Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.9 LAccepted-AOC 141 1 ARYAPALLY NORTH BARANILPUR PURBA BARDHAMAN | BARANILPUR | PURBA BARDHAMAN | WEST BENGAL | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹10.9 L+₹1.0 L (10.4%)Rejected-AOC | L2 | Rejected-AOC Being L2 | |
| 3 | L3₹12.5 L+₹2.6 L (26.5%)Rejected-Finance | L3 | Rejected-Finance BeingL3 |
Tender Value
Refer Docs
EMD Value
₹20,000
Closing Date
2 Jul 2025, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, Bardhaman Electrical Division,
Purta Bhavan, 1st Floor, Purba Bardhaman
Renovation of Electrical Works including Installation of RAC and UPS For Labour Room With one Antenatal and One Post Natal Room in Ground Floor 100 Bed COVID Hospital at Srirampur RH, Purbasthali, Purba Bardhaman
2025_WBPWD_867145_1
WBPWD/EEBED/NIQ-05/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Purba Bardhaman
Please refer Tender documents.
4 documents required · 4 mandatory
₹20,000
7 Aug 2025
19 Jun 2025
4 Jul 2025
19 Jun 2025
2 Jul 2025
19 Jun 2025
Amount
Part A---Electrical Installation Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment 6way with inbuild1 no. 415V 80 A. FP Isolator and 18 nos 240 V 6-32 A. SP MCB as required.(D-10/14,D-5/6,D-6/7)(Make:-Legrand/Siemens/ABB Itus)
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. 2+10 way inbuild with 1 no. 240 V 40 A. DP MCB Isolator and 10 nos. 240 V 6-32 A. SP MCB as required.(D-10/13)(D-5/6)(D-6/7)(Make:-Legrand/Siemens/ABB Itus)
Supply & Delivery of 1.1KV grade 4 core 35 sqmm XLPE insulated Armoured Alluminium cable with Extruded PVC Type ST2 Outer Sheathed As Per IS-7098 (Part 1) 2011. [Make - Polycab/Havells/RR Kabel/Gloster] (From main panel 63A spare MS to 6way PBDB )
Laying of cable upto 3/4 core 35 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2x10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. (F-1/2C)
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below (F-4/7C) i)3/4 core 35 sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials (F-5/8B/XV) i)3/4 core 35 sqmm
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Make - Polycab/Havells/RR Kabel/Gloster) partly in 20mm size PVC rigid conduit 'FR' (Precision mms make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] (E-15/5C)--Average run 8 mtr
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make - Polycab/Havells/RR Kabel/Gloster) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 5A 3 pin plug point incl. S&F 240 V 5A 3 pin flush type plug socket & piano key type switch (Anchor make) incl. S&F earth continuity wire, fixed on sheet metal (16 SWG) switch board with bakelite/perspex (wall matching colour) top cover (3 mm thick) flushed in wall incl. mending good damages to original finish point 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC (E-10/4a) On Board
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make - Polycab/Havells/RR Kabel/Gloster) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required.( E-9/C-1) 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC (From existing HTPN DB/SPN DB to 15A/Computer Socket)
2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC (For AC machine & OT Board )
2x80/0.4 (10 sqmm) + 1x84/0.3 (6 sqmm) as ECC(PBDB to UPS toSPNDB)
3 x 22/0.3 (1.5 sqmm)(Extra wiring)
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., includingsupplying sockets, tapes.(F-5/9) I)2.5 Sqmm
ii)4 sqmm
iii)6 sqmm
iv)10 sqnm
Supplying and fixing PVC Rigid Conduit 'FR' [Precision MMS Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works E16/7a 20mm size(If required)
Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator & 20A switch type SP MCB (Anchor make) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.(E-7/26)
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Anchor make) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.(Power Soket for single phase small type auto-clave) E-6/22
Supply & Fixing 240 V, 4 nos. 20A plug socket with separate 4 nos. 20A Piano key type switch, indicator & 16A kit-kat flush type fuse (Anchor make) on sheet metal switch board embedded in wall incl. S & F300x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick byBrass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required(E-8/31)
S&F 230 V. 32 A Industrial Plug & socket Board with 240 V, 32Amp SPN & Earth Metal Industrial Plug socket & 32A Industrial top incl. S&F 32 A DP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and necessary conection for UPS as per GS. (Legrand Type TEMPRA PRO INTERLOCKED(056669) similar type of ABB/LK)
S&F 230 V. 9 W LED cool day bulb with B22Base (Philips Make)
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket, on S&F 2 Module PVC Modular type switch board (all Mk. Legrand Myrius / Anchor Roma / Schneider / Cabtree) after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. (E19/16)
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (all Mk. Legrand Myrius / Anchor Roma / Schneider / Cabtree) & necy. Connections. (E-17/5b)
Supply & Fixing 240 V, 25 A, Modular type starter with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate (all Mk. Legrand Myrus / Anchor Roma / Schneider / Cabtree) flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (E19/17)
S&F timer box made of 16 SWG MS Sheet, Powder Coated Painted (Siemens Grey) consisting with 1 no. 230 V. 32 A. DP MCB, 1 no. 32 A. 3 pole Power contactor, 1 no. toggle switch, 1 no. analog timer clock, Inditating lamps, 2 nos. connectors etc. (Mk. L&T / Siemens / ABB) incl. suitable size of interconnecting wire (power line by 6 sq.mm. wire, control circuit by 1.5 sq.mm., indicating circuit by 1.5 sq.mm. Mk. Havell's / Gloster / Polycab) as reqd. as per GS. [For AC]
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts.long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & 15 mm dia GI pipe protection (1 Mts. long) to be filled with partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:(G-1,2a) By TATA-Medium GI pipe
Excavation of soft soil for installation of Earth Electrode and filling & ramming. (G1/1a)
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. (G2/4a)
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damage No. 10 SWG(G-2/5/iv)
Supply and delivery of LED Tube Double Fittings, Make- Philips, cat no.- TMC 502 P 2xT-LED 22W P3241 incl. 2x 18/20 Watt Polycarbonate Body with inbuilt driver and Metal Heat Sink having length 1200mm, T8, Iumen Output - Min. 2100 Lumen. Make : Philips / Crompton / Wipro) bottom cover of the fittings should be screwed at both ends. Fittings having warranty at least 03 (Three) years.
Part B--- SITC of RAC :- Supply ,Installation ,Testing & Commissioning of Split type AC machine having colling capacity range (6.6KW-7.0KW),With variable speed rotary compressor ,refrigerant gas R32/R410 BBE star rating-3(EER range 3.5 to 3.99),Air flow range CFM(780-850), P2 capcitor, Indoor and outdoor PCB should be in metal enclosure both condencer and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391(Part-i &Part-II)with all amendments(Make:-Mitsubishi Electric/O General/ Mitsubishi Heavy)
Supply ,Installation ,Testing & Commissioning of Split type AC machine having colling capacity range (5.2KW-5.3KW),With variable speed rotary compressor ,refrigerant gas R32/R410 BBE star rating-3(EER range 3.1 to 3.09),Air flow range CFM(560-600), P2 capcitor, Indoor and outdoor PCB should be in metal enclosure both condencer and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391(Part-i &Part-II)with all amendments(Make:-Mitsubishi Electric/O General/Mitsubishi Heavy)
Supply, installation, testing & commissioning of copper refrigeration pipe line for liquid and Suction line including vaccumiazation and Nitrogen of testing of following nominal size of soft/ hard drawn copper refrigerent piping for Split AC system, complete with fittings with adjustable ring type hanger supports, jointing/ brazing including accessories, insulated with XLPE class - O tubular insulation/ with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 9mm. thickness for suction and liquid lines, all accessories as per specification etc. as required & as per direction of EIC with proper mending good damages to original finish. Mk. of Cu pipe - Rajco/ Ryoku/ Mandev/ Nippon Mk. of Nitrile Rubber Insulation - Aeroflex/ K-flex/ Accroflex/ Armacell. (a) 15.88 mm (5/8) O.D. (Thickness : 1mm) (Insulation : 9 mm) & (b) 6.4 mm O.D (1/4). (Thickness : 0.8mm) (Insulation : 9 mm)
Supply and Laying of 4 core 2.5 sq.mm 1.1 KV grade unsheathed FR Cu cable with gas line as per direction of EIC for Indoor to Outdoor communication for Split type AC m/c.(Make - Polycab/Havells/RR Kabel/Gloster)
S/L of 3core 4 sq.mm 1.1 KV grade unsheathed "FR" Cu cable with gas line as per direction of EIC for Indoor to Outdoor Communication for Split type AC m/c.(Make - Polycab/Havells/RR Kabel/ Gloster)
Supply & laying Soft Drawn heavy duty braided hose PVC Pipe 19mm dia for water drain with proper supports & brackets as per direction EIC. (Make: Suprime/Oriplast as per approved by EIC)
Part-C SITC of UPS : Technical Specification for 6 KVA online UPS Single phase input & Single phase out put. (Allocation--1nos UPS Labour Room ) Topology, IGBT BASED DSP CONTROLED Rating of UPS(KVA/KW): 6 KVA / 4.8 KW (Make: APC-SRCE6KUXI/Emerson, NUMERIC/Switching AVO-- as per Direction of EIC) Nominal Input Voltage: 230V Input Frequency: 40- to 70Hz. Input Voltage : 100-285V ( Outpot derated lineraly to 50% of UPSCapacity @ <160V) Isolation Transformer: Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided at output Back feed Protection: UPS should have back feed protection Charging: Autometic float cum Boots Charging Capability with setteble flote & boost charging voltages and current levels and boots charger timer Nominal Output Voltage: 230V Other programble Voltage: 230 V/240V Output Voltage Regulation: Static Variation +/- 1% and Dynamic variation +/-3% Output Frequency: 50 Hz +/- 0.1% Waveform: Pure Sine Wave Output Power Factor: 0.98 Crest Factor: 3:1 THDu: < 2% (linear load), < 5%(non linear load) Birdge: Microprocessor based and IGBT Technology
Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 30 sec Bypass Type: Internal Static bypass( Autometic & manual) Maximum Bypass current: 40A Bypass input voltage range :170V-270V Static By Pass: 100 % rated static switches with fuse protection overload on Bypass: 100% for 10 ms Overall Efficiency: 92% Charger Power / Current:1500W/6.5A Maximum Battery Bank Voltage:192V Battery : 12 V, Mono Block batteries. SMF VRLA DC Bus : Minimum 192V or above, 90 min back up required (Minimum 19200VAH) Battery. Battery Make: Exide/Amar Raja(Quanta) Protection: Multi Protection-Over Temperature Protection with 8 Sensors, Overload, Battery Under Voltage, Fan Failures ,Short Circuit. Four Circuit Breakers, Providing Full Protection When Fault, Strong Overload Capability. Surge Protector at Panel Input & EB Input. PV Reverse Polarity, Input Low & High Voltage, Output Low & High Voltage cut off. Glass cartridge Fuse on Control Circuits MCB at Input Panel, Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip Metering: Graphical LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current
Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch .Termination: Input, Battery, Output & Bypass Enclosure: IP 20 Operating Temp: 0 to 40 Deg C Humidity: Upto 95% Rh (non-condensing) Cooling: Forced Air Noise: < 55 dB Cold Start : Provided Battary Rack: With power coated MS angle with suiteble dimention and gadge.Useing Nyvin cable with proper rating for interlink cables and battery input and necessary accessories. CE Certification:IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture) ISO 9001: 2015, ISO 14001: 2015, ISO 45001:2018,ISO 50001;2018 , ISO:20000-1:2011,ISO:27001:2013, ROHS Warranty:One Year on UPS & two yers on batteries on site against any Manufacturing defects
Rates to be quoted will be inclusive of all the taxes incl. GST. No other additional charges will be applicable in addition to the quoted rates.
DELTA BROTHERS (BID ID -6646082)
M/S KALIMATA ENTERPRISE (BID ID -6644635)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .