Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.0 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹26.2 L+₹70,230 (2.75%)Rejected-Finance | L2 | Rejected-Finance Not Being Lowest | |
| 3 | L3₹28.5 L+₹2.9 L (11.5%)Rejected-Finance 137 3 STREET NO 4 RAJINDER NAGAR DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | L3 | Rejected-Finance Not Being Lowest | |
| 4 | L4₹33.3 L+₹7.7 L (30.2%)Rejected-Finance PLOT NO 10 9 OM VIHAR PHASE 1 A UTTAM NAGAR NEW DELHI 110059 | WEST DELHI | DELHI | 110059 | L4 | Rejected-Finance Not Being Lowest | |
| 5 | L5₹34.0 L+₹8.5 L (33.2%)Rejected-Finance | L5 | Rejected-Finance Not Being Lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
27 Dec 2022, 6:00 pmClosed
GE (Central) Delhi Cantt-10
GE (Central) Delhi Cantt-10
REPAIR/ REPLACEMENT OF UNSV PARTS OF LT PANEL INCLUDING EARTHING AND SUB MAIN WIRING DB INCLUDING MANNING AND OPERATION OF SEWAGE INSTALLATION AND REPAIR TO PUMP AND MISC WORK AT ARJAN VIHAR NPC DS PRATAP CHOWK OFFRS MD ACCN DK-I AND DK-II OFFRS ACCN
2022_MES_566509_1
GE/C-68/2022-23
Open Tender
Civil Works
Item Rate
335 days
GE (Central) Delhi Cantt-10
As per NIT
9 documents required · 9 mandatory
₹500
Yes
GE (Central) Delhi Cantt-10
₹80,000
Yes
9 Jan 2023
1 Dec 2022
29 Dec 2022
1 Dec 2022
27 Dec 2022
15 Dec 2022
1 Dec 2022 - 15 Dec 2022
Amount
S/F in replacement Sluice valve , CI, 100 mm dia ,PN - 1.6 type, complete with spindle ,etc. flanged type, ISI marked complete all as specified and directed.
S/F in replacement non return valve CI, 100mm dia PN-1 type flanged complete set ISI marked complete all as specified and directed.
S/F in replacement foot valve CI 100mm dia complete with flanged type ISI marked complete all as specified and directed.
S&F in replacement Suction pipe GI medium grade 100mm dia ISI marked complete all as specified and directed.
S&F in replacement delivery pipe CI medium grade 100mm dia ISI marked complete all as specified and directed.
S&F in replacement GI/CI bend heavy duty 100mm dia ISI marked complete all as specified and directed.
S/F in replacement Tyre/rubber coupling complete set all as specified and directed by engineer in charge.
S& F in replacement ball bearing suitable size complete all as specified and directed by Engineer in Charge.
S& F in replacement Voltmeter digital type suitable size all as specified and directed by Engineer in Charge.
S& F Ammeter meter digital type suitable size all as specified and directed by Engineer in Charge.
M & L for dismantling centrifugal pump coupled with electric motor capacity 10 to 15 HP 3 phase 415 V of overhauling the pumpsets including cleaning with kerosene/petrol for removing the scales and replacement of necessary parts of case ring, latern ring, shaft sleeve, CI gland covers with MS studs, ball bearings, coupling key, rubber bush nut & bolts, impeller key, lock washer, gasket, and greasing, re-assembling same in position, testing and commissioning the following capacity pump sets complete all as specified and directed by the Engr-in-Charge.
Taking down existing electric motor capacity 10 to 15 HP, 3 Phase 415V, 50 cycles, AC from foundation/coupling opening the motor cutting and the burnt windings including bearings necessary spares parts, cleaning the sator and water with cleaning agent, rewinding the motor with appropriate gauge of super enamelled copper wire of approved make, insulating winding with same class of insulation, varnishing backing up indication supply and provision of base foundation and fixing with bolts, nuts and re-installation of motor satisfactory perfomance of Engineer-in-charge.
Desludging of existinng sewage sump by mechanical means or manually and removing the sludge in closed container outside MOD land including providing necessary safety equipments to the worksmen deployed all as specified and directed by Engineer in charge.
M&L 50mm thick PCC 1:2:4 type B-2 using 40mm gradded stone aggregate as in floors finished even and smooth including demolation.complete all as specified and directed by Engr -In- charge.
M&L machine pressed precast concrete chemical treated interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness, M-35 Grade including 25 mm thick sand cusion complete all as specified and directed by Engr -In- charge.
M & L for nonskid ceramic coloured tiles in floorl surface 300x300x7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match laid over and included 15 mm thick cement mortar secrewed bed in cm (1:6) including roughing of excluding floor, complete all as specified and directed by Engr -In- charge.
Takiking down cement plaster in any thickenss from brick or stone tc including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed.
M&L for ready mix plaster of 15mm thick on brick or conc surfaces incl necessary cement slurry with bulk density 1.40 to 1.70kg , water ratio 17 to 19% by weight & compressive strength as per IS 4031 part 6 applied as per manufacture instruction.
M&L for applying two coat of white wash on wall on decorated or undecorated surface complete all as specified.
M& L second class HW clean swan unframed work complete all as specified and directed by Engr -in-Charge.
Supply and Fix in repair 45W High efficient LED Street light fitting with pressure die cast LM6 Aluminum housing and has lenses specially designed for Street Lighting with polycarbonate cover. System level efficacy of the Luminarie is 100lm/W with a life class of 50,000 burning hours at L70. The color temperature is around 6500 K with a color rendering index of 70. The luminaire is IP:66 protected with IK05 impact resistance. It has an electronic driver complaint to IEC safety standards with a power factor>.0.9, voltage variation range 120-270V, THD<20%, High and low protection along with a surge protection of 4 KV including provision of 40mm dia GI light grade pipe1.5 meter length bend to shape and necessary clamps etc for fixing the light fittings on pole fixed complete as specified and directed.
Taking down carefully copper/aluminium point wiring ( light, fan , socket or power) excluding complete fittings fixture such as switches Ceiling roses, pen dents regulators, sockets etc to be measured separately and making good disturbed surfaces of walls, floors etc. complete all as specified & directed.
M&L point wiring with PVC insulated FRLS 1100 Volts unsheathed cable 1.5 Sqmm multistranded copper conductor and drawing in & including rigid PVC conduit with replacement of sunken terminal MS boxes thickness and 3 mm thick hylam sheet cover for terminal boxes for including porvision of earth wire PVC insulated FRLS 1100 Volts unsheathed 1.5 sqmm stranded copper conductor single core cable connected to common earth dolly the following :-(a) One light/fan/bell point controlled by one by one way switch (switch to be measured and paid separtely)complete all as specified & directed.
All as per items No 23 above but for One 3 pin socket outlet 5 hole 5 Amp independent including PVC unsheathed copper conductor 1.5 Sqmm cable as earth wire connected to common earth and to earth dully socket & switches to be measured and paid separately.complete all as specified & directed.
All as per items No 23 but Same board.complete all as specified & directed.
All as per items No 23 above but One power point with insulated stranded copper conductor cable 4 Sqmm single core and PVC insulated FRLS 1100 Volts unsheathed copper conductor 2.5 Sqmm S/C as earth wire connected to dolly complete ( socket and switches to be measured and paid separately) complete all as specified & directed.
M&L for submain wiring with two single core PVC insulated FRLS 1100 Volts unseathed stranded copperconductor cable 6 Sqmm in and including PVC conduit for submain wiring and connection complete including PVC unsheathed copper conuctor cable of 6 Sqmm size S/C as earthwire.complete all as specified & directed.
S&F in repair switch piano flush button type single pole one way 6 Amps complete all as specified and directed by Engineer in charge.
S&F in repair socket outlet 6 Amp flush button type complete all as specified and directed by Engineer in charge.
S&F in repair switch piano flush button type single pole 16 Amps complete all as specified and directed by Engineer in charge .
S&F in repair socket outlet, 2 in 1, 3 pin 6A and 16 Amp single pole complete all as specified and directed by Engineer in charge.
S&F ceiling rose PVC/Polycarbonate type with three terminals complete all as specified and directed by Engineer in charge.
M/L in replacement insulated body, angle holder (metal ring) with back plate complete all as specified and directed by Engineer in charge.
Supply and Fixing LED bulb 9 watts, 900 lumens output, 6500K suitable for B-22 base complete all as specified and directed by Engineer in charge .
Supply and fix LED batten luminaire surface mounted, 4 feet system wattage of 22 Watts, > 2400 systems lumen outputwith lifetime of 50000 burning hours with 70% of its initial lumen maintained. CRI>80, Power Factor > 0.95, THD< 10%, colour temperature - 6500K, surge protection 2.5KV in CM, IP-20 protected, meets LED IS specifications, Class - 1, Short circuit and over circuit protection, voltage range - 150 to 270 Volts AC, temperature range 0 to 50 DegreeC and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as specified and directed.
S/F in replacement Fully automatic star delta starter for 12.5HP to 15 HP Motor three phase 415 Volt.
Supply and fix in replacement MCB DB SPN 4 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge.
Taking down carefully unserviceable LT panel including disconnecting of incoming and outgoing connections complete all as specified and directed.
Taking down carefully unserviceable distribution boards including disconnecting of incoming and outgoing connections complete all as specified and directed.
Supply and fix MCB DB SPN 12 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge.
Supply and fix MCB DB SPN 8 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge.
Supply and fix MCB SPN 40 to 63 Amp Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge.
Supply and fix MCB SPN 32 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge.
Supply and fix MCB SP 6-32 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge.
S&F factory made epoxy powder coated Distribution board (MCCB DB) TPN 4 way vertical type, IP - 43 Protection made out of min 1.6 mm thick CRCA sheet, fabricated, metal double door fixed to wall and suitable for universal mounting and including 200 Amps rated copper bus bar, neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removeable gland plated with knockouts and suitable for TPN MCCB 125/160 Amps as incomer and 12 SP or 04 Nos TP MCBS as outgoing complete all as specified and confirming to IS : 8623 complete all as specified and directed.
Supply and fix Sub main wiring complete with two runs of 1.5 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 1 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through metallic/ non metallic conduit in walls all as specified and as directed.
Supply and fix Sub main wiring complete with two runs of 4 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 4 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 20mm dia metallic/ non metallic conduit in walls all as specified and as directed. Note: Three run of 4Sqmm cable shall be measured as one length.
Supply and fix Sub main wiring complete with two runs of 6 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 6 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 20mm dia metallic/ non metallic conduit in walls all as specified and as directed. Note: Three run of 6 Sqmm cable shall be measured as one length.
Supply and fix Sub main wiring complete with two runs of 10 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 10 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 20mm dia metallic/ non metallic conduit in walls all as specified and as directed. Note: Three run of 10 Sqmm cable shall be measured as one length.
S&F blank plate of suitable size for open space in distribution boards complete all as specified and directed.
M&L providing protection pipe PVC or flexible pipe as reqd at site to out going cables, cleaning of LT panel boards with air blower cleaning inside, dressing in proper alignment, replacement of rusted iron parts with new one with suitable size of angles/strips tightening of fixing bolts and nuts, providing thimbles to whole bunch of wires uniformly clean manner etc complete all as specified and directed.
Supply and fix in repair MCCB 160 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge.
Supply and fixing Ventilating Fan 250 mm sweep, 1250 RPM, non metallic resin body, single phase 240 volts AC 50 Hz and connecting up complete including louvers and provision of making holes and copper cable 3 core of size 0.5 sqmm for connection from ceiling rose to fan complete all as specified and as directed.
S&F switch fuse unit TPN 440V 50Hz AC 200A with HRC fuse including connecting, testing with suitable size aluminium lugs as per site requirement complete all as specified and directed by Engineer-in-Charge.
M&L earthing with galvanized steel earth plate 600 x 600 x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized iron strip 25 x 4 mm as earthing lead by means of bolts, nuts, check-nuts, and washers of galvanized iron or steel besides welding at all joints including excavation and earth work, GI pipe light grade 40 mm bore for protection of G.I. strip from earth electrode to the Main switch/Distribution Board, supplying and laying charcoal dust, common salt, PCC 1:2:4 type B-1 using 20mm graded stone aggregate chamber and MS angle iron frame 40 x 40 x 3 mm and RCC cover 40 mm thick RCC (1:2:4) type B-1 (20 mm graded stone aggregate) reinforced with 6 mm dia round bars @ 75 mm C/C both ways with MS handle 12 mm dia, round, GI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in Plate No. 3 of SSR Part I of 2009 and connected to earth test point including testing complete all as specified & directed.
S&F in repair Fresh air fan motor of capacity 1/6 HP 230 volts, 50 Hz, AC supply suitable for 250/200 mm size Fresh air fan as per sample complete all as spd and directed.
Supply only exhaust fan motor Heavy duty copper winding capacity 1/4 HP 230 volts suitable for 300 mm size exhaust fan complete all as directed.
GI Strip of size 25 x 3mm as in earth continuity conductor fixed to wall on batten or recess or cases or buried in ground or any other situation for loop earthing as required at site.
Supply and fix in repair MCCB 125 Amps, FP 415 volts 25 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge.
M&L in replacement sheet metal enclosure, single pole and neutral with a two pin and earth plug and socket 240 Volts grade 20Amps complete with one single pole MCB 'C' series 10/20 A capacity complete all as specified and directed by Engineer in charge.
M&L for disconnecting all the cable connection from indoor LT Panel and servicing to Panel board (Approximate size 1700mm x1300mm x 300mm) opening up all cubical doors, cleaning with air blower, removing the burnt out unserviceable copper wiring kit and burn out unserviceable extended copper terminals/copper cable and replacing with new copper extended terminal bus bar with suitable size along with required nut bolt, washers and cleaning with air blower to serviceable parts like MCCB's, all terminals, replacement of damaged aluminium/copper lugs any discription of LT UG cable/ copper wire incomming and out going, welding of broken door with suitable hinges, replacement of defective copper wiring with suitable copper conductor with circuit indiator replacement of defective rubber beading,writing various feeder complete all as specified and as directed.
S &F sheet metal enclosure one way for independent mounting of 4 Pole MCCB, Including MCCB 4 Pole 250 Amps 25 KA, 415 Volts complete all as specified.
Supply and lay XLPE insulated PVC bedded galvanised steel strip or wire armoured electric power cables(heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 core including connection of cable at both ends with suitable size of glands, aluminum lugs complete jointing, testing and commissioning complete all as specified and directed.
Supply and fix LED 2 X 2 ft backlite surface mounted fitting 36/40 Watts not less than 3200lm with Metallic CRCA powder coated body with high efficiency opal/PMMA diffuser with system efficacy > 80 lm/W, CRI>80, color temperature >5700k, IP 20, Power factor<0.95, THD<10%, 50000 burning hours , Ambient temperature 0 to 500 DegC, Driver should meet IEC complaint for safety, with voltage variation range of 150-270 V and surge protection of 2.5 KV including necessary fixing arrangementsfixed complete all as specified and directed by engr-in-charge.
Schedule of Credit
POONAM ENTERPRISES
M/S ANIL KUMAR
LAMBA ENTERPRISES
M/s S.G. BUILDERS
Surjit and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .