Capital (Works)
PND WORKS
12 conditions · 1 needing a document upload
No Technical & Financial eligibility criteria are required for the work costing upto 50 Lakhs but recent documents should be submitted in evidence of tenderer's capacity to carry out the work efficiently and of sound financial capacity. In addition, the tenderer should submit Electrical Contractor license, recent Income tax Return clearance, pan card, GST registration certificate & the tenderers shall submit a self- declarationas per tender condition etc. Note: Non-Submission of Valid Electrical Contractor License, Recent Income Tax Return Clearance or Balance sheet, GST Registration Certificate, PAN Card by the Bidder shall result in summarily rejection of his/their bid.The firm may submit work experience certificate related to electrical works, Bank Mandate form, cancelled cheque, EPF, ESI, Trade License, etc (If available).The tenderer shall have submitted an undertaking that he is not blacklisted or debarred by Railways or any other Ministry/Department of Govt. of India from participation in tender on the date of opening of bids, either in individual capacity or as a member of the partnership firm or JV in which he was/is a partner/member (Format in Annexure-VA). Concealment/wrong information in regard to above shall make the contract liable for determination under Clause 62 of the General Conditions of Contract.
I/we the tenderer (s) am/are signing this document after carefully reading the contents.
I/We the tenderer(s) also accept all the conditions of the tender and have signed all the pages in confirmation thereof.
I/we hereby declare that I/we have downloaded the tender documents from Indian Railway website www.ireps.gov.in . I/we have verified the content of the document from the website and there is no addition, no deletion or no alteration to the content of the tender document. In case of any discrepancy noticed at any stage i.e. evaluation of tenders, execution of work or final payment of the contract, the master copy available with the railway Administration shall be final and binding upon me/us.
I/we declare and certify that I/we have not made any misleading or false representation in the forms, statements and attachments in proof of the qualification requirements.
I/We also understand that my/our offer will be evaluated based on the documents/credentials submitted along with the offer and same shall be binding upon me/us.
I/We declare that the information and documents submitted along with the tender by me/us are correct and I/we are fully responsible for the correctness of the information and documents, submitted by us.
I/we certify that I/we the tenderer(s) is/are not blacklisted or debarred by Railways or any other Ministry / Department of Govt. of India from participation in tender on the date of submission of bids, either in individual capacity or as a HUF/ member of the partnership firm/LLP/JV/Society/Trust.
I/we understand that if the contents of the certificate submitted by us are found to be forged/false at any time during process for evaluation of tenders, it shall lead to forfeiture of the Bid Security and may also lead to any other action provided in the contract including banning of business for a period of upto two year. Further, I/we and all my/our constituents understand that my/our offer shall be summarily rejected.
I/we also understand that if the contents of the certificate submitted by us are found to be false/forged at any time after the award of the contract, it will lead to termination of the contract, along with forfeiture of Bid Security/Security Deposit and Performance guarantee and may also lead to any other action provided in the contract including banning of business for a period of upto two year.
I/We have read the clause regarding restriction on procurement from a bidder of a country which shares a land border with India and certify that I am/We are not from such a country or, if from such a country, have been registered with the competent Authority. I/We hereby certify that I/we fulfil all the requirements in this regard and am/are eligible to be considered (evidence of valid registration by the competent authority is enclosed)
6 conditions · 4 needing a document upload
GST registration certificate along with its supportive documents as per GCC 2022 or its latest amendments must be summitted by the firm. Note:- Non-submission of this document by the bidder shall result in summarily rejection of his/their bid.
Recent Income Tax Return clearance 'OR' Balance sheet must be submitted by the firm. Note:- Non-submission of this document by the bidder shall result in summarily rejection of his/their bid.
PAN Card must be submitted by the firm. Note:- Non-submission of this document by the bidder shall result in summarily rejection of his/their bid.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
GCC 2022 and its all amendments from Railway Board will be followed in this work.
Renovation of old and new filter house including replacement of various valves and media for electrical (G) works under the jurisdiction of Dy.CEE/G/KPA.
KPA-EG-OT-01-26-27
KPA-EG-OT-01-26-27
Open
Works - General
12 Months
North 24 Parganas, West Bengal
₹0
₹43,300
18 Aug 2026
25 Jul 2026
4 Aug 2026
61 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 21,62,941.38 | ||
| — | — | — | 4,029.28 | ||
| Supply, erection, testing and commissioning of LT XLPE cable gland with aluminium sockets / lugs (4 Nos.) suitable for LT 4 core 16-35 sq.mm XLPE insulated aluminum conductor armoured cable. | — | 16.00 | — | — | |
| — | — | — | 9,362.92 | ||
| Supply, erection, testing and commissioning of LT XLPE cable gland with aluminium sockets / lugs (4 Nos.) suitable for LT 4 core 50-95 sq.mm XLPE insulated aluminum conductor armoured cable. | — | 28.00 | — | — | |
| — | — | — | 2,03,256 | ||
| Supply & laying of 80mm or above nominal bore (dia.) heavy duty GI pipe/tube conforming to IS:1239 (Part-1) of latest amendment in underground by cutting trench in road / wall / platform / surface / across the Railway track or recessing in wall / platform / along the Railway track etc. with making good of damages after laying of pipe (GI pipe make: as per Annexure-I) | — | Breakup | for details. | — | |
| — | — | — | 6,775.4 | ||
| Laying of cable through the trench, GI pipe, HDPE pipe, PVC pipe, cable tray, cable duct, wall surface etc. as per IS:1255 of latest amendmend with making good of damages after laying of cable and connection with switchgears along with necessary materials as required. N.B: only cable will be supplied by Rlys, all other materials required during execution of work and connection are to be supplied by the firm. | — | 380.00 | — | — | |
| — | — | — | 39,866 | ||
| Laying, jointing, connection, testing & commissioning of LT cable 1100V grade of sizes upto 95 sq.mm along the wall by necessary clamping arrangement including socketing and termination with epoxy end jointing where necessary. Clamps should be made from 50mm x 6mm MS flat.N.B: Only cable will be supplied by Rly, all other materials required during execution of work and connection to be supplied by firm. | — | 620.00 | — | — | |
| — | — | — | 6,200 | ||
| Supply of indoor type LED Tube light, T-5, 4 ft. length, 18-22W, Retrofit type, SMD LED chip, life span of LED >/= 50,000 burning hours, CRI >/= 70, system efficacy >/= 100 Lm/W, color temperature: 6500 ± 500K (cool white), PF >/= 0.9, IP 20 (or better) suitable for 220-230V AC, 50Hz power supply. (make as per Annexure-I) | — | 25.00 | — | — | |
| — | — | — | 2,625.5 | ||
| Supply of batten suitable for 1 No. LED tube light of 4 feet long, both side holder, without ballast and starter with internal copper wiring. | — | 25.00 | — | — | |
| — | — | — | 3,950 | ||
| Fixing, connection, testing and commissioning of LED tube light fittings with batten for indoor use with suitable size GI clamps and GI nut-bolts and PVC insulated twin copper flexible cord as connected lead including old fittings to be removed, if any required. (N.B: All materials required during execution of the work and connections are to be supplied by the firm). | — | 25.00 | — | — | |
| — | — | — | 9,011.49 | ||
| Supply of wall bracket fan of 400mm sweep suitable for single phase 220-230V, 50Hz power supply including all accessories (make as per Annexure-I). | — | 3.00 | — | — | |
| — | — | — | 1,029.6 | ||
| Installation, connection, testing and commissioning of wall bracket fan by suitable size GI clamps, GI nut-bolts etc. including PVC insulated twin copper flexible cord as connected lead and necessary masonry works. (N.B.: All materials required for execution of the work and connection are to be supplied by the firm) | — | 3.00 | — | — | |
| — | — | — | 17,525.7 | ||
| Supply, installation, testing & commissioning of 6 [i.e. 2+4] way double door powder coated SPN DB with copper busbar, IP43 or better protected and consisting of (i) SPN/DP MCB of 40- 63A, 10kA (minimum) breaking capacity - 1 No., (ii) SP MCB of 6-32A, 10kA (minimum) breaking capacity - 4 Nos. with neutral link, earth bar, DIN rail and all other accessories (Make: as per Annexure-I). N.B. Ratings of MCBs will be decided by Rly. Authority. | — | Breakup | for details. | — | |
| — | — | — | 9,283.16 | ||
| Supply, installation, testing & commissioning of 8 [i.e. 2+6] way double door powder coated SPN DB with copper busba, IP43 or better protected and consisting of (i) SPN/DP MCB of 40- 63A, 10kA (minimum) breaking capacity - 1 No., (ii) SP MCB of 6-32A, 10kA (minimum) breaking capacity - 6 Nos. with neutral link, earth bar, DIN rail and all other accessories (make: as per Annexure-I). N.B. Ratings of MCBs will be decided by Rly. authority. | — | Breakup | for details. | — | |
| — | — | — | 30,160.68 | ||
| Supply, installation, testing and commissioning of 4 way double door powder coated TPN DB with copper busbar, IP43 or better protected and consisting of (i) Four pole MCCB of 100A, 415V, 25kA (minimum) breaking capacity - 01 No., (ii) Four pole MCB of 63A, 415V, 10kA (minimum) breaking capacity - 1 No., (iii) SP MCB of 40A, 10kA (minimum) breaking capacity - 8 Nos., with neutral link, DIN rail and all other accessories (make as per Annexure-I) | — | Breakup | for details. | — | |
| — | — | — | 22,518.98 | ||
| Supply, installation, testing and commissioning of 4 way powder coated TPN DB with copper busbar consisting of (i) Four pole MCCB of 100A, 415V, 25kA (minimum) breaking capacity - 01 No., (ii) SP MCB of 40-63A, 10kA (minimum) breaking capacity - 12 Nos., with neutral link, DIN rail and all other accessories (make as per Annexure-I). N.B. Ratings of MCBs will be decided by Rly. authority. | — | Breakup | for details. | — | |
| — | — | — | 1,236.6 | ||
| Supply, installation, testing & commissioning of 6A plug-socket point with 6A modular type switch, 6A, 3 pin (minimum) modular type socket, PVC board / cover, suitable size GI/PVC box (if required) as per advice of the competent authority & all other required accessories including internal wiring (make as per Annexure-I). | — | 6.00 | — | — | |
| — | — | — | 437.52 | ||
| Supply, installation, testing & commissioning of 16A plug-socket point with 16A modular type switch, 16A, 3 pin (minimum) modular type socket, modular indication lamp, modular fuse with PVC board / cover in suitable size GI/PVC box as per advice of the competent authority in a separate board & all other required accessories including internal wiring (make as per Annexure-I). | — | 2.00 | — | — | |
| — | — | — | 11,479.76 | ||
| Supply, erection, testing & commissioning of multi-plug point with modular type switches, sockets, PVC board, suitable size GI/PVC box as per advice of the competent authority consisting of the followings & all other required accessories with internal wiring: (i) 6A switch - 03 Nos., (ii) 6A, 3 pin (minimum) plug-socket - 03 Nos., (iii) 16A switch - 01 No., (iv) 16A, 3 pin (minimum) plug-socket - 01 No., (v) 16A MCB - 01 No., and (vi) LED indicator - 01 No. (make as per Annexure-I). | — | 8.00 | — | — | |
| — | — | — | 3,089.94 | ||
| Installation, connection, testing and commissioning of LED street/girder light of different capacity including all accessories and old fittings are to be removed, if any. (N.B: All materials required during execution of work and connection are to be supplied by the firm.) | — | 14.00 | — | — | |
| — | — | — | 50,731.38 | ||
| Supply of 60W (or less) LED luminaries in pressure die casted aluminium alloy housing having higher thermal conductivity and corrosion resistant powder coated body with transparent toughened glass cover (thickness >/= 4mm), SMD LED chip as per LM80, photo- biological safety (exempt group), CRI >/= 70, luminous flux (total lumen) >/= 6,000 Lm, system efficacy >/= 100 Lm/W, color temperature: 5,000-6,500K, PF >/= 0.90, life span of LED >/= 50,000 burning hours, IP 66 or better, BIS CRS compliant, having inbuilt protection against short-circuit, overload, over-voltage, reverse-polarity etc. works on 220-230V AC, 50Hz power supply with accessories suitable for street / girder lighting. | — | 14.00 | — | — | |
| — | — | — | 6,041.28 | ||
| Supply, fixing & commissioning of MS pipe of 40/50mm dia. (nominal bore), 3 feet long bend type with suitable MS clamp (Two pair), nuts, bolts & washer for fixing of MS pipe for street / girder lights. | — | Breakup | for details. | — | |
| — | — | — | 37,410 | ||
| Wiring of main / sub-main line in casing-capping / conduit with 02 Nos. 6 sq.mm (for phase and neutral) and 01 No. 2.5 sq.mm (for ECC) copper wire in suitable size heavy gauge inflammable PVC conduit / casing including all other accessories with dismantling of existing wiring, if any, and making good of wall / ceiling surface as its original condition. Copper wire shall be PVC insulated multi-strand single core FR/ZHFR/FRLSH 1100V grade conforming to IS:694 of latest amendment. N.B.: Main/sub-main wiring shall be measured on linear basis along the run of the wiring. The measurement shall include all lengths from end to end of conduit or channel as the case may be, exclusive of interconnections inside the switchboard (make as per Annexure-I). | — | 200.00 | — | — | |
| — | — | — | 75,053.75 | ||
| Wiring of main / sub-main line in casing-capping / conduit with 02 Nos. 4 sq.mm (for phase and neutral) and 01 No. 1.5 sq.mm (for ECC) copper wire in suitable size heavy gauge inflammable PVC conduit / casing including all other accessories with dismantling of existing wiring, if any, and making good of wall / ceiling surface as its original condition. Copper wire shall be PVC insulated multi-strand single core FR/ZHFR/FRLSH 1100V grade conforming to IS:694 of latest amendment. N.B: Main/sub-main wiring shall be measured on linear basis along the run of the wiring. The measurement shall include all lengths from end to end of conduit or channel as the case may be, exclusive of interconnections inside the switchboard (make as per Annexure-I). | — | 485.00 | — | — | |
| — | — | — | 14,824.6 | ||
| Wiring of light, fan, call bell etc. in casing-capping / conduit with 02 Nos. 2.5 sq.mm (for phase and neutral) and 01 No. 1.0 sq.mm (for ECC) copper wire in suitable size heavy gauge inflammable PVC conduit / casing with provision of suitable size modular PVC boards, PVC boxes, modular switches (piano type), fuses, indicator lamps, ceiling rose, angular holder etc. and all other required accessories with fixing & commissioning electronic fan regulator in case of fan point (excluding supply of fan & regulator) with dismantling of existing wiring, if any, including make good of wall / ceiling surface as its original condition. Copper wire shall be PVC insulated multi-strand single-core FR/ZHFR/FRLSH 1100V grade conforming to IS:694 of latest amendment. The wiring shall be done in conformation with IS:732 of latest amendment and IE rule upto date. The circuit shall be planned in such a way that each board shall not exceed total 10 points of light, fans & 6A socket outlets & total connected load of such board shall be restricted to maximum 800W (make as per Annexure-I). | — | 28.00 | — | — | |
| — | — | — | 9,587.84 | ||
| Supply of earth pipe made of 50mm (or above) nominal bore (dia.) heavy duty GI pipe, 3 mtr. (or above) long and digging, insertion, testing and commissioning of earth pipe including construction of earth pit. Each pit should be provided with 2 Nos. of above pipe duly shorted by suitable length of GI flat (50mm x 6mm) including necessary earth connection from pit to the assets with 4 SWG (or thicker) GI wire. Alternate layer of salt and charcoal is to be spread inside the pit. Earth pit shall be completed with necessary civil work like brick chamber, PCC work & finally covered with medium duty cast iron hinged cover of size 400mm x 400mm (minimum) (make of GI pipe as per Annexure-I) N.B.: The earthing should be done as per CEE/KKK's specification. All earth value should be marked on MS plate with date by painting work. The MS flat, plate should be painted by one coat of red oxide and 2 coats of black paint before execution. The marking should be done by white paint. | — | Breakup | for details. | — | |
| — | — | — | 59,000 | ||
| Dismantling of the existing clarifier-flocculator system including turbine box, turbine wheel, casing, pinion, bearing, housing block, scrapper arrangement etc. at old and new filter house, and to be handed over to concerned SSE in-charge. N.B.: Entire clarifier-flocculator system is to be considered as one unit. | — | 2.00 | — | — | |
| — | — | — | 11,800 | ||
| Cleaning of mud, sludge etc. from inside including base of the clarifier-flocculator tank after dismantling of all parts at old and new filter house. N.B.: Entire clarifier-flocculator system is to be considered as one unit. | — | 2.00 | — | — | |
| — | — | — | 14,19,894 | ||
| Supply, installation, testing and commissioning of the Clarifier-flocculator system with scraper arrangement to collect the retain sludge into the central pocket for dewatering. The work also includes required masonry works i.e. cement work of the clarifier-flocculator tank and other places against defective. | — | Breakup | for details. | — | |
| — | — | — | 42,480 | ||
| Painting of the entire structure (fittings) of the clarifier-flocculator system including MS jetty after scrapping, cleaning etc. with one coat of anti-corrosive red oxide paint and finally two coats of aluminium paint. N.B: All material required for painting work are to be supplied by the contractor. Entire clarifier-flocculator system is to be considered as one unit. (Paint make: Shalimar/ Berger/ Asian Paint/ Dulux) | — | 2.00 | — | — | |
| — | — | — | 47,200 | ||
| Supply of wall mounted LT cubical panel board made from 14 SWG (or thicker) MS/CRCA sheet duly powder coated painting, dust and vermin proof comprising of the following: (i) MCB 40A, 4 pole, 10kA (or higher) breaking capacity, 415V, 50Hz - 01 No., (ii) DOL starter suitable for 5HP, 3phase induction motor with 16A (or higher) contactor, auxiliary switches, protective devices, trip circuits and relay arrangement etc. - 02 set, (iii) Four pole copper busbar of 100A (or above) capacity of suitable size & length, heat shrinkable PVC sleeves insulated, supported on suitable insulator - 01 set., (iv) Digital type voltmeter, ammeter (for each starters) with selector switches (if required), LED phase indicator & ON-OFF indicator etc. (Make: As per Annexure-I) | — | 2.00 | — | — | |
| — | — | — | 7,080 | ||
| Installation, connection, testing & commissioning of above Panel Board with necessary masonry works. The work also includes provision of power supply arrangement by providing necessary accessories including gland, socket, cable entry box etc., and dismantling of existing panels, if any required. The panel is to be properly grouted with wall and earthed. It should be complete with 'Danger Board'. | — | 2.00 | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Tenderdocument_1.pdf
ATTACHMENT
Scheduleofwork.pdf
ATTACHMENT
GeneralSpecification.pdf
ATTACHMENT
checklist.pdf
ATTACHMENT
Annexure-IaIbIIIIIVVA.pdf
ATTACHMENT
Annexure-IVVIVIAVIBVIIVIII.pdf
ATTACHMENT
MakeAnnexure-I.pdf
ATTACHMENT
GCC2022.pdf
ATTACHMENT
AdvancecorrectionslipsofGCC2022.pdf Advance correction slips of GCC
ATTACHMENT
SharamikKalyalSpecialCondition.pdf
ATTACHMENT
AdvancecorrectionslipsofGCC2022.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .