GENERAL MANAGER
VERKA BATHINDA DAIRY
SUPPLY INSTALLATION AND COMMISSIONING 11 KV SUB STATION
2020_Coop_44876_1
VERKA_BTD_ENGG11KV
Open Tender
Electrical Works
Item Wise
90 days
VERKA BATHINDA DAIRY
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
VERKA BATHINDA DAIRY
₹2 L
25 Jul 2020
20 Feb 2020
19 Mar 2020
20 Feb 2020
18 Mar 2020
20 Feb 2020
RECESSED CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES
Wiring in PVC insulated Fire Retardent Copper conductor (ISI marked) Un-sheathed flexible multistrand cable to be laid in heavy gauge uPVC, fire retardent conduit pipe 20mm/25mm dia 2 mm thick ISI marked, recessed in wall etc complete with powder coated/anodized concealed metal boxes required for suitable number of modules for having electronic fan regulators, bell push, electronic buzzer 3 pin 6 Amp, 3 pin 16/20 Amp sockets and 6 Amp, 16/20 Amp Switches ( Screw Type Modular Accessories ) etc. and covered with Frame Plate etc & including the cost of required number of modular Switches / Sockets step type Electronic fan Regulator 100 Watts. PVC connector ( For Fan Box and Electronic Buzzer ) PVC connector (for fan box & electronics buzzer), Steel Hooks, Circular inspection box ( Recessed Type and Deep Type ) PVC conduit pipe & copper wire and other petty material etc including the cost of cutting and filling up of chases.
Wiring fan point with sheet metal fan box (shape hexagonal & sheet thickness not less than 1.60 mm) in PVC insulated copper conductor single core FRLS cable (ISI marked) overall 1.5 sq. mm, 1100volts grade with step type electronic fan regulator 100watts (two module).
Wiring light point in PVC insulated copper conductor single core FRLS cable (ISI marked) overall 1.5 sq. mm, 1100volts grade .
Wiring light point in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5 sq. mm, 1100volts grade complete without control switch.
Wiring 3 pin 16/20 amp. power plug control (shuttered) and switch.
LIGHT / POWER CIRCUIT WIRING : Supply and erection of PVC insulated single core FRLS copper conductor cable ISI marked left bare in pipe or casing of suitable size excluding the cost of supply and erection of pipe or casing.
PVC insulated copper conductor single core FRLS cable (ISI marked) overall 1.0 sq.mm, 1100volts grade
PVC insulated copper conductor single core FRLS cable (ISI marked) overall 2.5 sq.mm, 1100volts grade
PVC insulated copper conductor single core FRLS cable (ISI marked) overall 6 sq.mm, 1100volts grade
PVC insulated copper conductor single core FRLS cable (ISI marked) overall 10 sq.mm, 1100volts grade
PVC, HDPE PIPES & PVC FLEXIBLE PIPES : Supply & erection of PVC HDPE pipe (fire retardent) for wiring purposes including bends, inspection boxes etc., where necessary including painting as per PWD General Specifications 2010:-
Heavy gauge PVC conduit pipe 40 mm dia (ISI marked 2mm thick) (Flushed)
RCCB, MCB SP, DP, TP, TPN & FP : Supply and erection of Miniature Circuit Breakers/ RCBO's/ RCCB's in the existing MCB distribution board as per PWD General Specifications 2010 including connections with suitable size of thimbles/lugs.
GROUP-A: SIEMENS (Beta Guard), LEGRAND (Ekinoxe), SCHNEIDER (Acti9), L & T (Hager Vision)
Miniature circuit breaker single pole 6 to 32amp. (Breaking capacity 10kA, Curve-C) suitable for 240/ 415 volts 50cycles (for L/PDB)
Miniature circuit breaker tripple pole 63amp. (Breaking capacity 10kA, Curve-C) suitable for 240/ 415 volts 50cycles (for VDB)
Miniature circuit breaker four pole 63 amp. (Breaking capacity 10kA, Curve-C) suitable for 240/ 415 volts 50cycles (As I/C of L/PDB)
RCCB : Residual Current Circuit Breaker (RCCB for Earth Leakage Protection) Double Pole 63amp. Sensitivity 300ma (As per Standard IEC 61008) suitable for 240 / 415Vols 50Hz AC supply
MOULDED CASE CIRCUIT BREAKER
Supply and erection of MCCB (Panel Mounted Cubicle Type) in the exixting cubicle panel (Confirms to IEC : 60947-II) and relevant PWD specifications 2010 complete with GI bolts, nuts, & connection on both sides of MCCB with suitable size of thimbles etc.
MCCB Adjustable Thermal & Magnetic Protection Make : L & T (DSine), ABB (T-MAX), Scheneider (NSX), Siemens (3VL)
125Amp, 415V breaking capacity ≥ 35kA FP Adjustable Thermal & Magnetic Protection MCCB unit (As Incomer of L/PDB)
SHEET METAL DOUBLE DOOR DISTRIBUTION BOARDS FOR MCB/RCBO/RCCB`s Supply and erection of sheet metal double door distribution boards of suitable size and of required number of ways for mounting MCB/RCBO/RCCB in the existing MCB DB as per PWD General Specification 2010 including connections with suitable sizes of thimbles and bondings to existing earth etc.
GROUP - A SIEMENS (Beta Guard), LEGRAND (Ekinoxe), SCHNEIDER (Acti9), L & T (Hager Vision)
Sheet metal double door T.P. & N (horizontal design) distribution board (dust protected) provided with bus-bar neutral link and din bar, suitable for incorporating FP MCB for incoming and Single Pole MCB`s for outgoing 8 way each
Sheet metal double door T.P. & N (Vertical design) distribution board (dust protected) provided with bus-bar neutral link and din bar, suitable for incorporating FP MCCB`s for incoming and Tripple Pole MCB`s for outgoing 4 way each
EARTHING OF METALLIC CASES / EQUIPMENT's ETC.
Earthing of sheet metal / iron clad switches and metallic cases etc with No.7/12 SWG (7/2.80mm) in 20mm dia GI pipe partly on surface complete with 135cm long 50mm dia GI earth pipe with GI reducing socket (50mmx20mm) including erection of the same,10 mtr below ground level with necessary charcoal salt mixture etc upto 13 mtr in length (including boring & refiling)
Earthing of Metallic cases etc., with G.I. stranded wire No. 7/12 SWG (7/2.80mm) in 20mm dia G.I. pipe recessed inwall and floor etc., as required.
Earthing of metallic cases etc., with G.I. wire No. 8 S.W.G. (4mm dia.) in 15mm dia. G.I. pipe recess in wall etc. (as additional length)
Earthing of Sheet metal/ iron clad switches and metallic cases etc., with 40 mm x 5 mm thick electrolytic copper tape rivetted (with 10 nos. copper rivets) to 30 cm x 120 cm x 3 mm thick tinned copper plate (made cylindrical) burried 20 metre below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper tape on wall and in floor etc., up to 23 metre in length (including bore length). G.I. pipe 20mm dia. (A-class) should be laid in the hole of excavation from bore surface level to 1 feet below ground level and having wire mesh funnel fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm around the hole of excavation. (for Neutral of TR & DG)
Supply and Erection of 40mm x 5mm thick copper tape (As additional length).
Earthing with G.I. (Hot Dip) earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. and earth collecting strip 50 X 5mm thick (Hot Dip) with charcoal/ coke and salt as required. (for TR Body - 4nos, DG Body-4nos, MLTP -2nos, LBS - 2nos, VCB - 2nos)
Supply and Erection of 50mm x 5mm thick G.I. (Hot Dip) tape (As additional length).
MAIN LT PANEL
LT PANELS Supply/Receiving/Handling/Erection/Testing & Commissioning of cubicle type (bolted & modular construction) panels, fabericated out of 1.6 mm / 2mm (All load bearing member shall be 2mm and other parts shall be 1.6mm) rust inhibited CRCA sheet steel, 7 tank treated sheets and powder coated shall be complete with incoming and out-going feeders, electrolytic grade (E91) aluminum bus-bar, duly insulated with heat shrinkable PVC colour coded sleeves,shrouders, bus-bar droppers, supported on DMC/SMC insulators. Panel construction shall be Modular and fool proof protection from dust, water, humidity, fire, vibratioins, temerature, variations, pull tension, noise, entry of rodent etc. with heavy duty neoprene gaskets. The floor mounting panels shall be provided with mounting channels not less than 75mm X 75mm X 5mm thick of size (for floor mounting panels). Panels shall have aluminum earth bus through out the panel of suitable size. The panel shall be provided with name / designation plate for all incoming/ outgoing feeders, danger plate, door steel locks etc. The key should be common for all compartment / doors. The doors of compartment must not open when switch is in "ON" position and provision of de-interlock facility shall be provided. Internal control / power wiring of the panel shall be carried out with FRLS insulated copper conductors PVC insulated. All testsl shall be carried out as per IS Standards as applicable in the presence of client or his representative and all tests certificates shall be submitted to the client in original duly signed by concerned authority. The switchboard shall be complete in all respect as desired by client. Make of Panels = L&T, Schneider, ABB & Siemens (OEM only/Franchise), responsibility shall be with OEM.
GENERAL NOTE FOR CONTRACTOR
The rates for all these items under the following heads should include all necessary items and equipments as required.
Assembling loose components of the various equipment as per manufacturer's instructions or as per advise of Engineer-in-Charge
Bonding onto masonry/concrete work including cutting/drilling holes through walls/floors and grouting with cement mortar 1:2:4 (provide the finish level)
Providing all fixing accessories such as nuts, screws, bolts, Anchor Fastners etc. as required.
Effecting adequate and proper connections to the main Earthing Stations (AS PER IS 3043)
Touching up all damaged paint over equipment with same type shade and painting the MS angle , C-channels etc. with two coats of Red Oxide & Two Coats of finishing approved synthetic enamel paint.
All items listed in the BOQ shall be of approved make only as per tender.
Any unspecified item shall be as per approval of consultant / Architect / Owner.
All Digital Meters shall have RS 485 Port
All Panels/Cubicle shall be provided with sufficient number of Space Heaters (80 Watts) Controlled by Thermostate and MCB
All wires used in the panel shall be multistranded copper conductor LSZH insulated, 1100V Grade.
CT, PT & Earth wires shall be 2.5Sq.mm copper conductor, LSZH, PVC insulated and Control wiring not less than 1.5sqmm, FRLS PVC insulated, copper conductor shall be used. Color Coding shall be as per the IS standard. Power wiring shall be of suitable rating with FRLS, PVC insulated, copper conductor multistrand.
Note : Any item seems to be missing and needed for smooth running/functioning of the system shall be treated as included and no extra price will be paid for the same.
Aluminium Busbar shall be Electrolytic Grade - E91. Busbar shall be duly covered with heat shirankable PVC Insulated coloured sleeve. Neutral bus shall be equal to the Phase Bus. Current Density for Aluminum bus shall be consider as 0.8A / Sq.mm
ACB MP Based, Make :- L&T Model U-Power (Omega MTX3.5EC), FP, 50kA, Schneider Master Pact (NW Micrologic 6E), FP, 50kA , Siemens Model 3WL (ETU76B), FP, 50kA. ABB (Emax PR123) FP, 50kA. ACB release should be have Inbuilt Energy monitoring (V,I,F, PF,KW,KwH, KVA, kVAH, THD etc.), 5 Last Fault trip history, with Communication Module for Data Transfer on PC/Laptop, Trip Histroy with Data and Time should display on PC/Laptop. All ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact. DG Feeder shall have external Reverse Power Relay.
M/P Based MCCB Make :-All MCCB`s with M/P Based and having O/L, S/C & E/F Protection - MCCB release should be with Communication Module for Data Transfer on PC/Laptop, Trip Histroy with Data and Time should display on PC/Laptop. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Instantaneous Current and Fault current with Date/time L&T Model D-Sine (MTX2/3), Schneider Model NSX (Micrologic 6A), Siemens Model 3VA (ETU560). ABB Model Tmax.(PR332)
TMD Based MCCB Make :-All MCCB's with TM Based and having Abjustable O/L, S/C Protection - L&T Model D-Sine), Schneider Model NSX, Siemens Model 3VA. ABB Model Tmax. (T2 Frame) Ics=Icu=100%
All settings of Relay/Releases of ACB/MCCB shall be set as per the requirement of the site and it will be in the scope of Manufacturer through Contractor.
The Bus-bar supports shall be on Cast Epoxy/ Resin/ Fiber Glass Insulator/ DMC and sized as per CPWD specifications. The live parts of the panel shall be shrouded/covered by un-breakable polycarbonate sheet with suitable warning stickers
All CT`s shall be Cast Resin Type, for Metering CL-0.5, Burden 15VA, & for Protection CL-5P10, Burden 15VA,
Contactor to maintain the site neat & clean and all debris to be cleared from the site on completion of day work before leaving the site.
All Meters in Main LT panel should be with RS485 Port, connected with each through 2 Core Shielded Cable. Data of Main LT Panel Meters V, A, Hz, Pf, KWh, KVA, THD, KVAH etc should be display on PC/ Laptop through Ethernet gateways or Software (Should be supplied along with Panel). All ACB of Main LT Panel should also connected with Same system for display of Trip History with date and time on PC/Laptop Make : L&T, Schneider, Siemens, ABB
MAIN LT PANEL
INCOMER TRANSFORMER - 1 & 2
Phase Indicators LED R-Y-B with HRC Fuse/MCB - 02 Set
Neutral Link 16A - 02nos
16A TPN MCB, 10kA, Curve - C (for Synch Panel Raw Supply) - 02nos
25kVAR, Heavy Duty, Box/Cylindrical type Resin filled, 480V Capacitor (Loss 0.35W/kVAr) with 63A, TPN MCCB, 50kA, Adj. TMD Including ROH, Spreader with ON/OFF LED Indicators including suitable ratings MCB, 10kA, Curve - C for indicators - 02set
1600A FP ACB, EDO, 50KA, Manually Draw Out with Microprocessor Based Protection with O/L, S/C & E/F, Icu = Ics = Icw =100%, Omega MTX3.5EC), Schneider Master Pact (NW Micrologic 6E), Siemens Model 3WL (ETU76B), ABB (Emax PR123). ACB release should be have Inbuilt Energy monitoring (V,I,pf,KW,KwH etc.), 5 Last Fault trip history, Communication Module, ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact.. - 02 nos
ON, OFF, TRIP, SC & TCH LED Indication with required MCB etc. - 02Each
TNC Switch 16Amp. - 02nos
Electrical Interlocking accessories as required -02Set
3 Phase Over Current + Earth Fault Relay Neumerical type with High Set, Operating Voltage 240V AC including control fuse/MCB etc Complete in all respect as required - 02nos
CTR 1600/5, Burden - 15VA, Class - 0.5 for metering & APFC Relay -12nos
CTR 1600/5, Burden - 15VA, Class - 5P10 for 51/51N -06nos for Protection
Digital Multifunction Meter having RS 485 Port (V,A,Hz,Pf,KW, KWh, KVA, THD,KVAH). Ref. Model Schneider EM6400Ng or equivalent - 02nos
Voltage Monitering Relay - 02Nos
Termination of Bus Duct incoming from Transformer
INCOMER FROM SYNCH. PANEL - 1 & 2
Phase Indicators LED R-Y-B with HRC Fuse/MCB - 02 Set
Neutral Link 16A - 02nos
2500A FP ACB, EDO, 50KA, Manually Draw Out with Microprocessor Based Protection with O/L, S/C & E/F, Icu = Ics = Icw =100%, Omega Frame UW225 MTX3.5E), Schneider Master Pact (NW Micrologic 6E), Siemens Model 3WL (ETU76B), ABB (Emax PR123). ACB release should be have Inbuilt Energy monitoring (V,I,pf,KW,KwH etc.), 5 Last Fault trip history, Communication Module, ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact. - 02 nos
ON, OFF, TRIP, SC & TCH LED Indication with required MCB etc. - 02Each
TNC Switch 16Amp. - 02nos
Electrical Interlocking accessories as required -02Set
3 Phase Over Current + Earth Fault Relay Neumerical type with High Set, Operating Voltage 240V AC including control fuse/MCB etc Complete in all respect as required - 02nos
CTR 1600/5, Burden - 15VA, Class - 0.5 for metering - 06nos
CTR 1600/5, Burden - 15VA, Class - 5P10 for 51/51N -06nos
Digital Multifunction Meter having RS 485 Port (V,A,Hz,Pf,KWh, KVA, THD,KVAH). Ref. Model Schneider EM6400NG or equivalent - 02nos
Voltage Monitering Relay - 02Nos
Termination of LT Power Power Cables as per SLD.
BUS COUPLER
1600A FP ACB, EDO, 50KA, with Microprocessor Based Protection with O/L, S/C & E/F, Icu = Ics = Icw =100%, Omega MTX3.5E), Schneider Master Pact (NW Micrologic 6E), Siemens Model 3WL (ETU76B), ABB (Emax PR123). ACB release should be have Inbuilt Energy monitoring (V,I,pf,KW,KwH etc.), 5 Last Fault trip history, Communication Module, ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact. - 01 nos
ON, OFF, TRIP, SC & TCH LED Indication with suitable rating 3nos MCB, 10kA, Curve - C, -01set
Neutral Link 16A - 01nos
TNC Switch 16Amp. - 01nos
Electrical Interlocking accessories as required -01Set
BUS-BAR
Aluminium busbar 2500 amp, TPN with colour coded sleeves, Aluminium Grade E-91, Neutral Bus shall be Half of the Phase and Currenty density 0.8Amp per sqmm.
OUT GOINGS
800Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current including in built Neutral O/L protection, Front LED Indication, Extended Rotary Handle, Spreaders, 800/5A, 3nos CT`s, Cl-0.5, Resin Cast Digital Multifunction Meter with RS 485 Port (V, A, Hz, Pf, KWh, KVA, THD, KVAH). Ref. Model Schneider EM6400NG - 04set
630Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current including in built Neutral O/L protection, Front LED Indication, Extended Rotary Handle, Spreaders, 630/5A, 3nos CT`s, Cl-0.5, Resin Cast Digital Multifunction Meter with RS 485 Port (V, A, Hz, Pf, KWh, KVA, THD, KVAH). Ref. Model Schneider EM6400NG - 05set
400Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module.. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current including in built Neutral O/L protection, Front LED Indication, Extended Rotary Handle, Spreaders, 400/5A, 3nos CT`s, Cl-0.5, Resin Cast Digital Multifunction Meter with RS 485 Port (V, A, Hz, Pf, KWh, KVA, THD, KVAH). Ref. Model Schneider EM6400NG - 01set
320Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current including in built Neutral O/L protection, Front LED Indication, Extended Rotary Handle, Spreaders, 320/5A, 3nos CT`s, Cl-0.5, Resin Cast Digital Multifunction Meter with RS 485 Port (V, A, Hz, Pf, KWh, KVA, THD, KVAH). Ref. Model Schneider EM6400NG - 03set
250Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current including in built Neutral O/L protection, Front LED Indication, Extended Rotary Handle, Spreaders, 250/5A, 3nos CT`s, Cl-0.5, Resin Cast Digital Multifunction Meter with RS 485 Port (V, A, Hz, Pf, KWh, KVA, THD, KVAH). Ref. Model Schneider EM6400NG - 02set
125Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current including in built Neutral O/L protection, Front LED Indication, Extended Rotary Handle, Spreaders, 150/5A, 3nos CT`s, Cl-0.5, Resin Cast Digital Multifunction Meter with RS 485 Port (V, A, Hz, Pf, KWh, KVA, THD, KVAH). Ref. Model Schneider EM6400NG - 04set
100Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current including in built Neutral O/L protection, Front LED Indication, Extended Rotary Handle, Spreaders, 100/5A, 3nos CT`s, Cl-0.5, Resin Cast Digital Multifunction Meter with RS 485 Port (V, A, Hz, Pf, KWh, KVA, THD, KVAH). Ref. Model Schneider EM6400NG - 01set
CAPACITOR BANK PANEL - 1 & 2
INCOMER
To be connected with BUS-BAR with the respective section of the MAIN PANEL (Incomer Consider in the Main Panel)
Phase Indicators LED R-Y-B with HRC Fuse/MCB - 01 Set
16Amp. Neutral Link - 01 Nos
12/14 steps Intelligent microprocessor based Automatic Power factor Correction relay having measurment sensitivity of 1 %.
OUTGOINGS :
125A, 415V, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 05Nos.
63A, 415V, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 03Nos.
40A, 415V, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 01Nos.
25A, 415V, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 2Nos
16A, 415V, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 1Nos
50kVAR rating Capacitor Duty contactor with 2NO + 2NC - 5Nos.
25kVAR rating Capacitor Duty contactor with 2NO + 2NC- 3Nos.
10kVAR rating Capacitor Duty contactor with 2NO + 2NC - 2Nos.
5kVAR rating Capacitor Duty contactor with 2NO + 2NC - 2Nos.
2.5kVAR rating Capacitor Duty contactor with 2NO + 2NC - 1Nos.
ON/ OFF delay timers for switching capacitor circuit - 13Nos
"ON" and "OFF" LED indicating push buttons with inbuilt lamps and 2A control SP MCBs - for each capacitor ban - 13Sets.
50kVAR super heavy duty, low loss (0.35W/kVAR) Capacitor bank 480V Box/Cylinderical type duly Resin filled - 05 Nos.
25kVAR super heavy duty, low loss (0.35W/kVAR) Capacitor bank 480V Box/Cylinderical type duly Resin filled - 03 Nos.
5kVAR super heavy duty, low loss (0.35W/kVAR) Capacitor bank 480V Box/Cylinderical type duly Resin filled - 02 Nos.
2.5kVAR super heavy duty, low loss Capacitor bank (0.35W/kVAR), 480V Box/Cylinderical type duly Resin filled - 01 Nos.
SYNCHRONIZING PANEL
INCOMER (DG-1 & 2)
Phase Indicators LED R-Y-B with HRC Fuse/MCB - 02 Set
Neutral Link 16A - 02nos
1250A FP ACB, EDO, 50KA, Manually Draw Out with Microprocessor Based Protection with O/L, S/C & E/F, Icu = Ics = Icw =100%, Omega MTX3.5EC), Schneider Master Pact (NW Micrologic 6E), Siemens Model 3WL (ETU76B), ABB (Emax PR123). ACB release should be have Inbuilt Energy monitoring (V,A,Hz,Pf,KW, KWh, KVA, THD,KVAH etc.), 5 Last Fault trip history, Communication Module, ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact. - 02 nos
ON, OFF, TRIP, SC & TCH LED Indication with required MCB etc. - 02Each
TNC Switch 16Amp. - 02nos
Electrical Interlocking accessories as required -02Set
3 Phase Over Current + Earth Fault Relay Neumerical type with High Set, Operating Voltage 240V AC including control fuse/MCB etc Complete in all respect as required - 02nos
CTR 1250/5, Burden - 15VA, Class - 0.5 for metering - 06nos
CTR 1600/5, Burden - 15VA, Class - 5P10 for 51/51N -06nos
Digital Multifunction Meter having RS 485 Port (V,A,Hz,Pf,KWh, KVA, THD,KVAH). Ref. Model Schneider EM6400NG or equivalent - 02nos
Voltage Monitering Relay - 02Nos
325A, FP, Power Contactor AC 3 Duty with Copper Shorting Links of suitable rating 2Nos per Contractor - 02 Nos
INCOMER (DG-3)
Phase Indicators LED R-Y-B with HRC Fuse/MCB - 01 Set
Neutral Link 16A - 01nos
800A FP ACB, EDO, 50KA, Manually Draw Out with Microprocessor Based Protection with O/L, S/C & E/F, Icu = Ics = Icw =100%, Omega MTX3.5E), Schneider Master Pact (NW Micrologic 6E), Siemens Model 3WL (ETU76B), ABB (Emax PR123). ACB release should be have Inbuilt Energy monitoring (V,I,pf,KW,KwH etc.), 5 Last Fault trip history, Communication Module, ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact.. - 01 nos
ON, OFF, TRIP, SC & TCH LED Indication with required MCB etc. - 01Each
TNC Switch 16Amp. - 01nos
Electrical Interlocking accessories as required -01Set
3 Phase Over Current + Earth Fault Relay Neumerical type with High Set, Operating Voltage 240V AC including control fuse/MCB etc Complete in all respect as required - 01nos
CTR 800/5, Burden - 15VA, Class - 0.5 for metering - 03nos
CTR 800/5, Burden - 15VA, Class - 5P10 for 51/51N -03nos
Digital Multifunction Meter having RS 485 Port (V,A,Hz,Pf,KWh, KVA, THD,KVAH). Ref. Model Schneider EM6400NG or equivalent - 01nos
Voltage Monitering Relay - 01Nos
200A, FP, Power Contactor AC 3 Duty with Copper Shorting Links of suitable rating 2Nos per Contractor - 01 Nos
BUS COUPLER
2500A FP ACB, EDO, 50KA, Manually Draw Out with Microprocessor Based Protection with O/L, S/C & E/F, Icu = Ics = Icw =100%, Omega Frame UW225 MTX3.5E), Schneider Master Pact (NW Micrologic 6E) , Siemens Model 3WL (ETU76B), . ABB (Emax PR123). ACB release should be have Inbuilt Energy monitoring (V,I,pf,KW,KwH etc.), 5 Last Fault trip history, Communication Module, ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact. - 01 nos
ON, OFF, TRIP, SC & TCH LED Indication with suitable rating 3nos MCB, 10kA, Curve - C, -01set
Neutral Link 16A - 01nos
TNC Switch 16Amp. - 01nos
Electrical Interlocking accessories as required -01Set
BUS-BAR
Aluminium busbar 3200 amp, TPN with colour coded sleeves, Aluminium Grade E-91, Neutral Bus shall be Half of the Phase and Currenty density 0.8Amp per sqmm.
OUT GOINGS
2500A FP ACB, EDO, 50KA, Manually Draw Out with Microprocessor Based Protection with O/L, S/C & E/F, Icu = Ics = Icw =100%, Omega Frame UW225 MTX3.5E), Schneider Master Pact (NW Micrologic 6E), FP, 50kA , Siemens Model 3WL (ETU76B), FP, 50kA. ABB (Emax PR123) FP, 50kA. ACB release should be have Inbuilt Energy monitoring (V,I,pf,KW,KwH etc.), 5 Last Fault trip history, Communication Module, ACB shall be with Terminal Adaptor on both sides, Safety Shutters, 4 Change Over contacts, Fault Indication Contact. - 02 nos
ON, OFF, TRIP, SC & TCH LED Indication with suitable rating 3nos MCB, 10kA, Curve - C, -02set
Neutral Link 16A - 02nos
TNC Switch 16Amp. - 02nos
Electrical Interlocking accessories as required -02Set
Syn. Controller Model Easygen 3200 (make - Woodward) - 03 Nos
Gateway (KW & KVAR) (Make - Woodward) - 01 Nos
Micrology PLC (Make Allen Bradley) suitable for Syn. Panel - 01 Nos
Battery Charger of suitable rating with features like Trickle, Boost & float charging - 03Nos
All other accessories required for the panel for smooth functioning
SUB LT PANEL NEAR RMP AREA
INCOMER
Phase Indicators LED R-Y-B with HRC Fuse/MCB - 02 Set
Neutral Link 16A - 02nos
800Amp. FP, MCCB, O/L, S/C & E/F 36ka with Microprocessor Based Release, Ics = 100% Icu, MCCB release should be communication Module. MCCB release should have display to Indicated type of fault O/L, S/C and E/F. also display Current instantaneous and Fault current, Front LED Indication, Extended Rotary Handle, Spreaders. - 02set
Digital Multifunction Meter having (V , I & F). - 02nos
CTR 800/5, Burden - 15VA, Class - 0.5 for metering - 06nos
Mechanical Interlocking arrangement (2 Lock & 1 Key) - 01Set
BUS-BAR
Aluminium busbar 800 amp, TPN with colour coded sleeves, Aluminium Grade E-91, Neutral Bus shall be Half of the Phase and Currenty density 0.8Amp per sqmm.
OUT GOINGS
400A, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 01Nos.
200A, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 01Nos.
160A, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 03Nos.
100A, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 01Nos.
63A, 25 KA TP MCCB with Adj. TMD + ROH + Seperader - 01Nos.
63A, TPN, 10 KA, MCB, Curve-C - 04Nos.
BUS DUCT/TRUNKING (TRANSFORMER TO LT PANEL)
Supplying, Installation including Suspension, Testing & Commissioning of following Capacity Sandwich type, Aluminum busway (3L+N+PE), with Original Mylar insulation, , 100% N, 50kA for 1 sec, 50% Integral or Internal Earth, Housing 1.6mm thick Electro-galvanized steel), Paint: Epoxy electrostatic powder,Temp rise: 55 deg. over ambient of 40 deg. Rated insulation voltage = 1000V. (Fully Type tested as per IEC-61439-12) supply including Jointing of sections, Flexible Joints, Expansion Joints, Flenge End, Bends, Adaptor Box, Links, Hangers and earting with 2 runs of hot dip galvanised iron strips of size 50 X 6mm (one on each side), Suspenders, angle iron bracket, steel fastners, connecting to earthing system etc. Complete in all respect as required at site.
1600Amp Rating, 50KA/1Sec (Qty. shall be checked with actual requirements)
NOTE : ACTUAL LENGTH & ROUTE SHALL BE TAKEN BY THE CONTACTOR ON INSTALLATION OF RELATED EQUIPMENT
LIGHT FIXTURES AND FANS
Light Fixtures
S/E of Bajaj Model No. BCLSBAL 18W, 1 X TL-18W indoor decorative, Extruded Aluminum LED Batten, surface mounted luminaire complete with all accessories or equivalent make as approved by the Engineer in charge complete in all respect as required.
Supply and eraction of Heavy Duty Exhaust Fan totally enclosed heavy duty motor with die cast aluminium rotor mounted on 2 ball bearings, IP 65 range and available with ISI mark, Make Crompton Greaves or equilant as required by the site Engineer - In - Charge complete in all respect.
Exhaust Fan 300mm sweep (900 rpm) CGL Ref Model EXHD 300-6-1
Supply and eraction of alluminium louver shutter for exhaust fan
11KV VCB PANEL BOARD WITH INCOMER - 1NOS + 2NOS O/G (Total Qty. 3)
Supply of HT 12KV, 3Phase 50Hz, totally metal clad withdraw able type Vacuum Circuit Breaker INCOMER panel with Copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current, as per IEC 62271-100-200.The switchgear panel shall be of sheet steel construction with not less than 2.5mm thickness for load bearing section and not less than 2 mm thickness for non-load bearing and shall be totally dust and vermin proof.The offered panels shall be tested for IAC level of 25kA/1 Sec., No. of operation of Vacuum Interrupter Bottles (ABB/Siemens/ Schneider only) for better performance: (i) Mechanical life -30,000 , (ii) Rated Current – 10,000 & (iii) Rated Short Circuit Current – 100 nos. - All the main components like VI/ VCB/ Relays/ Meters shall be of same make. Approved Makes: ABB / Siemens / Schneider / L&T. i.e. Original Manufacturer or their authorized Core Componenet Partner. Panel and VCB parameters are as below:
INCOMER
Rated Voltage Level / PF withstand Voltage / Impulse Level - 12KV/ 28kV / 75kVp
Continuous current rating: minimum 630A
Short circuit withstand current: minimum 25KA for 3sec.
One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:
Manually & Motor operated(230V,AC,50Hz) spring charged type, manually and electrically open (electrical – 110 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position.
Cast resin Current transformer 11KV, 125/5-5A, Core1: class1.0, 15VA for 3 phase , Core2: 5P10, 15VA,
Cast resin potential transformer 11KV/V3/110V/V3/110V/3, 50VA, Cl 1.0, Cl 3P and HT Fuse at the primary end and 04 pole MCB of suitable Ratings at the secondary end of the PT (Confirming related IS specifications).
Protection arrangements for the breaker shall comprise of the following:
E/F, O/C, S/C, TCS with MODBUS protocol - Numerical Type Siemens (Siprotec)/ ABB (REF series)/ Schneider (MICOM P111)
Relay should have mimic display
Complete with Master Trip/ Anti pumping relay.
All the Relays shall belong to a common platform and shall be of single make with Electromechanical Relays in Draw-out casing
The following meters, indications and accessories are to be provided with the panel:
Multi-Function Meter (EM6400NG) - 01nos
One set of indicating lamps to indicate OPEN, CLOSE, TRIP, AC, DC, SPRING CHARGED (Spring charging must be Manual & Motorised) - 01nos each
25A TNC (Trip - Neutral - Close) Rotory Switch for Open / Close - 01nos
Emergency Push - 01nos
8 Window Annunciator, Aux. Supply- 24V DC - 1No.
Panel Height shall not be more than 2300mm
OUTGOINGS (02 Nos.)
Rated Voltage Level / PF withstand Voltage / Impulse Level - 12KV/ 28kV / 75kVp
Continuous current rating: minimum 630A
Short circuit withstand current: minimum 25KA for 3sec.
One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:
Manually & Motor operated (230V,AC,50Hz) spring charged type, manually and electrically open (electrical – 110 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position.
Cast resin Current transformer 11KV, 60/5-5A, Core1: class1.0, 15VA for 3 phase , Core2: 5P10, 15VA,
Protection arrangements for the breaker shall comprise of the following:
E/F, O/C, S/C, TCS with MODBUS protocol - Numerical Type Siemens (Siprotec)/ ABB (REF series)/ Schneider (MICOM P111)
Relay should have mimic display
Complete with Master Trip/ Anti pumping relay. (Aux. Relays Alarm / Trip OTI, WTI, Bulcholz, Oil Pressure, Oil Level Low etc.)
All the Relays shall belong to a common platform and shall be of single make with Electromechanical Relays in Draw-out casing
The following meters, indications and accessories are to be provided with the panel:
Multi-Function Meter (EM6400NG) - 01nos
One set of indicating lamps to indicate OPEN, CLOSE, TRIP, AC, DC, SPRING CHARGED (Spring charging must be Manual & Motorised) - 01nos each
25A TNC (Trip - Neutral - Close) Rotory Switch for Open / Close - 01nos
Emergency Push - 01nos
Panel Height shall not be more than 2300mm (Note:- Please refer the SLD of 11KV Switchgear Panel)
BATTERY CHARGER PANEL
Supply of the 20Amp. 24Volt battery charger panel having Boost, float & trickle charge facility with Battery Charging Cabling etc. as required. Battery Charger suitable to charge 110Ah 12Volt Battery for control system of HT panel shall be be Fabricated out of CRCA sheet of 14 / 16 gauge, powder coated including stand for batteries as approved by Engineer in change and as required,
Lead Acid Battery of 110 AH, 12V capacity, 2 Nos.
Boost and Trickle charger suitable for above item.
1 No. AC Voltmeter 0-300 V
1 No. DC Voltmeter 0-30 V
1 No. AC Ammeter 0-10 A
1 No. DC Battery charging position indicator
For DC distribution 3no. DP MCB (out put) and incomer DP MCB of suitable rating
TRANSFORMER AS PER 1S 1180, LEVEL-II
Supply, erection, testing and commissioning of 1000 KVA, 11/0433KV, 3 Phase, 4 Wire, 50 Hz, Vector Group - Dyn11, ONAN, OFF LOAD TAP CHANGER, tappings on HV side Tapping Switch in the range of +5% to -10% in step of 2.5% per step as per Standard IS 2026 and IS 1180 (Part - 1) Level - 2 with cable termination Box on both ends, the No load and full load losses should be as per IS - 1180 Level 2. The Core of the transformer shall be constructed from high grade, non ageing, prime grade, CRGO with M4 grade or better. The core material make shall be Posco / Nippon / Novex / AK Steels. Temperture rise of Oil / Winding Over Design ambient temperature of 50℃ shall be 40/45℃. Transformer shall be filled with 1st Fill (Brand new Oil) of Oil duly Dehydrated and confirming to IS Standards. As per Technical Specifications and complete in all respect required by the Engineer in charge of the site. Makes: Refer List of Makes
Type of Transformer - Indoor type
HT side - Cable Box
LT side - Cable Box
System Voltage - 12kV on HV side
Insulation Level
H.V. Power Frequency (KV rms) - 28kV
H.V. Impluse withstand Voltage (KV Peak) - 75kVp
HT Termination - Ccble Box
LT Termination - Cable Box for Bus Duct
Rating Plate
Rollers
Silica gel breather
Double Float Bulchz Relay with Alarm & Trip Contact
OTI with Alarm & Trip Contact
WTI with Alarm & Trip Contact
OIL Pressure switch with Alarm & Trip Contact
Clear Glass Oil Visible window
Marshalling Box duly wire from all safeties and wiring diagrame
Lifting Hook
Thermometer Pocket
11KV XLPE INSULATED ARMOURED CABLE LOOSE
Supply & laying of Circular Aluminium conductor, conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FRLS PVC inner sheathed, galvanised steel strip armoured and overall FRLS PVC sheathed cable confirming to IS:7098/II/85 working voltage 11KV(UE) grade to be laid loose on the existing pipe, pole, trench, hanged on existing Poles (with support GI wires) or cable tray etc. as required at site of following size:-
Circular Aluminium conductor, conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FRLS PVC inner sheathed, galvanised steel strip armoured and overall FRLS PVC sheathed cable confirming to IS:7098/II/85 working voltage 11KV(UE) grade 185sq.mm (Three Core)
11KV TERMINATION 3C X 185 sq. mm
Supplying and making end termination with heat shrinkable jointing kit complete with all accessories including Lugs suitable for following size 3 core XLPE aluminium conductor cable of 11 KV grade as required.
185 sq. mm (Indoor Type)
185 sq. mm (Outdoor Type)
LT POWER / CONTROL CABLES AND CABLE TRAYS
LT POWER CABLES
XLPE INSULATED ARMOURED CABLES (LOOSE) : Supply & Laying of aluminium conductor XLPE insulated armoured and served cable to be laid loose in the existing trench, cable tray or pipe as per PWD General Specifications 2010 :
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 16 sqmm (4 Core) cable.
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 50 sqmm (3 ½ Core) cable.
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 70 sqmm (3 ½ Core).
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 95 sqmm (3 ½ Core).
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 185 sqmm (3 ½ Core).
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 240 sqmm (3 ½ Core).
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 300 sqmm (3 ½ Core).
Aluminium conductor XLPE insulated armoured and served cable working voltage 1100 volts grade 400 sqmm (3 ½ Core). (Owner will provide the LT Power Cable Schedule and afterthat vendor shall measure the actual Length at site before ordering. Payment shall be made on actual measurement basis only.)
LT COPPER CONTROL CABLES
PVC INSULATED ARMOURED CABLES (LOOSE): Supply & Laying of copper conductor, PVC insulated armoured cables and served cable to be laid loose in the existing trench, cable tray or pipe as per PWD General Specifications 2010 :
3C X 2.5sqmm Cu. Ar. Cable
4C X 2.5sqmm Cu. Ar. Cable
4C X 6.0sqmm Cu. Ar. Cable
12C X 2.5sqmm Cu. Ar. Cable
ALUMINUM THIMBLES S/E of heavy duty Aluminium Thimbles / lugs for cables end terminations duly crimpped including making necessary connections etc.
Thimble for 16 sqmm conductor
Thimble for 25 sqmm conductor
Thimble for 35 sqmm conductor
Thimble for 50 sqmm conductor
Thimble for 70 sqmm conductor
Thimble for 95 sqmm conductor
Thimble for 150 sqmm conductor
Thimble for 185 sqmm conductor
Thimble for 240 sqmm conductor
Thimble for 300 sqmm conductor
Thimble for 400 sqmm conductor (Quantity is tentative, however Actual Quantity shall be derived from LT Power Cable Schedule before ordering.)
COPPER THIMBLES S/E of heavy duty Copper Thimbles / lugs for control cables end terminations duly crimpped including making necessary connections etc..
Thimble 2.5sqmm
END TERMINATION OF XLPE / PVC INSULATED, ALUMINUM/COPPER AR. CABLES S/E of heavy duty brass single compression gland for cable end termination duly complete with checknuts etc. including making necessary connections.
Gland for XLPE Aluminium 1100 volts grade 16 sqmm (4 Core).
Gland for XLPE Aluminium 1100 volts grade 50 sqmm (3 ½ Core).
Gland for XLPE Aluminium 1100 volts grade 70 sqmm (3 ½ Core).
Gland for XLPE Aluminium 1100 volts grade 95 sqmm (3 ½ Core).
Gland for XLPE Aluminium 1100 volts grade 185 sqmm (3 ½ Core).
Gland for XLPE Aluminium 1100 volts grade 240 sqmm (3 ½ Core).
Gland for XLPE Aluminium 1100 volts grade 300 sqmm (3 ½ Core).
Gland for XLPE Aluminium 1100 volts grade 400 sqmm (3 ½ Core).
4C X 2.5 sqmm Cu. Arm. Cable / 3C X 2.5 sqmm Cu. Arm. Cable
12C X 2.5 sqmm Cu. Ar. Cable
4C X 6.0 sqmm Cu. Ar. Cable
Disconnecting/Removing/Re-routing/Re-connection of existing Cables as per reuirements of new MLTP Locations
CABLE TRAY
Supplying and Installing following sizes of perforated Hot Dipped Galvanized Iron Cable Tary (galvanized Thickness not less than 50Micron) with perforations not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders/cable tray supports, including G.I. bolts & nuts, etc. Complete in all respecty as required at site :
450mm X 50mm X 2.0mm Thickness
750mm X 62.5mm X 2.0mm Thickness
900mm X 62.5mm X 2.0mm Thickness (Quantity is tentative, however Actual Quantity shall be measured at site.)
MISCELLANEOUS ITEMS
Supply, fabrication, cutting, welding, jointing of M.S. Steel, including welding rod etc complete in all respect as required by the Engineer - In - Charge at site
Supply, fabrication, cutting, welding, jointing of M.S. Equal Angle of size 75 x 75 X 6mm, Wt. 6.4Kg/Mtr. (As per given design) 110mTR
Supply, fabrication, cutting, welding, jointing of M.S.Channel (C-Channel) Section size 100 x 50mm, wt 9.6Kg/Meter (As per given design), complete in all respect L =20mtrs
Supply, fabrication, cutting, welding, jointing of M.S.Chequer Plate 6mm thick, Wt 45.90Kg/Sq. Meter (As per given design) Including lifting handle etc complete in all respect 30 SQMTRS
Provding & fixing of rubber mat with (Bottom side of mat shall anti skid type) of size 1 Mtr wide X 2 Mtr Long, laid in front and back side of the panels. Thickness of the mat shall be 2.5 mm thick to withstand 11 KV dielectric strength as per IS IS 15652 : 2006, Superseding IS 5424 :1969 Old Standard (colour - Black/Blue) ISI Engraved
Providing of set of 4 Nos. 9.5 Ltrs. Capacity GI bucket painted in post office red colour with prior coat of red oxide paint and written with white paint "FIRE" and mounted on MS angle iron frame with bracket of appropriate size and capacity i/c filling sand etc. (Near DG Set -1Set)
Supply and fixing of safety instruction chart in word duly framed with 5 mm thick glass as required. (Approx. front area 1.20 sq mtrs.)
Supply & fixing shock treatmernt chart duly mounted on a wooden frame with 5 mm thick glass as required. (Approx. front area 1.20 sq mtr)
Providing and fixing 6Kg, Dry ABC powder Fire Extinguisherbearing IS : 2171 marking, fixing to wall including brackets etc. Complete as required. (DG Area & TR Area)
Providing and fixing Mechanical Foam type Fire exitnguisher 9 ltrs. Capacity type, ISI marked with all accessories etc. complete as required. (DG Area)
Providing & fixing Cabon Dioxide fire Exinguisher consisting of MS cylinderical body, squeeze liver discharge valve fitted with internal discharge tube, 30cm long high pressure discharge hose, discharge nozzle, suspension bracket, conforming to IS : 934 finished externally with red enamel paint and fixed to wall with brackets with wral plugs / dash fasteners complete with internal charge of following ratings (CCOE Nagpur Approved Cylinder) in Panel Room.
a.) Capacity 4.5Kg (ISI Marked IS 2878) (Panel room -1no. & VCB Area - 1No and DG Area - 1No)
b.) Capacity 9Kg CO2 Mobile Fire Extinguisher with all accessories like wheeled trolley etc. Complete in all respect as required. (Near Transformer)
Liasoning Work
Installation of 11 KV HT Line
Installation, Testing and Commissioning of 11 KV Sub-Station
Note:i.) CONTRACTOR TO SUBMIT 4 COPIES OF DRAWINGS ON COMPLETION OF WORK LIKE SLD, GA, CONTROL CIRCUIT WIRING, ALL LAYOUT DRGS, TRF. DRAWINGS, VCB DRAWINGS, AS BUILT CABLE SCHEDULE, DG SETS DRAWINGS AND ALL MANUALS OF EQUIPMENTS INCLUDING PHOTOCOPY OF ORIGINAL EQUIPMENT BILLS OR ANY OTHER DOCUMENTS LEFT OVER SAME SHALL BE SUPPLIED TO THE OWNER/ARCHITECTS. ii.) THE CONTRACTOR TO NOTE THAT ALL QUANTITIES ARE TENTATIVE HE MUST CHECK THE QUANTITY HIMSELF BEFORE PLACING THE PURCHASE ORDER SINCE THE RATES ARE ITEM RATE AND WILL BE PAID AS PER ACTUAL WORK COMPLETED AT SITE. iii.) THE CONTRACTOR TO PASTE THE CONTROL DRAWING DULY LAMINATED ON THE INNER SIDE OF RESPECTIVE DOOR/COVER OF THE PANEL. iv.) BIDDER SHALL VISIT SITE IF ANY INFORMATION REQUIRED. NO DEVIATION IS ACCEPTED LATER. v.) BIDDER SHALL STRICTLY FOLLOW THE SLD AND BOM FOR DETAILED SPECIFICATION OF THE REQUIRED EQUIPMENTS.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .