartmentalized for each control gears.The panel should have suitable size of aluminium Bus -bar three phase 4 wire system having current carrying capacity 400 Amps of the incomer MCCB. The panel should have the following incoming and out going controlls duly fixed with the panel by means of suitable link plates complete all as specified and as directed by Engineer -in-charge. (PCC platform of suitable size for mounting the LT Panel is deemed to be included in the quoted rate )
M&L for earthing with galvanised earth plate electrode 600x600x6mm thick burried directly in ground (earth pit not less than 2.25 deep below ground level) with top edge of the plate not less than 1.5 mt below normal ground level connected to galvanised iron wire 4 mm dia as earthing lead protected by GI pipe medium grade 15 mm bore for protection of GI earth wire and 20 mm bore GI pipe medium grade for watering with alternate layer of char coal dust and salt including all accessories like nut bolts, redecer, napple wire mesh/screended funel and making brick machinery finished chamber of intern size 300x300x300mm with concrete base covered with a cost iron hinged cover resting over the cost iron frame painted with black betuminus paint which shall be imbedded in the block machinery including excavation work refilling connecting to main switch/MCB DB for feeding the electric supply all as spcified and directed and shown in electrical plate No. 3 of SSR Part-I and testing the earth resistance as required
S&F the following spare parts for lift:-
(a) M&L Automatic rescue Divce Card
(b) Display Board
(c ) Door Sensor
(d ) Micro processor card
(e) Door drive unit
(f) 12 Volt Batterry 7 AH
M/S SHIV BALLABH MISHRA
ARADHYA ENTERPRISES
M/s RAM LAKHAN GUPTA
PITAMBARI TRADERS
P S TRADERS
Avion Industries
ASIA ENGINEERING WORKS
M/S Satyam Associates
TRINITY CONSTRUCTION
MTR GROUP & COMPANY
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .