Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹25.7 L
EMD Value
₹26,000
Closing Date
11 Oct 2022, 1:00 pmClosed
SE ETC Mathura
132 KV S/S Aurangabad Mathura
Erection of 63 MVA Transformer and associated works at 220 KV Sub-Station Gokul Under ETD Mathura
2022_UPTCL_721615_2
ET-30/ETC(M)/22-23
Open Tender
Electrical Works
Lump-sum
45 days
Under ETC Mathura
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
EE ETD Mathura
₹26,000
18 Oct 2022
23 Sept 2022
14 Oct 2022
23 Sept 2022
11 Oct 2022
23 Sept 2022
Amount
Construction of 132 KV Transfer Bus bay , 63 MVA Transformer bay ,Erection of 2 Nos capacitor bank
Erection of main and auxiliary structure consisting of columns, beams, peaks, masts etc. and auxiliary structure required for installation of Jack busbar isolators, P.I., CVTs., L.As. and all other equipments. The job consists of shifting of all material i.e. conductor, fittings, structure parts, nuts, bolts, washer etc. from store to site of erection, erection of structure as per relevant drawing and practices using flat and spring washer with each bolt. Matching of holes, cutting, matching of members if required shall also be done by the contractor without any extra cost to complete the work satisfactorily. All material to be erected shall be supplied by UPPTCL free of cost but all men, material and T&P required for satisfactorily completion of work shall be arranged by the contractor at his own cost.
Dismantling of main and auxiliary structure consisting of columns, beams, peaks, masts etc. and auxiliary structure required for installation of Jack busbar isolators, P.I., CVTs., L.As. and all other equipments. The job consists of shifting of all material i.e. conductor, fittings, structure parts, nuts, bolts, washer etc. as per practices. All material to be dismantled shall be shifted to designated place. all men, material and T&P required for satisfactorily completion of work shall be arranged by the contractor at his own cost.
Dismantlingof following equipments as per instruction manual of various equipments and technical specifications including shifting of material/equipments from site to store including all other associated work to complete the job satisfactorily.
132 KV Isolator
33 KV VCB
33 KV Post insulator
33 KV BI/LI
33 KV CT/PT
Erection of following equipments as per instruction manual of various equipments and technical specifications including shifting of material/equipments from store to erection site including all other associated work to complete the job satisfactorily.
132 KV CT and PT junction box
T/F C&R Panel
33 KV VCB
33KV CT Junction Box
Series Reactor for capacitor bank
Capacitor bank C&R Panel
Stringing of various main, Transfer & T/F jack bus of 132 KV/33 KV with different type conductor and different length of span mention below including fitting of tension clamp hoisting of insulators cutting of conductor and also shifting of all material form store to work site and all other associated works required for completion of job satisfactorily as per technical specification.
132 KV Main Bus 3x Tarantulla/Moose (Approx 12 Mtr section)
132 KV Transfer Bus with 3x Zebra (Approx 24 Mtr section)
132/33 KV Jack bus 3x Twin Zebra (Approx 24 Mtr section)
132/33 KV Jack bus 3x Zebra (Approx 24 Mtr section)
Stringing of 33 KV Main bus 3xTwin Zebra(Approx 18 Mtrs section)
Stringing of 3x panther Jack bus (Approx 18 Mtrs section)
Stringing of 33 KV Main bus 3x Zebra (Approx 12 Mtrs section)
Stringing of 33 KV Main bus 3x Zebra through PI (Approx 35 Mtrs section)
Stringing of 33 KV Main bus 3x Twin Zebra through PI (Approx 35 Mtrs section)
Stringing of 132 KV 3x Panther Line from 132 KV Tower to Gantry (Approx 80 mtrs)
Dismantling of Stringing section
Destringing of 132 KV Jack Bus 3xPanther section ( Approx. 24 Mtr)
Destringing of Transfer Bus 3xPanther section ( Approx. 12 Mtr)
Destringing of 33 KV Jack bus(Approx. 18 mtrs)
Destringing of 132 KV 3x Panther Line from 132 KV Tower to Gantry (Approx 80 mtrs)
Making of new jumpers of 132 KV & 33KV C.B., C.T., ,Isolator and LA by the single/Twin Moose/Zebra/Panther conductor with cutting bending and shaping of conductor along with shifting of material from site store to work place.
Dismantling of jumpers of 132KV & 33KV C.B., C.T., ,Isolator and LA by the single/Twin Moose/Zebra/Panther conductor with shifting of material from site to store .
Providing inter connection diagram and cable schedule as per drawing to complete above job including C.B., C.T., Isolator, Panel and Transformer etc.
Laying of following sizes of control cable in the cable trench from control relay panel to various equipments/marshalling boxes/junction box etc. in switchyard as per cable schedule, their saddling at every 750mm distance with M.S. saddles of size 25x3mm size including carriage of cable drums from store to laying site and shifting back the remaining material to store and all other associated work to complete the job satisfactorily as per technical specification.
10x2.5 Sq mm
6x2.5 Sq. mm.
4x2.5 Sq. mm.
2x2.5 Sq. mm.
Termination of following sizes of cable as laid above as per cable schedule including making necessary holes in glands plates or box wherever required. Supply and fixing of cable glands of appropriate size, supply and providing ferrules and Nos. for each core. (The rates of termination of control cable include the all cores of cable at one end with lug)
10x2.5 Sq mm
6x2.5 Sq. mm.
4x2.5 Sq. mm.
2x2.5 Sq. mm.
Cutting, straightening bending & laying 800mm below inside ground and above ground of following size M.S. flat for earthing of main and auxiliary structure, equipment structure etc. including welding with main earthmat and with object to be earthed excavation of trenches, its back filling, painting and all other associated work as required to complete the work satisfactorily excluding the cost of M.S. flat.
To make earthing for L.A. with 06 Nos. Electrode of 03 meter long M.S. round including cutting, welding and making electrode and making a rectangle with 75x10mm M.S. flat inside earth below 0.8mtr. deep including excavation and refilling of soil with T&P and labour etc for completion satisfactorily.
Laying of 40/36 mm size M.S. round bar 600 mm below ground level including cutting, straightening welding, painting of joints with bitumen black Japan paint, excavation of trench, its back filling and all other associated work to complete the work satisfactorily as per drawing and technical specification (excluding the cost of MS bar) work includes providing and fixing of 100 mm long, 50X50X6 mm MS angle (4 Pcs) at each cross joint of earth mat as per direction of supervising engineer to complete the job satisfactorily.
Sorting/counting/stacking erection mark wise and proper loading of GI substation structure (CCR,CGR, ALP, ABL, BCT) etc. in trucks / trailor at EFU Nainy Allahabad and Safe carriage of loaded structure from EFU Nainy Allahabad to 220 KV S/S Gokul Under ETD Mathura. App. 600 Km and Unloading of carriage structure from the trucks/trailor at 220 KV S/S Gokul Under ETD Mathura. Its sorting, counting and proper stacking at the S/S premises as per direction of supervisory engineer to complete the job satisfactorily (Appr. weight of 24 MT)
Dismantling of 33 KV complete capacitor bank series reactor 04 Nos., NCT-02 Nos, capacitor bank cells with structure & Opening of copper bonds. . Shifting dismantled structure and equipment and other material from site to store/designated place within S/S boundary and other associated work to complete the job satisfactorily as per direction of supervising engineer.
Erection of capacitor bank unit (1X5 MVAR) by erecting of its structure with the help of post insulators, Nut and bolts and then fixing of cells properly and jumpering between each cells and all other associated works required for completion of job satisfactorily as per direction of supervising engineer.
Preparation of Inter connection diagram and cable schedule as per drawing to complete the job of cable termination of capacitor bank completely
Providing and fixing of retro reflective sign board of size 3ftx2ft made out of 2mm thick aluminum sheet, face to fully covered with 3M DG cube retro reflective sheet of green colour. The letters and symbols shall be computer cut and in white colour. Board is to be supplied along with the back support from of size 35x35x5mm & two legs for grouting. Backside of aluminum sheet shall be painted with stove enamel black paint for new 63 MVA, 132/33KV Transformer-I. Language for writing will be provided by the department (UPPTCL).
Fabrication of hut type fire bucket stand made of MS angle of size 40x40x6 mm and ISI mark MS roofing sheet, having arrangment for hanging 10 buckets. All the metal surfaces should be painted with one coat of red oxide and two coats of first quality post office red synthetic enamel paint of Asian Paints/Nerolac/Berger. " FIRE" in 25 cm should be written in white color on the top of the both side of roof after painting in red colour. All the material including MS angle shall be provided by the contractor at his own cost.
Providing fire buckets of 9 ltr capacity as per IS 2546, buckets should be painted inside by white and outside by post office red colour; ear and handle by black color with two coats of first quality synthetic enamel paint after one coat of red oxide, from Asian Paints/Nerolac/Berger. "FIRE" and "avkx" in 10 cm font in white color should be written on opposite sides of buckets. All the material shall be provided by the contractor at his own cost.
Providing and fixing of digitally printed glow sign board of Single Line Diagram of 220 KV S/S Gokul of size 6'x4' made of minimum 2 mm thick milky acrylic sheet and frame of 28 SWG G.I. Sheet having depth 150mm with 05 Nos. 20W, 230V, day light LED batten tube light fitted inside for glowing the board. Complete wiring should be of 0.75 mm² ISI mark copper wire with 3 mtr connecting cable of same standard including 3 pin ISI mark plug point.
Erection and Comissioning of 63 MVA Transformer
Shifting of main tank of 63 MVA,132/33 KV transformer from unloading place to the plinth distance about 20 meter including turning of tank, if required , including all T&P and all other works required to complete the job satisfactorily.
Additional shifting of approx. 5 Mtrs or part thereof. if any.
Draining out fresh transformer Oil from 209 Ltr. drums to 20 KL tank. (App. 29 Drums)
Centrifuging of transformer oil in 20 KL storage tank for 72 hours by 10 KL/Hour capacity centrifuging machine, to be arranged by the contractor alongwith operator and taking the B.D.V values of the oil periodically till the required value is achieved as per direction of supervising engineer.
Complete erection of 63 MVA capacity transformer by erection of radiators conservator tanks, all bushing, turrets, connecting oil pipe lines, cooling fans, motor drive mechanism of tap changer, RTCC panel, etc to complete the job satisfactory.
Erection of 63 MVA T/F, 132/33 KV 'RTCC' Panel
Filling of approximate 06 KL fresh centrifuged transformer oil in 63 MVA T/F after complete errection of transformer as per direction of supervising engineer.
Centrifuging of transformer oil in transformer main tank for 72 hours by 10 KL/Hour capacity centrifuging machine, to be arranged by the contractor alongwith operator and taking the B.D.V values of the oil periodically till the required value is achieved as per direction of supervising engineer.
Earthing of 63 MVA T/F HV and LV Neutrals, Body, Marshaling box, Drive mechanism etc. with 75X10/50X6 MS flat (To be provided by department) including, bending, cutting & welding etc.
Delta earthing for 63 MVA T/F after fabrication of delta set with 3 nos. 40mm/36mm dia size 3 mtrs. long electrodes their placing inside the ground at distance of 3 Mtr. to each other in delta pettern and connecting all the three electrodes with 75x10mm MS flat 700mm deep and connecting the delta with T/F HV and LV neutral seprately with the help of 75x10 mm MS flat. (M.S flat and M.S rod will be arranged by the Department).
Extension of Mulsifire system with Supply & erection of high velocity automatic water spraying system on 63 MVA, 132/33.KV Transformer including all materials and other associated works i.e. fabrication of rings of air and water of G.I. Pipe with follwing size pipe along with its elbow. tee sockets. flnngs and bends etc. including cutting, welding for fixing of air deterctor & water sprankles.
25mm dia
65mm dia
80mm dia
Installation of Deluge valve with all accessories of 150mm dia
Supply, installation and commission of high pressure Nozzle projector
Supply installation and commissioning of Q.B. detector
Supply erection of Pylon support and laying of underground M.S. pipe line as pr spech. Comlete with elbow,Tee, sockets, flanges ets, with anti-corrosive treatment with all material labour etc.
25mm dia
150mm dia
Fabricationand ereciton of M.S. angle of size 50x50x6 mm on Pylon supports for holding the air& water ring including cutting. Welding & clamping with 'U' bolt & including all associated works with all required material, labour & T&P.
Casting of pylon foundation in 1:2:4 concrete mixture size 500x500x1000mm with 16x450mm foundation bolt 4 Nos including cost of all material i.e. cement, sand 20mm stone ballast & foundation bolt skilled & unskilled labour etc for satisfactory camp of work.
Providing of Pressure switch
Providing of Pressure gauge
Providing of 150mm dia 'Y' strainer
Providing of 150mm dia gate valve
Painting of complete water ring/line Air Ring/line and Pylon support after cleaning pipe with one coat of red oxide and two coat synthetic enameted paint i.e. Air Ring Blue colour, water ring P.O. Red and Pylon supports Green colour for satisfactory completion of work.
Providing, fixing, testing and commissioning of follwing size dia gate valve with accessories
80mm dia
25mm dia
Providing, Fixing, testing and commissioning of 80mm dia fire hydrant valve with accessories made of brass (seat and spindle) and body cast iron for 80mm dia MS pipe.
Providing and fixing fire hydrant box and front door glass with proper locking arrangement.
Making of C.C. floor with 1:2:4 ratio of size 2.0x1.0x0.5(LxBxH)mtr. For fire hydrant.
Painting of complete 80mm MS hydrent pipe with 2 coat of synthetic enameled paint red colour for MS Pipe after one coat of red oxide.
Casting of plinth above ground lavel 300mm and blow ground lavel 300mm size 250x250mm² with cement coarse sand and concreteas as per instructions of supervising engineer for supporting 150mm main water line, 25mm air line & 80mm hydrant pipe.
Providing and fixing new generation energy saving and enviournemnt friendly long life versatile pressure die cast aluminium out door high beam flood light with high power 120W LEDs as light source and exclusively design poly carbonate cover satisfying IP65 standard alongwith electronic driver and complete fitting including GI pipe, clamp for round pole or GI structure, suitable for 220 V AC supply make CGL/Havells/Philips and Providing and fixing of junction box of 16 SWG MS sheet duly painted having size 150x150x200mm for above light on bottom of main structure or pole with the help of clamps junction box contain 01 No., 6Amp single pole MCB (L&T/Havells/Schneider make), 01 No. link and cable gland etc. as per specification and Laying, dressing and termination of contorl cable for the light with the help of clamps vertically on the gentry and all other associated to complete the work.
For Supply
Supply of Bolted type bus bar tension fitting suitable for Tarantulla conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase type turn buckle in all respect.
Supply of Bolted type bus bar tension fitting suitable for Zebra conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase type turn buckle in all respect.
Supply of Bolted type bus bar tension fitting suitable for ACSR Panther conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase type turn buckle in all respect.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Panther to Panther conductor.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Zebra to Panther conductor.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Zebra to Zebra conductor.
Supply of 145 KV Post Insulator clamp made of LM-6 alloy along with Nut, Bolt & washer suitable for Twin Zebra conductor.
Supply of 145 KV Post Insulator clamp made of LM-6 alloy along with Nut, Bolt & washer suitable for Panther conductor.
Supply of 33 KV Isolator clamp for Twin Zebra conductor with nut, bolt & washer.
Supply of 33 KV Isolator clamp for Twin Panther conductor with nut, bolt & washer.
Supply of 33 KV CT Clamp made of LM-6 alloy alongwith nut, bolts & washer suitable for2000/1 Amp. CT for Twin Zebra conductor.
Supply of 33 KV CT Clamp made of LM-6 alloy alongwith nut, bolts & washer suitable for2000/1 Amp. CT for Twin Panther conductor.
Supply of 33 KV V.C.B. clamp for Twin Zebra conductor with nut, bolt & washer.
Supply of 33 KV V.C.B. clamp for Twin Panther conductor with nut, bolt & washer.
Supply of tinned copper bond size 15x550mm long made of 12mm multi stranded rope type 450mm long should be joined together and cramped with copper lug (20mm hole) on both ends as per sample
Supply of 33 KV spacer 150 mm for twin Zebra conductor made of LM-6 aluminum alloy both side connecting for 33 KV with 12mm dia HDG nut, bolt & washer as per technical specification.
Supply of Earthing/Discharge rod of first class insulation for system voltage upto 400 KV having total height as 7200mm (24’) one set consisting following items. (a) Earthing pole 6.5Mtr. long in four pieces made of epoxy bonded glass fiber. (b) Earthing cable 12mtr. long with transparent PVC insulated 12 mm2 dia flexiblity copper wire fitted with line end earthing clamp of all alloy suitable for 4” IPS tube Moose/Zebra conductor. (c) Canvas carry bag for above.
Transformer oil sample collection testing of transformer oil at CPRI/ERDA Lab Sonipath & furnishing test report for a- Dissolve Gas Analysis test -01 Nos b- Breakdown Voltage Test - 01 Nos c- Water Content Test- 01 Nos
SHILPA ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .