Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.2 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹30.8 L+₹1.2 L (4.03%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹31.9 L+₹2.3 L (7.81%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹32.0 L+₹2.5 L (8.37%)Rejected-AOC 37 222 BUNDU KATRA AGRA UP | AGRA | UP | L4 | Rejected-AOC L4 | |
| 5 | L5₹32.3 L+₹2.7 L (9.16%)Rejected-AOC BUILDING NO FLAT NO 19 6TH CROSS ROAD SANJEEVINI NAGAR MUDALAPALYA BANGALORE 560072 | BANGALORE | BANGALORE | KARNATAKA | 560072 | L5 | Rejected-AOC L5 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
2 Jul 2022, 6:00 pmClosed
GE Bharatpur
Kanjoli line Bharatpur
Repair to LT external electric supply, LT Cables, LT OH Lines, LT Panels and connected works at Sewar fort area and parade ground under GE Bharatpur
2022_MES_528281_1
8160/E8
Open Tender
Civil Works
Item Rate
270 days
GE Bharatpur
as per tender document
6 documents required · 6 mandatory
₹500
GE Bharatpur
₹70,000
Yes
13 Aug 2022
3 Jun 2022
9 Jul 2022
3 Jun 2022
2 Jul 2022
17 Jun 2022
6 Jun 2022 - 15 Jun 2022
Amount
Excavation in trenches, n. exc 1.5 Mtr wide and n. exc 1.5 Mtr in depth for foundation/laying of cable and getting out in soft/loose soil.
Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick.
Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point
Supply & spread unwashed dry river sand for sand cushioning for covering the under ground cable in trenches. (Note :- Punning thickness shall be measured.)
M&L for cable protection cover with sub Class`B` bricks old size laid dry, flat perpendicular across the cable in trenches complete all as directed.
M/L for taking out Unsv U/G cable PVC insulated armoured PVC sheathed Al. Conductor, LT cable of any size.
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole of the following sizeS:- 240 Sqmm 3.5 core
185 Sqmm 3.5 core
120 Sqmm 3.5 core
95 Sqmm 3.5 core
70 Sqmm 3.5 core
50 Sqmm 3.5 core
25 Sqmm 4 core
16 Sqmm 4 core
10 Sqmm 2 core
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable of single core 95 Sqmm with stranded copper conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole
S&F in repair on existing location including taking out of existing MCCBs of following capacity :- MCCB 415 volts 400 Amps 04 pole 50KA
MCCB 415 volts 250 Amps 04 pole 36 KA
MCCB 415 volts 200 Amps 04 pole 36 KA
MCCB 415 volts 160 Amps 03 pole 36 KA
MCCB 415 volts 100 Amps 04 pole 25 KA
MCCB 415 volts 63 Amps 04 pole 25 KA
S & F or laying galvanised steel tubing light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing of size 50mm bore.
S & F or laying galvanixed steel tubing light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing of size 100mm bore.
M&L for road cutting in 300mm width & 450mm depth & repair to existing with bitumen premixed incl 150mm WBM complete all as specified and as dirceted
M&L for LT cable fault rectification upto 240 sqmm X 3.5/4 core by using Fault locator machine to detect fault and rectify the same incl T&P & items ie lugs,tape etc all as directed by Engr-in-charge.
M&L for cable jointing kit for 1.1 KV grade for straight through joint complete with jointing material and accessaries suitable for 3.5/4 core XLPE armourd aluminium conductor cable of following size after detaction of fault location .Make:3 M,Denson or equivalent Note: Earth work and returning filling which require in above job will be measured and paid seperataly. 25 Sqmm to 50 Sqmm
70 Sqmm to 120 Sqmm
150 Sqmm to 240 Sqmm
Complete removing paint from surface of Panel box and M & L for 02 coats of painting with approved colour of synthetic enamelled paint over a coat of red oxide primer for size of Panel boxes from all in & out side incl angle iron frame work min 04 Sqm area of sheets including angles canopy and legs etc. Note: Permission to shutdown of electric supply to the panel to be taken from MES before commencement of work.
Supply, install, commissioning and testing factory made (including CPRI test certified ) LT panel box (KIOSK) out door type mounted on MS angle ISA 40X40X5mm stand suitable for 415 volt , 3 phases, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with insulated copper bus bars 200 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & 2.0mm thick inner and individual compartment for MCCB/MCB & volt/Amps meter.The complete feeder pillar box should be powder coated including connections between main bus bar to outgoing MCCB/MCB shall be carried out by copper busbar 63Amps and above MCCB & below 63Amps by 16 Sqmm copper cable. Front opening type with approach for cable entry with double door shutter including locking arrangement as per manufacturers instruction with 2 Keys complete all as specified and directed.
Incoming
(a) MCCB 4 Pole, 415 V,Thermal Magnetic release, Adjustable type, 100 Amps with 25 KA rapturing capacity - 01 No.
(b) ON load changeover switch of cap-100Amps,4pole - 01 No
(c) Bus bar copper 200 Amps - 01 Set of 4
(f) Indicator lamp for three phase and seletor switch complete as required
Note: (i) Drawings of LT panel shall be got approved by GE beforeoreder placing to Manufacturer. (ii) Panel stand shall be made out of 40X40X5mm ISA angle of 60cm height and appropriate size as per panel. The same should be fixed in PCC 1:2:4 type B-1 below ground level 30cm and above ground level 20cm.
M& L for Earthing complete with galvanised mild steel plate electrode 600x600x6 mm thick buried directly in ground vertically (earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate electrode at a depth not less than 1.5m below normal ground level and including GI earth strip 32x6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate electrode at one end connected to metallic bodies of HT/LT equipment etc at the other and earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of earth plate electrode to body of equipment fixed with and including 25x6 mm flat iron clamps bolts, nuts and washers and including providing watering pipe 20mm bore GI Pipe electrode complete all as specified and shown in elctrical plate No 3 of MES SSR Part-I. the scope of work includes necessary excavation and earth work in any type of soil. removal of soil upto 50 metre PCC pit with precast RCC cover, charcoal/salt funnel, CI frame etc complete all as specified & directed.
NOTE:(I) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.50 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC(1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars @ 150mm c/c both ways. (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be adjusted through deviation order (iii) Item includes cost of 7.5 metre earth lead strip .Any variation in length shall be adjusted through deviation order. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thinkness of 15 cm on all sides.
Demolition of old PCC and M&L for cement concrete 1:4:8 type D2 (using 40 mm graded crushed stone aggregate) as in foudation,filling and mass concrete complete
Demolition of old PCC and M&L for cement concrete (1:2:4) type B-1 using 20mm graded crushed stone aggregate for pedestal of poles/ coping including necessary formwork, fair finishing to exposed surfaces using extra cement.
M&L for disconnection of LT panel incl LT cables of size upto 240Sqmm X 3.5/4core from existing foundation and reconnection with same panel after taking necessary corrective action to lift the panel height incl excavation and taking down existing cable with loop, providing new AL lugs and cable gland of appropriate size,insulation tape etc to restore electric supply incl necessary iron work to modify height of existing LT panel upto 1.2 Mtrs above existing level incl necessary welding work,nuts & bolts and 2 coat of paint with existing color over one coat of primer and required necessary PCC work complete all as specified and directed by Engr-in-charge. Note: PCC shall be measured & paid separately under respective item.
Supply and fix electronic meters temper proof LCD display with polycarbonate cover 230 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS13779, IP-54, with parameters to show data, time,current reading, load, PF, voltage and KWH complete incl taking down old unsv eletric meter & deposit to MES store yard
Ditto all as per item No 21 here in above but 3 Phase, 415 volt.
Supply and fixing of single / Three phase meter box made of accrylic sheet complete all as specified and directed by Engr-in-charge.
S & F in replacement low intensity twin type LED Aviation obstruction light fixed on OHT of cast aluminium ,Red in lighting color ,50 Hz, 230V AC operation range, IP 65 standard,power consumption 18 watt min Lux level 32 Lux at 1 Mtr required incl fastners/nut,bolts/clamp for fixing complete all as specified and directed by Engr-in-charge. Make: CG/Bajaj/Phillips
Supply and fixing in replacement of Lithium base Energy efficient integrated Solar street light of 36 watt in single FRP body duly polyurethane coating (Camouflage color), encases with monocrystalline solar PV panel of 65-67Wp,lithium battery 11.1/12.8V,33.0 AH with inbuilt BMS,IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminium reflector for better light distribution ,CRI>70, color temp 5700K-6500K Microcontroller based charge controller cum driver,automaticdimming function(First 04 hrs at full brightness & rest of the time at lower light level with PIR motion sensor), Dusk to dawn operation,suitable to working temp (-) 10C to (+) 55C ,weight not more thatn 16-18 Kg with adjustable MS clamp suitable for pole/wall mounting etc complete as reequired.Make: AXXON/HAVELLS/PHILLIPS/CG Protections: Short circuit, overload,Reserve polarity and battery protection.Firm should provide vital parametres Test report from NABL accredited lab and should be of made in India with CE & ROHS complaint. (Excavation & earth work shall be measured separately)
S&F in replacement new generation energy saving and environmental friendly long life varsatile pressure die cast aluminium IP66 road way light fitting with high power LED as light source of capacity 60 watts (Surge protection of the light should be 10 KV )with suitable drivers etc and connecting with 4.0 sqmm aluminium solid conductor PVC insulated twin core weather proof cable etc, fixing to wall / pole with and including bracket made out of GI pipe of 40mm dia light grade not less than 1.5 mtr long, bent to shape, fixed to Pole/Wall in any position with flat iron clamps of size 30 x 4mm complete all as specified and directed. Make:- Crompton / Philips/Bajaj/Havells.
Supply and fixing of PVC conduit size 25mm Rigid non-metallic PVC conduit exclusive of boxes (junction/terminal) but inclusive of all tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories including chase cutting such as couplers, lock nuts, saddles, pipe hooks etc
M/s Ranaji Construction Co
krishna Associate
PD GUPTA AND COMPANY
Rahul Enterprises
B R ENTERPRISES
TRIVENI ASSOCIATES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .