| 1 | L1₹2.6 CrAdmitted-Finance | ₹2.6 Cr | L1 | Admitted-Finance |
| Sl No | Description | Qty | Unit | DOUSE FIRE SYSTEMS PRIVATE LIMITED L1 |
|---|---|---|---|---|
| 1.00 | PART-A : FIREFIGHTING SYSTEM | 1 | no | 89,11,240 ₹89,11,240 Lowest |
| 2.00 | PART-B: FIRE ALARM AND PUBLIC ADDRESS SYSTEM | 1 | no | 39,67,990 ₹39,67,990 Lowest |
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
17 Oct 2023, 5:00 pmClosed
Cheif Engineer (ESG)
DCSEM, 3rd Floor, V.S. Bhavan, Anushaktiangar, Mumbai - 400094.
Supply, installation, testing and commissioning of firefighting systems along with fire alarm and public address system for VSB Parking at Anushaktinagar, Mumbai.
2023_DCSEM_773586_1
DCSEM/CQD/QSC/ VSB-CP-FF/NIT/20/23-24, 26.09.2023
Open Tender
Job Works
Works
120 days
V.S. Bhavan, Anushaktinagar, Mumbai
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹2.6 L
20 Dec 2023
27 Sept 2023
19 Oct 2023
27 Sept 2023
17 Oct 2023
27 Sept 2023
27 Sept 2023 - 10 Oct 2023
Amount
PART-A : FIREFIGHTING SYSTEM
PART-B: FIRE ALARM AND PUBLIC ADDRESS SYSTEM
Description of Work / Item(s)
Amount
Part-A: Firefighting system G.I. Pipes: Supply, installation, testing and commissioning of Heavy Duty, "C" Class GI pipes of following sizes confirming to IS-1239 along with all necessary fittings, flanges, jointing (screwed / welded / flanged etc.) and required supports with two coats of paint as per color code of the piping systems over two coats of red oxide primer, including all hardware, complete in all respects as per specifications and as instructed by Engineer-In-Charge. Note: 1) The pipe line shall be measured along the centre line. 2) Any Core cut if required for laying the pipes shall be included in above cost, no extra payment will be made for the same. 3) The GI pipes shall be connected with existing firefighting lines by cutting the existing pipes and to be extended to two upper floors and no extra payment will be made for the same. 4) The MS supports shall be measured separetly and paid under relevent item of this SOQ.
150 mm dia.
100 mm dia.
80 mm dia.
65 mm dia
50 mm dia
40 mm dia
32 mm dia
25 mm dia
M.S SEAMLESS PIPES: Supply, Installation, Testing and Commisioning of MS seamless pipe of following Sizes and conforming to ASTM 106 A, Grade B with all fittings, flanges, jointing, supports (Support for piping shall be paid separately) and painting with two coats of anti corrosion paints over two coats of red oxide primer (for laying above ground) and including providing wrapping with 4 mm thick PYPKOTE(corrision protection tape) with adhesive / coats as required(for laying underground) including all the hardware, complete in all respects of work, all as per drawings, specifications and as instructed by Engineer-In-Charge. Note: 1) Making of flanged joints including providing fasteners, blind flanges and gaskets shall be measured under pipelength of this item and no extra payment shall be made. 2) Pipe support shall be paid separately under relevent item of this BOQ.
150 mm dia. (Below Ground)
150 mm dia. (Above Ground)
100 mm dia. (Below Ground)
100 mm dia. (Above Ground)
CI Gate Valves: Supply, installation, testing and commissioning of double flanged CI/Cast Steel Gate Valve of required sizes of ratings PN 1.6 with rising stem conforming to IS-14846 with all necessary fittings like flanges, neoprene gaskets, nut bolts, hardware, flanges, neoprene gaskets, nut bolts, hardware, flange joint etc. as shown in the drawings and as per specifications and as instructed by EIC.
150 mm dia.
100 mm dia.
80 mm dia.
Gun Metal Gate Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to Class 2 of IS : 778 with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge.
50 mm dia.
HYDRANT LANDING VALVE: Supply, Installation, testing & commisioning of Single Outlet Hydrant landing valve of oblique Morris pattern Stainless Steel (SS-304) landing valve with C.I./ S.S. hand wheel, detachable stainless steel female coupling, conforming to IS-5290/BS-5041 having instantaneous coupling, having 63 mm dia. blank cap and chain conforming to IS-901 to suit the hosepipes, including nuts, bolts, washers, gaskets, with necessary fittings like tees etc. testing the unit, painting the Hydrant landing valve with 2 coats of signal red paint over a coat of Zinc reached primer, all as per specifications and as directed by E-I-C.
Hose Reel With Drum: Providing & fixing rubber hose reel of 20 mm diameter x 37 m along with swinging drum along with high pressure braided rubber hose conforming to IS 884 including 8 mm diameter SS cut off nozzle on one end, wall mounting type, necessary brackets suitable for wall mounting, fixing on wet riser cum downcomer including connecting the other end to the wet riser cum downcomer by providing necessary connecting nipple/coupling, nuts, bolts etc. and providing & fixing 20 mm dia G.M. peet valve of approved make all complete including painting (the drum and brackets shall be painted with two coats of signal red enamel paint from outside and white enamel paint from inside) & as shown and as instructed by Engineer-In-Charge.
Hose Cabinet: Supply, installation & commissioning of 1.6 mm thick MS sheet metal hose cabinet of size 750x650x250 mm for accomodating 02 nos. of hose pipes (measured & paid seperately under relevent SOQ item) and SS-304 branch pipe with nozzle or hosy branch pipe with nozzle. The box shall have front glass door lock with angle iron frame. The hose pipe box shall be fixed with Hilti make Anchor Fastner on the wall or nut bolts (in case of stand in open space) as shown in the drawing and as directed by EIC. The MS box shall be painted with two coats of signal red enamel paint from outside and white enamel paint from inside. The scope also includes supplying of gun metal / stainless steel branch pipe of 63 mm dia. fitted with detachable hexagonal nozzle of 19 mm dia. conforming to IS : 903 or universal pattern as per IS : 2871. The branch pipe with detachable nozzle shall be placed in the hose cabinet complete in all respect as instructed by Engineer-In-Charge.
Hose Pipe(For Hydrants, Landing Valve): Supply and installation of Unlined Flax Canvas (hose pipe) for fire fighting conforming to RRL fire hose type A or Synthetic Fibre Woven-Jacket (SFWJ) Elastomeric fire hose type B conforming to IS:636 all with ISI marks as required and of approved make and of 63 mm dia & 15 mtrs length, fitted with male and female SS coupling confirming to IS:903, ISI marks with guaranteed bursting pressure of 35.7 kg/sq.cm and complete as per the technical specifications and as instructed by Engineer-In-Charge. Each set shall comprise of 2 hose pipes.
Pressure Guages: Supply, installation testing and commisioning of pressure gauges of SS material with dial not less than 150 mm dia of appropriate range and complete in all respects with shut off gauge, cocks , all fittings etc, duly calibrated before installation in MKS and FPS units and duly tested after installation as per drawing and as instructed by Engineer-In-Charge.
Air Release Valve: Providing and fixing 20/25 mm dia. (PN - 1.6, Type-S1, Flanged, ISI marked) air release valve conforming to IS - 14845 : 2000 with Double Flange isolating valve (pressure rating PN 1.6) including making necessary flanged joints and providing all fitting materials nuts, bolts etc. and providing T on the pipeline for its installation at site all as per technical specification, drawings and as instructed by Engineer-In-Charge.
Orifice Plate: Design, supply and fixing stainless steel orifice plate of not less than 6 mm thick having suitable bore for reducing the pressure at the fire hydrant outlet as per fire brigade requirement and to restrict the operating pressure within 3.5 kg/sq.cm. at the fire hydrant outlet. The orifice plate shall be fixed in position & it shall be fitted between the flanges. The orifice plates shall have test certificate and calibrated to give the required pressure, complete all as per specification, drawings & as directed by E.I.C.
M.S. Supports / Structure: Supply, cutting, fabrication, welding, erecting & fixing in position of M.S. support/structure (angle, channel, beam, plate, chequered plate etc.) for steps and other purpose (not applicable for items for which supports are already included in the item) including painting with two coats of synthetic enamel paint of approved make & shade over a coat of approved steel primer all as instructed by Engineer-In-Charge. Material shall conform to IS-2062.
PCC Pedestals: Providing PCC pedestals /thrust /anchor block of required sizes for underground pipes, fire hose box etc. and specials with cement concrete 1:2:4 at required intervals including (frame work) shuttering, curing, finishing etc. complete in all respect as as per standard specifications and as instructed by Engineer-In-Charge.
Ordinary soil
Soft Rock
Hard Rock
DISPOSING OF SURPLUS MATERIALS: Disposing of the surplus excavated materials by mechanical transport to the lead upto 2 km over the initial lead of 150 m including loading, unloading, spreading, levelling etc., complete all as per specifications and as instructed by Engineer-In-Charge. Note: 1) Voids 20% for soils and 50% for Soft Rock/Hard Rock shall be deducted from stack/truck measurements to arrive at the net qty for payment in case if direct measurement is not possible. 2) Approval for disposal of surplus excavated materials from concerned authorities is responsibility of contractor and Quoted rate shall be inclusive of all charges if any from the statuatory authorities.
ROAD CUTTING & RE-SURFACING: Cutting the existing asphalt road and demolishing WBM or BBM including rubble soling if any for providing services and making good the same after the work is satisfactorily completed, including relaying of soling doing water bound macadam, bituminous bound macadam road providing and laying 50 mm thick asphaltic layer etc, complete as directed by EIC.
Sprinklers: Supply, installation, testing & commissioning of 15 mm dia recessed sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, with rosette plate [Pendent type Sprinkler (K-80), FM & UL approved] with all assembly complete in all respects as directed by EIC.
Description of Work / Item(s)
Amount
Part-B: Firealarm and Public Address System Fire Alarm system (FAS) Design,supply,installation,testing & commissioning of analogue addressable type fire alarm system as per relevant Indian Standard specifications and conforming with relevant specifications of fire authorities of local Municipal Corporation, and as directed by E-I-C and consisting of the following: Note: 1) The work shall be carried out by licensed agency complying local State Fire safety statutes. 2) Scope includes submission of factory test report of detectors,break glass and hooters and main panel and final inspection at site. 3)Make of all the components of FAS shall be same. 4) The Panel shall be suitable for networking using open technologies such as TCP/IP, Rs 485,modbus.
Multisensor Detectors: Supply ,installation,testing & commissioning of Intelligent addressable smoke detector unit working on multisensor detection technology with optical , heat detector sensor with inbuilt fault isolator complete with base as required & as per instructions of EIC.
Rate of Rise Heat Detectors (Thermal Detectors): Supply ,installation,testing & commissioning of Analog Addressable Heat Detectors with solid state design with sensing element combination of fixed type and rate of riseof temperature indicating LED, mounting base etc. as per detailed Specification.
Manual Call Point: Supply ,installation,testing & commissioning of dust and vermin proof Addressable Manual Call Point, break glass/pull station (square type/round type suitable for wall mounting surface/concealed) having painted/ engraved/ embossed as “IN CASE OF FIRE,BREAK GLASS” on it, small hammer fixed with chain (incase of break glass), painting and other accessories as required. complete as required & as per instructions of EIC.
Loop powered Sounder with Strobe Light: Supply ,installation,testing & commissioning of Wall Mounting Alarm Intelligent loop powered sounder complete as per specifications and as required & as per instructions of EIC.
Response Indicator: Supply ,installation,testing & commissioning of Response indicator consisting of aluminium casting enclosure & steady glowing 2 nos.red indicator (LED) and cover plate shall be screen printed as "FIRE". The unit shall be suitable for connecting in parallel to the multisensor & wall mounting type with provision of 25mm dia conduit entries ,painting & other materials as complete as per specifications & of E-I-C.
Fire Alarm Panel: Design,supply,installation,testing & commissioning of Analogue addressable microprocessor controlled Fire Alarm Control Panels, capable of being IP networked to the central monitoring System connecting through optical Fiber cable network to monitor and integrate above quantity of accessories like detectors, MCP's/loop power sounder/control modules, Fault Isolation Modules, Loop powered hooters, response indicators, fire/fault indicators,audio-visual signals, central processing units, complete with LED visual indicators, alpha-numeric display and audible alarm both for fire & fault, mains ON indication,test & reset provisions. Each loop should provided with minimum 125 detectors /devices. The panel shall include integral SMF lead acid batteries with sealed cells (max 24V) with appropriate AH capacity, as per IS requirement with integral battery charger, wire way box , if required ,front openable lockable cover with front glass etc. complete as required and as per specification & instructions of EIC. Note: If charger & battery-capacities provided in redymade panel are not meeting operation requirement as per IS2189 then charger & batteries shall be provided separately including wiring at no extra cost.
4 Loop panel
Supply ,installation,testing & commissioning of 12 relay transponder with surface mounting housing box and interconnection
Supply ,installation,testing & commissioning of Passive Repeater Panel suitable for wall mounting complete with visual indicators, as per specifications & instructions of EIC.
Wiring for Fire Alarm System: Wiring with 2 nos. 1.5 sqmm FRLS-PVC insulated Shielded twisted pair copper cable/wires in 25mm dia concealed/surface MS/PVC conduit (HMS variety)including cost of cutting and filling chases for concealed conduit/ cost of saddles etc. for surface conduit as required and including the cost of crimped termination’s as required, complete as per instructions of E-I-C.
Emergency Evacuation/Public Address System (PAS): Supply,installation,testing & commissioning of public Address system as per relevant standards, as directed by E-I-C and consisting of the following: Note: 1) The work shall be carried out by licensed agency complying local State Fire safety statutes. 2)Scope includes submission of factory test report of controller,amplifire, speakers call station etc. 3)Scope includes interconnection of various PAScomponents in 19" cabinet/rack 4)Make of all the components of PAS shall be same. 5) The sysem shall be suitable for networking using open technologies.
Supply,installation,testing & commissioning of 8 zone digital System Controller complete in 19'' Rack mountable Dual tone, integration with existing Fire alarm system,control for Speech & Music, tone generator & Speech Processor with relays for activating tone & pre-recorded fire alarm messages etc as specified in the Tender Specifications Note: scope also includes interconnection of above FA panel with PA controller including testing & commissioning of interface of integrated FA-PA system
Speakers:
Digital Power Amplifier: Supply ,installation,testing & commissioning of 19''rack mounted class-D Power Amplifier with on board DSP powerfor local signal processing, Switched mode power supply,Local audio inputs, Mains and battery operation and supervision, complete with following types and as per instructions of EIC.The amplifier shall be mounted in existing LAN rack.
2x250 W Power amplifier
Call Station: Basic Call Station with Power 'ON' indication, status/fault indications, priority level of destination is higher than that of the pending announcement indication, Supervision of microphone capsule and with built in On board DSP powerfor local audio processing. The call station basic can make manual or prerecorded announcements to anypre-assigned zones. The call station shall be provided with18" gooseneck type microphone. The call station shall be fully supervised and must supports failsafe operation. Even if the network controller fails, the call station shall be able to put through emergency calls and as specified in the tender specifications and as per instructions of EIC.
PA system cabling: Supply ,installation,testing & commissioning of 2 core twin twisted 48/0.2 ATC, multi stranded, overall PVC insulated and armoured cable (Blue colour) in existing PVC mini trunking, proper dressing of cables and including the cost of termination’s as required, complete as per instructions of E-I-C. The cost of mounting base boxes & the cost of providing cable glands etc shall be included in the scope of work.
Supply & installation of DVD player with USB support , in-built compressor & limiter as per instruction of EIC.
Supply, installation, testing & commissioning of 3 kVA double conversion (online) rack mountable UPS with single phase input and single phase output configuration with min. 15 minutes battery backup at 100% load using inbuilt sealed maintenance free batteries, flexible chord with plug in existing network rack as per instructions of EIC.
Supply, installation, testing & commissioning of double section 19" wall mounted pivoting type, 21U height & 600 mm depth rack having safety glass door & with standard accessories, including power supply panel, fans, cable manager, full cable entry plate with required & as per instructions of EIC.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.90 MB
TechdatasheetVSBCPFF.xls
Tender Documents • 0.08 MB
Drawing2697.pdf
Tender Documents • 0.17 MB
Drawing2698.pdf
Tender Documents • 0.16 MB
Drawing2699.pdf
Tender Documents • 0.14 MB
DetailedNITVSBCPFF.pdf
Tender Documents • 0.88 MB
TechnicalBidVSBCPFF.pdf
Tender Documents • 1.55 MB
BOQ_813207.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .