General Manager (Engineering)
Bridge and Roof Co. (India) Ltd Kankaria Centre (4TH/5th Floor) 2/1 Russel Street Kolkata 700 071
SUPPLY, INSTALLATION, TESTING and COMMISSIONING OF FIRE DETECTION and FIRE ALARM SYSTEM IN CONNECTION WITH THE CONSTRUCTION OF MULTI UTILITY COMPLEX and PG STUDENTS HOSTEL AT SARDAR VALLAVBHAI PATEL POST GRADUATE INSTITUTE OF PEDIATRIC (SVPPGIP)
2022_BandR_671300_1
BandR/HO/51155/TD/FIRE DETECTION and FIRE ALARM 01
Open Tender
Miscellaneous Works
Works
90 days
SISHUBHAWAN, CUTTACK ODISHA
As Per Tender Document
17 documents required · 17 mandatory
₹1,180
Yes
Bridge and Roof Co.India Ltd
Exempted
2 Jul 2022
1 Feb 2022
1 Mar 2022
1 Feb 2022
28 Feb 2022
1 Feb 2022
Amount
FIRE DETECTION & ALARM SYSTEM
Supply, installation, testing & commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event plus 1000 alarm log history events, QWERTY keypad for programming. The panel should be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of 250 detector & devices in any combination. The panel shall work in degrade mode in case of CPU failure. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. Fire Alarm Panel shall have MODBUS / BACnet connectivity to integrate with BMS system. Panel shall have Designed to meet EN54 / UL864, 10th Edition. Make - Notifier, Honewell , Bosch, Siemens, Edwards, Schneider
8 loop panel expendable upto 10 loop
Supply, installation, testing & commissioning of Active Networkable Repeater Panel complete with minimum suitable feather touch/ touch screen/keypad display with 600 character LCD to indicate the status of system and location of incident etc., back box and with control function. The Repeater panel shall be enclosed in a suitable locking type metallic cabinet for protection. Panel shall have Designed to meet EN54 / UL864, 10th Edition. Make - Notifier, Honewell, Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Graphics User Interface for Monitoring Fire Alarm System with the following minimum features: The software shall be capable of monitoring 2500 points & having multple client viewing facility. Make - Notifier, Honewell , Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 4.0% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. Additionally, the detector may have in-built isolator or isolator base for fault tolerance. The detector shall have single/ twin/ bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary switches/ electronic addressing. EN54 / UL268, 7th Edition approved. Make - Notifier, Honewell, Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min. Additionally, the detector may have in-built isolator or isolator base for fault tolerance. The detector shall have single/ twin/ bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary switches/ electronic addressing. EN54 / UL268, 7th Edition approved. Make - Notifier, Honewell, Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Beam Detector with addressable control module, if required. The beam detector shall be used for High Ceiling application with a detection range upto 100 mtrs having both infrared transmitter & CMOS imager. Make - Notifier, Bosch, Siemens, Edwards, Honewell, Schneider
Supply, installation, testing & commissioning of Addressable Manual Call Point (Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Additionally, the device may have in-built isolator for fault tolerance. EN54 / UL268, 7th Edition approved. Make - Notifier, Honewell, Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Addressable Control Module for Sounder cum Strobes. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Additionally, the device may have in-built isolator for fault tolerance. EN54 / UL268, 7th Edition approved. Make - Notifier, Honewell , Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs. The relay module shall provide contact rated at 24v DC, 1A/ 2A. The device shall have in-built isolator for fault tolerance. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Additionally, the device may have in-built isolator for fault tolerance. EN54 / UL268, 7th Edition approved. Make - Notifier, Honewell , Bosch, Siemens,Edwards, Schneider
Supply, installation, testing & commissioning of Addressable Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Additionally, the device may have in-built isolator for fault tolerance. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. EN54 / UL268, 7th Edition approved. Make - Notifier, Honewell, Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Make - Notifier, Honewell, Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and 115cd flashintg at 1 Hz for visual indication. Additionally, the device may have loop powered feature with in-built isolator for fault tolerance. EN54 / UL268, 7th Edition approved. Make - Notifier, Honewell, Bosch, Siemens, Edwards, Schneider
Supply, installation, testing & commissioning of Response indicator for True ceiling detector. Make - Ravel, Agni
Supply, installation, testing & commissioning of GSM based Autodialer with support for 2 SIM slots.
Supply, installation, testing & commissioning of Workstation for GUI : Intel i5/ Intel i7, 1 TB HDD, 8GB Memory, MS Windows 10 License, 21" Monitor, complete with A4 color printer, wired keyboard and mouse. Furniture for mounting and using the desktop should also be considered. Make- DELL, HP, HCL, WIPRO , IBM, Lenovo
Conventional Fire Alarm System
Supply, installation, testing & commissioning of 4 Zone Conventional Fire Alarm Panel Make- AGNI, SYSTEM SENSOR, RAVEL
Supply, installation, testing & commissioning of Hooter. Make- AGNI, SYSTEM SENSOR, RAVEL
Supply, installation, testing & commissioning of Conventional Manual Call Point Make- AGNI, SYSTEM SENSOR, RAVEL
Supply, installation, testing & commissioning of of GSM based Auto dialer with support for 2 SIM slots.
CABLES
Supply and laying of 2 C X 1.5 Sq mm armoured FRLS Copper cable with necessary arrangement for individual termination of armoured cable with MS/ PVC box and compression gland at device end as per site requirement. Make- UNIVERSAL, POLYCAB, FINOLEX , KEI , HAVELLS, RR KABEL
"NOTE:- THE ABOVE RATE SHALL BE INCLUSIVE OF ALL TAXES & DUTIES, ROYALTIES, CESS, ENVIORMENTAL & POLLUTION, FITNESS & SAFETY CLEARANCE CHARGES (IF ANY), OR ANY OTHER INCIDENTAL CHARGES ETC BUT EXCLUDING GST."
Security Engineers Pvt. Ltd.
Acharya Electrical
West Bengal Electronics Industry Development Corporation Ltd
BANFIRE
Fire Stop Sales And Services
GLYPTIC
VICOM SECURITY PVT LTD
Sacaya Technologies Pvt Ltd
UMA FIRE SERVICES PVT. LTD.
SAFE GUARD (INDIA)
dd electronics euip pvt ltd
Globe Solutions
stage.html
html • 0.09 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .