Lt Col Aditya Vanka
GE Navy Lakshadweep Coast Guard Road Kavaratti Island UT Of Lakshadweep 682 555
MAINTENANCE AND REPAIRS TO INTERNAL WIRING FITTINGS AND FIXTURES REWINDING OF CEILING FANS EXHAUST FANS SOLAR WATER HEATERS ELECTRIC GEYSERS AND COOLING APPLIANCES AT MINICOY ISLAND UNDER GE NAVY LAKSHADWEEP
2021_MES_476028_1
8301/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Minicoy
As per Tender documents
8 documents required · 8 mandatory
₹500
GE Navy Lakshadweep
₹26,000
Yes
9 Jun 2022
17 Sept 2021
18 Oct 2021
17 Sept 2021
15 Oct 2021
1 Oct 2021
18 Sept 2021 - 27 Sept 2021
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc.... removing materials to store for keeping in safe custody or for taking credit (credit for above items shall be made as per their conditions on site, separately) and making good disturbed surfaces of walls, floors, etc. complete all as specified and directed by Engineer-in-Charge.
Taking down carefully by unscrewing from boards/outlet boxes, fittings and fixtures such as switches, sockets ,ceiling roses, lamp holders, brackets, ceiling fittings, bulk head fittings, tube light fittings and regulators, etc... complete all as specified and directed by Engineer-in-Charge.
Material and labour for Point wiring with PVC insulated unsheathed and multistranded copper conductor cable, ISI marked, 1100 volt grade, FRLS of size 1.5 Sqmm drawn in and including concealed PVC rigid conduite of size not less than 20mm dia with modular metal flush box concealed and modular white plates with frame of suitable size as required at site with PVC insulated unsheathed stranded copper conductor of size 1.5 Sqmm as earth wire connected to common earth dolly as specified for one light point controlled by one switch for light/Fan complete all as specified and directed by Engineer-in-Charge. Note : (i) Rate quoted shall be deemed to include cost of modular metal flux box (concealed) and making good to walls (ii) Rate include the modular white cover plate with frame. (iii) Necessary blank plate as required at site.
Description all as per Sl item No, 03 here in before but one 3 pin 5 amps switch sockets on same board complete all as specified and directed by Engineer-in-Charge.
Description all as per Sl item No, 03 here in before but one 3 pin 5 amps switch sockets on independent board complete all as specified and directed by Engineer-in-Charge.
Description all as per Sl item No, 03 here in before but with cable size 2.5 Sqmm and 2.5 Sqmm as earthwire for 3/5 pin socket out let independent, 15/16 Amps, complete all as specified and directed by Engineer-in-Charge.
Supply and fix modular switch, 1 way, 6A, 1 module complete all as specified and directed by Engineer-in-Charge.
Supply and fix modular socket, 6A, 2/3 pin, combined 2 module complete all as specified and directed by Engineer-in-Charge.
Supply and fix modular switch, 1 way, 16A, 1 module, complete all as specified and directed by Engineer-in-Charge.
Supply and fix modular socket, 6/16A, 2/3 pin, combined 2 module complete all as specified and directed by Engineer-in-Charge.
Disconnection and removing the unserviceable 3 runs of 1.5 Sqmm PVC insulated unsheathed cable from the existing conduit/ casing caping and supply and fix 3 runs of 1.5 Sqmm PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor drawn in the existing metal/ PVC conduit & Casing capping including connecting of the ends into the switch / socket/ DB complete all as specified and directed by Engineer-in-Charge. Note : Three runs of cable measured as one unit.
Description all as per Sl Item No 11 here in before but of 3 runs of 2.5 Sqmm.
Description all as per Sl Item No 11 here in before but of 3 runs of 4 Sqmm.
Supply and fixing in replacement switch, piano flush type, single pole, one way, 5 amps, 230 volts, ISI Marked, complete all as specified and directed by Engineer-in-Charge.
Supply and Fixing in replacement switch socket combination, flush type, universal 2 in 1, 3 pin, 5 Amps, 230 volts, ISI Marked, complete all as specified and directed by Engineer-in-Charge.
Description all as per Sl Item No 15 here in before but of capacity 15 Amps.
Supply and fix in repairs Ceiling rose 3 terminal 5 Amps 230 volts ISI marked, PVC Polycarbonate, insulated body, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement Fan step Regulator, 120 Watt, 2 module, hum free complete all as specified and directed.
Supply and fix in replacement modular switch, 1 way, 6A, 1 module complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement modular socket, 6A, 2/3 pin, combined 2 module complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement modular switch, 1 way, 16A, 1 module complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement modular socket, 6/16A, 2/3 pin combined 2 module complete all as specified and directed by Engineer-in-Charge.
Material and labour for Submain wiring with Two runs of 2.5 sqmm size multi stranded copper conductor PVC insulated unsheathed cable (FRLS) in and including PVC rigid non metalic conduit and one run of PVC insulated cable of size 2.5 sqmm size multi stranded copper conductor PVC insulated and unsheathed for continious earth wire including taking down old existing submain wiring complete all as specified and directed by Engineer-in-Charge. Note: Rate quoted shall deemed to include for making good to walls as existing.
Material and labour for Submain wiring with Two runs of 4 sqmm size multi stranded copper conductor PVC insulated unsheathed cable (FRLS) in and including PVC rigid non metalic conduit and one run of PVC insulated cable of size 4 sqmm size multi stranded copper conductor PVC insulated and unsheathed for continious earth wire including taking down old existing submain wiring complete all as specified and directed by Engineer-in-Charge. Note: Rate quoted shall deemed to include for making good to walls as existing.
Material and labour for Submain wiring with Two runs of 6 sqmm size multi stranded copper conductor PVC insulated unsheathed cable (FRLS) in and including PVC rigid non metalic conduit and one run of PVC insulated cable of size 6 sqmm size multi stranded copper conductor PVC insulated and unsheathed for continious earth wire including taking down old existing submain wiring complete all as specified and directed by Engineer-in-Charge. Note: Rate quoted shall deemed to include for making good to walls as existing.
Supply and fix in replacement switch piano flush button type 5 Amp single pole one way complete all as specified and directed.
Supply and fix in replacement Modular Bell push, 5 Amps, 1 module complete all as specified and directed.
Supply and fix in replacement Bell electric ding dong AC 230 V single pole complete all as specified and directed by Engineer-in-Charge.
Supply and fixin replacement switch bell push button type 5 Amp, single pole complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement Surface and wall mounted LED 10 Watt 4ft long batten, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver with industrial grade heavy duty driver having THD<10% suitable pre wired and testing including all connections complete all as specified and as directed by Engineer in charge. Make: Havells Cat Part No. ENDURALINEARNEOBS10WLED865SPCWH or equivalent in Philips/Bajaj/Wipro/Crompton/Luker as approved by GE
Supply and fix in replacdment Surface and wall mounted LED 20 Watt 4ft long batten, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver with industrial grade heavy duty driver having THD<10% suitable pre wired and testing including all connections complete all as specified and as directed by Engineer in charge. Make: Havells Cat Part No. ENDURALINEARNEOBS20WLED865SPCWH or equivalent in Philips/Bajaj/Wipro/Crompton/Luker as approved by GE
Supply and fix in replacement, LED 10W CDL ball lamp suitable to hold in B22 base camp with system lumen output 850, complete all as specified and directed. Make: Havells Cat Part No. LED Adore 10W B22 cdl or equivalent in Philips/Bajaj/Wipro/Crompton/Luker as approved by GE
Supply and fix in replacement LED ceiling light, 36 W, Fixture size: (LxWxH) in (595x595x11) mm suitable for 2ft x 2ft grid false cieling, having color temparature 4000K with extruded aluminium heat sink housing complete with all accessories and internally pre-wired including LED drivers, complete all as directed Make: Havells Cat Part No. STRATO2X2PLR36WLED840MOD or equivalent in Philips/Bajaj/Wipro/Crompton/Luker as approved by GE
Supply and fix in repair street light brackets made out of 40mm bore GI tubing, light grade, 1.5 Mtrs long, bent to required shape, including necessary bending, welding, etc fixed with 2Nos. clamps made out of 32x5mm GI strip including necessary drilling holes, screws, nuts, bolts, etc... complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of unserviceable building security lights LED fitting 45 Watt of pressure die cast aluminium housing with seperate driver compartment and IP 66 protection and impact resistance of IK07, complete with all accessories including LED drivers and internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size, all as specified and directed by Engineer-in-Charge. Make: Havells Cat Part No. ENDURAPEARLNEOSL45WLED757PASYTOPC or equivalent in Philips/Bajaj/Wipro/Crompton/Luker as approved by GE
Supply and fix in replacement of unserviceable building security lights LED fitting 25 Watt of pressure die cast aluminium housing with seperate driver compartment and IP 66 protection and impact resistance of IK07, complete with all accessories including LED drivers and internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size, all as specified and directed by Engineer-in-Charge. Make: Havells Cat Part No. ENDURAPEARLSL25WLED757SASYTOPCMP or equivalent in Philips/Bajaj/Wipro/Crompton/Osram/Luker as approved by GE
Supply and fix in replacement sheet metal enclosure with two pin socket , chain plug cover with MCB SPN of 10 Amp capacity with alignment 10 KA ‘B’ series complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB SP 5 to 30 Amp, 240 V, B Series, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB SPN 32 Amp 240 V , 50 Hz, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB SPN 20 Amp 240 V , 50 Hz, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB TPN 40 Amp 415 V , 50 Hz, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB TPN 63 Amp 415 V , 50 Hz, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB DB TPN 4 Way 415 V , 50 Hz, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB DB SPN 4 Way 240 V , 50 Hz with 200A rated copper busbar complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB DB SPN 8 Way 240 V , 50 Hz, with 200A rated copper busbar complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement MCB DB SPN 12 Way 240 V , 50 Hz, with 200A rated copper busbar complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of vertical MCB DB TPN 6 Way 440V , 50 Hz with 200A rated copper busbar for three phase power supply with necessary color coding including MCCB 4P, 63A, 415V,25KA mounted at bottom side of MCB DB for terminating incoming XLPE Cable termination complete all as specified and directed by Engineer-in-Charge.
Taking down existing unserviciable ceiling fan /exhaust fan of any type and rewinding the same with fine enamelled copper conductor and refixing band and testing complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of condenser of 2.5 MFD complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of unserviceable ball bearing suitable for existing size for ceiling fan 1200mm sweep, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of unserviceable ball bearing suitable for existing size for exhaust fan 300 mm sweep, complete all as specified and directed by Engineer-in-Charge.
Taking down the unserviceable Electric geyser 25 Ltrs capacity and transporting to work shop for repairs/replacement of unserverviceable items such as heating coil, Thermo stat , copper container ,indicating lamp to match the existing geyser complete all as specified and directed by Engineer-in- Charge. Note: Repalcement of unserviceable items will be measured and paid under respective items as Supply only
Supply only Heating coil suitable for Electric geyser 25 Ltrs complete all as specified and directed by Engineer-in- Charge.
Supply only thermostat suitable for Electric geyser 25 Ltrs complete all as specified and directed by Engineer-in- Charge.
Supply only inner container made of copper suitable for Electric geyser 25 Ltrs complete all as specified and directed by Engineer-in- Charge.
COOLING APPLIANCES Maintenance and servicing of split type AC including cleaning filter, washing with soap solution after removing from site and refixing complete all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of hermitically sealed outdoor compressor unit including brazing/welding and leakage testing after completon of job for 1.5 Ton Split type AC all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of hermitically sealed outdoor compressor unit including brazing/welding and leakage testing after completon of job for 2 Ton Split type AC all as specified and as directed by Engineer-in- Charge.
Material and labour for gas charging including commissioning and testing complete of split AC 1.5/2 TR, any type and size all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of condensing coil copper including soldering with existing system for 1.5 Ton AC complete all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of condensing coil copper including soldering with existing system for 2 Ton AC complete all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of condenser fan motor for 1.5 Ton AC all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of condenser fan motor for 2.0 Ton AC all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of outdoor unit Capacitor of capacity 40 + 5 MFD all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of outdoor Capacitor of capacity 60 + 5 MFD all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of indoor unit Capacitor of capacity 2.5 + 5 MFD all as specified and as directed by Engineer-in- Charge.
Disconnection and removing the unserviceable PCB from the indoor unit of Split type Air conditioner and supply and fix New PCB unit suitable for the existing Makes of Air conditioners all as specified and as directed by Engineer-in- Charge.
Disconnection and removing the unserviceable indoor fan motor from the indoor unit of 1.5 TR Split type Air conditioner and supply and fix New indoor fan motor unit suitable for the existing Makes of Air conditioners all as specified and as directed by Engineer-in- Charge.
Disconnection and removing the unserviceable indoor fan blower unit from the indoor unit of 1.5 TR Split type Air conditioner and supply and fix new indoor fan blower unit suitable for the existing Air conditioners at site all as specified and as directed by Engineer-in- Charge.
Disconnection and removing the unserviceable indoor fan blower unit from the indoor unit of 2 TR Split type Air conditioner and supply and fix new indoor fan blower unit suitable for the existing Air conditioners at site all as specified and as directed by Engineer-in- Charge.
Supply and fix in replacement, copper pipe of size 1/2" dia with necessary fixing arrangements for such as welding ,brazing,nut,bolts and testing complete all as specified and as directed by Engineer-in- Charge.
Supply and fix in replacement of copper pipe of size 1/4" dia with necessary fixing arrangements for such as welding ,brazing,nut,bolts and testing complete all as specified and as directed by Engineer-in- Charge.
Material and labour for gas charging including commissioning and testing complete of 40 /80 Ltrs capacity water cooler all as specified and as directed by Engineer-in- Charge.
Material and labour in replacement of compressor unit for 40/80 Ltrs capacity including comissioning and testing complete all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of thermostat for water cooler of existing capacity and make complete all as specified and as directed by Engineer-in- Charge.
Supply and fixing in replacement of capacitor of 10 MFD for water cooler complete all as specified and as directed by Engineer-in- Charge.
Disconnection and removing the unserviceable voltage stabilizer and replace the unserviceable items such as PCB and refixing back in its original position including testing, as per existing Makes of capacity 4.0 KVA/5.0 KVA complete all as specified and directed by Engineer-in-Charge. Note: PCB shall be measured and paid seperately under respective items.
Supply and fix in repairs PCB/control board suitable for 4.0 KVA Voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repairs PCB/control board suitable for 5.0 KVA Voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
KRA Engineering and Construction
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .