Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Not Qualified - Work Experience certificate not appropriate |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Others-Relevant / appropriate document and appropriate EMD amount not enclosed as per NIT of the above work in submitted envelop. |
Tender Value
₹29.4 L
EMD Value
₹58,879
Closing Date
8 Apr 2022, 6:00 pmClosed
DIRECTOR
CSIR-CIMAP, Lucknow
Replacement of existing 22.5 TR old non energy efficient AC plant with energy smart VRF/VRV AC plant at CSIR-CIMAP, Lucknow
2022_CSIR_111018_1
68_48/839/2022-MP(Works)
Open Tender
Job Works
Item Rate
90 days
CSIR-CIMAP Lucknow
OEMs / their authorized dealers /
authorized distributers /authorized assemblers of VRV/VRF AC plant
2 documents required · 2 mandatory
₹1,120
DIRECTOR, CSIR-CIMAP
₹58,879
1 Jun 2022
24 Mar 2022
11 Apr 2022
24 Mar 2022
8 Apr 2022
24 Mar 2022
24 Mar 2022 - 8 Apr 2022
Amount
Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units with stand suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5
Capacity 14 HP
Supply, installation, testing and commissioning of floor mounted packaged type Indoor units with washable synthetic media pre-filter, dynamically balanced blower designed for silent operation, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports as per site requirements, suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System.
Capacity 10-11 TR (Packaged IDUs + Controllers) Complete
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required.
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
SITC of GSS Rectangular ducting (Class VIII Galvanised) with all component like GI sheets , duct support MS angles, nut bolts etc as per site requirements
22 Gauge
24 Gauge
SITC of Duct Acoustic lining with 25 mm thick fiberglass covered with RP Tissue paper & perforated Alluminium sheet
SITC of Duct Insulation with XLP 13mm thermal insulation
SITC of Extruded Aluminium Powder coated supply/ return air Spot grilles
SITC of MS Volume Control Damper
SITC of Duct Damper
SITC of Canvass connection (1 no per Unit)
SITC of sand,Cement Plaster with Thermocol , wire mesh for exposed Duct open in Roof
SITC of Slotted angle Cable tray for laying of pipes and cables for exposed piping only(Width 200mm / Hight of Tray wall 25mm)
Flexible Pipe for condensate Drain from indoor unit to the nearest drain point as per site suitability.(40 mm hard PVC)
Annual Maintenance contract (Comprehensive) of Variable Refrigerant Flow/Variable Refrigerant Volume air cooled units for 03 years after the date of defect liability period of one year from the date of commissioning. The work Includes Quarterly visit, unlimited complains attending as and when required, Variable Refrigerant Flow/Variable Refrigerant Volume air cooled units in proper functioning to maintain the cooling requirements. Nothing will be paid extra on any account during the AMC period
1 st year CAMC
2 nd year CAMC
3 rd year CAMC
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Buy back and dismantling of old existing air conditioners water cooled voltas make plant 3X7.5 TR rating installed in institute premises. The existing air conditioners water cooled voltas make plant is in operational/functional condition. The firm has to dismantle, transport, and take back the existing Air conditioners from the installation place. A detailed item list is prepared and submitted by the firm to issue gate pass to take the materials outside the institute. Format will be given by concerned Engineer In charge towards issue of gate pass. Make good if any things occurs during dismantling (personal safety gears, machinery, lifts, special tools etc.). Nothing will be paid extra on any account. The firm may physically inspect and check the existing old water cooled AC plant before quoting the price. Buy Back is mandatory.
UNITY ENGINEERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .