Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 CrAccepted-AOC | ₹8.9 Cr | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹8.9 Cr+₹2.5 L (0.28%)Rejected-AOC | ₹8.9 Cr+₹2.5 L (0.28%) | L2 | Rejected-AOC NOT BEING LOWEST |
| 3 | L3₹8.9 Cr+₹7.0 L (0.79%)Rejected-AOC | ₹8.9 Cr+₹7.0 L (0.79%) | L3 | Rejected-AOC NOT BEING LOWEST |
| 4 | L4₹9.8 Cr+₹91.8 L (10.4%)Rejected-AOC | ₹9.8 Cr+₹91.8 L (10.4%) | L4 | Rejected-AOC NOT BEING LOWEST |
| 5 | L5₹10.7 Cr+₹1.8 Cr (20.5%)Rejected-AOC NO 15 B 2ND FLOOR 4TH CROSS T ASHWATHNARAYANA ROAD THIMMAIAH NAGARA YELAHANKA BANGALORE 560 064 | BANGALORE | BANGALORE | KARNATAKA | 560064 | ₹10.7 Cr+₹1.8 Cr (20.5%) | L5 | Rejected-AOC NOT BEING LOWEST |
Tender Value
₹8.5 Cr
EMD Value
₹7.5 L
Closing Date
28 Mar 2024, 6:00 pmClosed
Chief Engineer AF Bangalore
Chief Engineer AF Bangalore No. 2 DC Area MES Road Yeshwantpur Post Bangalore 560022
CONSTRUCTION OF WAREHOUSE FOR TEJAS FLEET AND OTHER OTM ACCN 26 ED AF STATION MARATHAHALLI
2024_MES_640012_1
801550/E8
Open Tender
Civil Works
Lump-sum
540 days
GE (AF) Marathahalli
As per NIT
8 documents required · 8 mandatory
₹3,000
GE (AF) Marathahalli
₹7.5 L
Yes
19 Apr 2024
31 Jan 2024
4 Apr 2024
31 Jan 2024
28 Mar 2024
14 Mar 2024
1 Feb 2024 - 12 Feb 2024
Amount
BOQ Dated 07 Mar 2024
GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to XII are prepriced by MES under Ser No. 1 to 12. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lumpsum price worked out by the contractor for “Building or works” as listed in Schedule ‘A’ Part–I
Lumpsum price worked out by the contractor for “Internal Water Supply” as listed in Schedule ‘A’ Part–II
Lumpsum price worked out by the contractor for “Internal Electric Supply" as listed in Schedule ‘A’ Part–III
Lumpsum price worked out by the contractor for “Site Clearance ” as listed in Schedule ‘A’ Part – IV.
Lumpsum price worked out by the contractor for “Road / Path / Culvert/Hardstanding " as listed in Schedule ‘A’ Part V .
Lumpsum price worked out by the contractor for "Sewage Disposal" as listed in Schedule ‘A’ Part VI .
Lumpsum price worked out by the contractor for “Area Drainage” as listed in Schedule ‘A’ Part – VII.
Lumpsum price worked out by the contractor for “Demolition/Dismantling” as listed in Schedule ‘A’ Part – VIII.
Lumpsum price worked out by the contractor for “External Water Supply” as listed in Schedule ‘A’ Part – IX.
Lumpsum price worked out by the contractor for “External Electric Supply” as listed in Schedule ‘A’ Part – X.
Lumpsum price worked out by the contractor for “Lightning Ptotection” as listed in Schedule ‘A’ Part – XI.
Lumpsum price worked out by the contractor for “Fire Fighting/Alarm System” as listed in Schedule ‘A’ Part – XII.
Sch 'A' Part - XIII : DG SET Supply , installed , commissioning and testing of Silent DG set as per Retro fitting emission control device CPCB approved of capacity 200 KVA , 160 KW , 1500 RPM , Turbo Charged, water cooled comprising of suitable 259 BHP Engine with microprocessor based Genset controller with silencer and canopy for soundles mode (sound level not exe level specified by contol pollution board) and alternator both mounted on a common base frame conforming to ISO-3046/ ISO-9001 and IS-13018 rated for 415 volts 50 cycles , 0.8 Power factor (PF) complete with residential silencer, AVM pads , battery with its leads, first fill of lub oil and all engine accessories such as self starter, alternator/dynomo with suitable coupling and base frame on foundation as recommended by the manufacturer and consisting of other electrical component and maintenance free battey including suitable size of coppeer cable lead with teminal, all mounting accssory and AVM pads all as specified comprising with the following.
A. Engine:- (a) Vertical multicylinder, cold starting in accordance with BS-5514/IS-10002 at 1500 RPM including the following accessories :- (i) Fuel tank(Suitable for capacity for minimum 12 Hrs run). (ii) Fuel filter(Ore & Micro). (iii) Fuel feed pump(Inline monoblock/PT type) with governor. (iv) Lub oil filter.(v) Lub oil cooler.(vi) Dry type/ol bah type air cleaner.(vii) Exhaust Silencer(Industrial type).viii) Radiator, Radiator fan & mounting.(ix) Fly wheel with starting ring.(x) Expansion bellow.(xi) Exhaust gas turbocharger.(xii) 24 volt electric stater with 02 Nos maintenance free battery of suitable capacity (xiii) Battery charging alternator (xiv) Engine control panel consisting with ON/OFF Start Key,Lub oil pressure guage, Battery charging ammeter,Coolant temp gauge, RPM Meter etc. (xv) Suitable flexible coupling (xvi) Front & Rear engine mounting supports (AVM pads) B. ALTERNATOR :- (i) Alternator, 3 phase, 415 Volts, 50 Hzs 0.8 PF 1500 RPM self excited, self regulated screen profected, drip proof alternator of capacity 200 KVA conforming to IS / IEC60034-1 with insulation class "H", single bearing and automatic voltage regulator accessories.C. ACOUSTIC ENCLOSURE:- (i) Specially design to meet stringent MOEF/CPCB norms of 75 dBA @ 1 mtr at 75% load under free field conditions. (ii) Air inlet louvers specially designed to operate at rated load even at 50 deg C air inlet temp. (iii) Powder coated for long lasting service life and superior finish. (iii) Powder coated for long lasting service life and superior finish. D. ACCESSORIES:-(i) Suitable channel frame (ii) Storage battery of suitable capacity as per manufactures instruction mounted on angle iron froame of suitable size as directed.
E. CONTROL PANEL: (a) The control panel shall be made of CRCA sheet duly fabricated and powder coated and complete with internal wiring, bus bar etc and fitted with the following accessories :- (i) MCCB of 4 pole 320 Amps, 25 ka- 01 No (ii) Digital Ammeter – 01 No (0 to 200 A) (iii) Digital Voltmeter 3 Ph 415 volts – 01 No (0 to 500V) (iv) Indicating lamps (LED type) (R-Y-B) – 01 set F. AMF PANEL:Shall be measured and paid seperately under relevant item of BOQ. NOTE:- (i) Antivibraton mounting pads to be incorported during installation as recommended by OEM. (ii) PCC Foundation and platform as per manufacterer's design / recommendation to be followed during installation of DG Set inclusive as per OEM recommandation.. (iii) Silencer pipe of engine is to be extended out of the building with suitable dia of MS / GI medium grade pipe duly heat insulated with suitable glass fibre wool material and covering with ss sheet the rate of which deemed to be included in the unit rate of Gen set. (iv) Lubricating oil shall be provided by the conractor cost of which deemed to be included in the unit rate of DG Set. (v) Four Nos free serviceing with complete material such as Lubricating oil, coolent, Lub oil filter, diesel filters, Air filter and fan belts etc as per manufacturer recommendation will be deemed included in the unit rate of DG set. (v) CPCB certificate for DG Set to be submitted by contractor to the Eng-in-charge prior to approval.(v) The quoted rate is inclusive of the above and also the cost of testing of DG set is also deemed to be included and nothing extra will paid on any account whatsoever.
Supply,testing & commissioning fixing out door type AMF control panel including Auto change over 320 A switch busbars control cable panel meter,incommer main MCCB 320 amps 50 KA and all control devices,relays,indicator etc all as directed below: The control panel shall be double door outdoor type weather and vermin proof IP65 with locking and ventilation arrangements with canopy made of CRCA sheet 3.15mm thickness factory made certified by OEM, powder coated and complete with angle iron frame 50x50x6mm including mounting arrangements of 1 feet height grouted PCC 1:2:4, Type B1 using 20mm graded stone aggregate, internal wiring, busbar etc and fitted with the following accessories:-
M & L for Earthing complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 25 x 3 mm as earthing lead by means of GI bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 40 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR Part I and including necessary excavation and earth work in any type of soil, 20 mm bore light grade GI pipe for watering funnel wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 8 mm dia TMT bars @ 15 cm c/c both way for cover and MS frame etc., complete all as directed. NOTE: (i) The unit rate includes earth wire and protection pipe up to (maximum 7.5 metre from earth plate) earth point/test point. (ii) Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
All as per item 15 here-in-before but with using galvanised iron strip 32 x6 mm.
Sch 'A' Part - XIV : LIFTS: Design, supply, install, testing & Commissioning goods lift (MRL) of capacity 2000 Kg, speed 0.5 metre/sec with single speed motor, 440/415 volts, 3 phase AC 50 Hz AC supply confirming to IS 14665 and as ammended suitable to service G+ 02 upper floors with AC Variable Voltage & Variable Frequency microprocessor based with V3F drive including ARD device system,3D infra red sensor in full height of door & built in announcing system with or with out and set complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors,Aluminium chequred plate floor,signals emergency Alarm bell ,Up/down direction and position indication at car and all landings Auxillary supply 230 volts single phase complete all as specified and as directed.
Note:- The lift shall be manufactured and installed as per IS-14665 (Part1 to Part 5) with latest ammendments and after completion of the installation, it shall be tested and commissioned as per IS-14665 or relevant IS Code in the presence of Lift Inspector of the state/ or any other competant authority. Also refer Sch 'A' Notes also to be taken into consideration while quoting. The expenditure for testing and commissiong shall also be demed to be included in the quoted rate. Make: Schneider/OTIS/Johnson Lift Pvt Ltd/KONE India/MITSUBISHI ELECTRIC/HITACHI Lifts/Thyssen Krupp
M & L for Earthing complete with galvanized steel plate electrode 600 mm x 600 mm x 6.3 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized earth wire 4mm dia as earthing lead by means of GI bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 40 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR Part I and including necessary excavation and earth work in any type of soil, 20 mm bore light grade GI pipe for watering funnel wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 8 mm dia TMT bars @ 15 cm c/c both way for cover and MS frame etc., complete all as directed. NOTE: (i) The unit rate includes earth wire and protection pipe up to (maximum 7.5 metre from earth plate) earth point/test point. (ii) Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
Sch 'A' Part - XV : Air conditioning/Water Cooler : Supply, install, commissioning and testing of Air Cooled Packaged Air Conditioners comprising of Hermatically sealed scroll compressors with microprocessor based control including copper refrigerant piping, electrical interconnection between indoor and outdoor units suitable for operation on R-410a refrigerants and of nominal capacity as 16.5TR complete as directed. (2 working + 1 standby)
Supply and installation of copper pipes of 7/8" with insulation-13mm thick.
All as per item No. 20 but of 1/2".
All as per item No. 20 but of 5/8".
All as per item No. 20 but of 3/8".
Supply and installation of communication cable of 3 core 1.5 sqmm with PVC conduit pipe.
Supply and installation of power cable of 4 core 16 sqmm .
Supply and installation of CPVC drain pipe 40mm dia.
Supply and installation of factory made rectangular duct with angle, flanges, supports, joints, gaskets,bolts & nuts etc of 24 gauge.
All as per item No.27 here-in-before but of 22Gauge.
Supply and installation of acoustic insulation-10mm thickness.
Supply and installation of thermal insulation-13mm thickness.
Supply and installation of aluminium grill with collar damper.
Supply and installation of fire retatdent flexible canvass connection.
Supply and installation of OPU stand floor mounted.
Supply and installation of Nitrogen pressure test, vaccumisation, gas charging and commissioning the system.
Supply, installation,commissioning of Water cooler partially stainless steel, electric driven single phase having approx storage capacity of 80 Ltr and nominal cooling capacity of 40 Ltr per hour with R-134A Refrigerant complete .
Supply and installation of voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 Volts to 250 Volts with output voltage stabilized at 230 Volts with accuracy of ± 2.5% and of capacity 2 KVA complete .
Sch 'A' Part - XVI : Fittings / Fixtures & Misc items. INTERNAL ELECTRIC SUPPLY : Supply and fixing Telephone socket, PVC/ploy carbonate type with back plate suitable for fittings all as directed.
Supply and fixing wall mounted fan 600mm sweep 900 rpm single phase 240 volts AC 50 Hz and connecting up complete including frame and louvers and provision of copper cable 3 core of size 0.5 sqmm all as directed.
Supply and fixing of LED light fitting 4 feet, 2 x 18/20 Watt, surface mounted mirror optic luminaires with parabolic bright anodized AL reflector and plactic end caps suitable for connecting up with three core flexible copper conductor cable of suitable size from ceilling rose complete all as directed.
Supply and fixing LED PC batten light fitting of 2 feet 10 Watt with energy efficient LED and integrated electronic driver of 10W fitting including connecting up with three core flexible copper conductor cable of suitable size from ceilling rose complete all as directed.
Supply and fixing of LED light fitting 2'x2' of cap 36 Watt, 220 Volt surface mounted mirror optic luminaire with parabolic bright anodized AL reflector and plactic end caps suitable and connecting up with three core flexible copper conductor cable of suitable size from ceilling rose complete all as directed.
Supply and fixing LED PC batten light fitting of 4 feet 20 Watt with energy efficient LED and integrated electronic driver of 20W fitting including connecting up with three core flexible copper conductor cable of suitable size from ceilling rose complete all as directed.
External Water Supply:- Construction of new valve chamber of size 900x900x900mm with foundation cement concret brick / bricks in cement mortar 1:6 , with PCC 1:4:8 type D2 sub base plaster internally and exposed external surface in cement mortar 1:4 (15 mm thick and provision of valve chamber cover made out of MS sheet 3.0 mm thick welded on angle iron frames 40 x 40 x 5 mm made out of double door type with hinges and locking arrangement duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer all as directed complete with good finishing..
External Electric Supply:- Suppy ,install,testing & commissioning 11 KV,200 KVA,out door type compact pre-fabricated package substatiion as per OEM make comprising of Transformer high voltage switch gear, control gear,low voltage switch gear and corresponding Interconnection (cable flexible,busbar) APFC panel auxiliary equipment ,11 KV unipackage substation shall consist of the following specifications:
HT SWITCH GEAR:-11kV 350 MVA, 630Amps 21KA for 3 Sec. SF6 insulated Non-Extinsible Compact switchgear (DV) consisting of One No. Direct module as incoming and One No. Fixed Manual Vacuum Circuit Breaker as outgoing with Microprocessor based self Powered Relay in SF6 insulated stainless steel enclosure, with series trip,self powered microprocessor based numerical over current relay (IDMTL + Inst.) protection. Interconnection between HT switchgear and transformer shall be using 1Cx3x95 sq.mm Al. armoured XLPE Cable -01 No. Self powered Numerical Non-communicable O/C & E/F Relay -01 No. CT - 40/1A, CL -5P10, Burden - 2.5VA for Protection.-03 No Manometer -01 No TRANSFORMER:-200KVA 11KV/433V 30 50Hz DYn11 Oil Filled Hermatically sealed copper wound transformer with corrugated wall and without conservator type design & Top normal porceilein bushing for HT and LT with Off load tap switch of range +5% to -5% insteps of 2.5%. Temp rise over an ambiant temp of 50Deg C- shall be 40/50 Deg C for Oil/winding resp. Insulation Class A; Losses (Subject to IS1180 Level 1 / Star 1) Max Losses at 50% Loading :780 Watts and Max Losses at 100% Loading : 2300Watts, Impedance shall be 4.5%.-01 No . Oil Temperature Indicator with alarm and trip contact -01 No. Winding Temperature Indicator with alarm and trip contact-01 No
LVS PANEL - 400AMPS ALUMINIUMBUSBAR( 100% for Phase and 50% for neutral ) Current Density for Al- 1amp/Sqmm, fabrication of CRCA 1.5/2mm Sheet. INCOMER FROM TRANSFORMER: 350Amps 433V 4P 50Hz 50KA Fixed manual Type Moulded Case Circuit Breaker (MCCB) with Thermal magnetic based release for Overload and magnetic short circuit protection. - 01 No . R,Y,B ON-OFF-TRIP Indication - 01 Set OUTGOINGS: 350Amps MCCB 4 pole 36KA with Thermal magnetic based release for Overload and magnetic short circuit protection Extended terminals - 01 No APFC PANEL (60KVAR) 60kVAR Automatic power factor correction panel in 6 steps (10KVAR x 6 ) consisting of following 160Amps 433V 3P 36KA Manual Fixed Type Moulded Case Circuit Breaker (MCCB) with Thermal mangetic based release for over current and magnetic short circuit as incomer to APFC Panel -01 No.APFCRVC Relay for 6 steps- 01 No. 10 KVAR metallized polypropylene capacitor bank- 06 No Capacitor duty contactor for switching on & switching off 10 KVAR bank - 06 No . 32Amps 433V 3P 10KA Miniature Circuit Breaker for 10kVAR capacitor protection - 06 No
OUTDOOR ENCLOSURE:-Outdoor type enclosure having construction of Galvanised Sheet Steel of combination 1.5/2mm with 4mm HRCAbaseframe. The Enclosure shall have IP54 degree of protection for HT& LT switchgear compartment & IP23 degree of protection for Transformer compartment. The enclosure shall be Powder Coated (Colour Light Gray &D.A.Gray ). Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for MV & LV compartment. Seperate Switch Operated bulket lamp + Hooter in Transformer compartment - 01 Set. INTERCONNECTION AND EARTHING:-Interconnection Between HT switchgear & Transformer using 1Cx3x95 Sq.mm XLPE Single core cable & Interconnection between Transformer & LT switchgear using AluminiumBusbars. Internal earthing connections by using 50 x 6mm GI strips- 01 Set Notes:-(1) Packge Sub-Station is outdoor plinth mounted type. Erection, and Civil work for package substation are to be included in the quoted rate . The Foundation details is to be approved by GE. (2) Package Sub-staion will be complete with the internal interconnections & earthing.
Supply installation testing and commissioning of 12 KV 630 A, 3 phase 21kA SF6 insulation 50 Hz outdoor type(IP54) extendable manually operated LBS feeder 1 incoming and 2 outgoing Ring Main Unit with Aluminum busbar ( 1 LBS incommer + 2 VCB out going) RMU all as directed .
Disconnecting carefully existing HT cable 11KV of size 95 sq mm cutting and connecting up to VCB to proposed RMU reconnecting and relaying all as specified and as directed. Note:- End termination, Excavation, returning, filling, sand cushioning and removing of extra material will be measured and paid with relevent items of pre-priced schedule of External electric supply..
Supply, install, testing & commissioning LT panel board, factory made cubicle totally enclosed in door type, CPRI approved, IP-65, fabricated out of 2 mm thick CRCA sheet with angle iron base frame made front side opening single door cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamel smoke grey colour paint over a coat of red oxide, inside and outside,copper bus bar of rating 640 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts HRFR grade copper conductor, single core, multi stranded , comprising of the following including necessary PCC work:-
(a) MCCB 320 amps 4 pole,25 KA,415 V - 01 No (incomming ) (b) MCCB 200 amps ,Adjustable type 3 pole,36 KA,415 V with neutral link - 01 No (O/G) (c) MCCB 100 amps ,Adjustable type 3 pole,16 KA,415 V - 03No (O/G) (d) MCCB 63 amps ,Adjustable type 3 pole,16 KA,415 V - 02No (O/G) (e) MCCB 32A TPN amps ,Adjustable type 3 pole,16 KA,415 V - 01No (O/G) (f) pre wired meter module with voltmeter ,Ammete,selctor switch cts control fuse & indicating lights-(g) RYB indicators - 01 set (h) copper bus Bar 600 Amps 4 Way with colour code red yellow,blue and black. Assembly -01 nos
Supply and fixing connecting up complete MCCB DB TPN 4 way-VTPN (vetical) double door 415 volts AC 50 Hz IP-43 protection comforming to IS 13032 universal mounting with copper busbar,neutral lind,earth studs detachable glands plates with knock outs on both sides all as directed.
Supply, install, testing & commissioning LT panel board, factory made cubicle totally enclosed in door type, CPRI approved, IP-65, fabricated out of 2 mm thick CRCA sheet with angle iron base frame made front side opening single door cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamell smoke grey colour paint over a coat of red oxide, inside and outside, copper bus bar of rating 200 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts HRFR grade copper conductor, single core, multi stranded , comprising of the following including necessary PCC work complete all as directed.
(a) MCCB 100 amps TPN 4pole Microprocessor type,16 KA,415 V - 01 Nos ( Incomming) (b) MCCB 63 amps ,Adjustable type 4 pole,16 KA,415 V - 02No (Out going) (c) MCB16- 32A TPN amps ,Adjustable type 4 pole,36 KA,415 V - 02No (Out going) (d) pre wired meter module with voltmeter ,Ammete,selctor switch cts control fuse & indicating lights-(e) RYB indicators - 01 set (f) copper bus Bar 200 Amps 4 Way with colour code red yellow,blue and black. Assembly -01 nos
Supply, install, testing & commissioning LT panel board, factory made cubicle totally enclosed in door type, CPRI approved, IP-65, fabricated out of 2 mm thick CRCA sheet with angle iron base frame made front side opening single door cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamell smoke grey colour paint over a coat of red oxide, inside and outside, copper bus bar of rating 200 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts FR HR grade copper conductor, single core, multi stranded , comprising of the following including necessary PCC work complete all as directed.
(a) MCCB 200 amps ,Adjustable type four pole,36 KA,415 V with neutral link - 01 No (incomming) (b) MCCB 32 amps ,Adjustable type 3 pole,16 KA,415 V - 07No (Out going) (c) pre wired meter module with voltmeter ,Ammete,selctor switch cts control fuse & indicating lights (d) Aluminium bus Bar 200 Amps 4 Way with colour code red yellow,blue and black. Assembly -01 nos (e) Painting.
Supply and fixing LED street light fitting 35 Watt 230 Volt AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
Supply and fixing moulded PVC / SMC Junction boxes out door type, weather proof, of size 240 x 130 x 95 mm to be fixed at the bottom of street light pole 3ph RYB busbar 200 amps capacity complete with suitable clamp , nut, bolt, washers and suitable glands ,to accommodate 01 No MCB SP 5 Amps 10 KA, with suitable connectors for incoming and outgoing connections, complete all as directed.
M & L for street light bracket made out of GI pipe light grade 40mm dia 1.2 metre length bent to shape and reduced to required size at top upto 1.5 metre length by cutting, welding and well finishing including MS clamp of flat iron of size 40x6 suitable length 2 sets complete with drilling, hole, fixing with nuts bolts and washers including painted with two coats of aluminium paint over a coat of red oxide primer including dismantling existing complete all as directed.
Material and labour for pole wiring drawn through 20 mm pvc conduit regid pipe including copper wiring multistrand two runs of 1.5 sqmm and one run of 1.5 sqmm earth wire as earth dolly.wiring sintex box to light fitting and internal connections for light fittings complete.
Supply and fixing HT cable root marker MS cast iron round die cast 4" round plate 2 mm thickness MS angle of 2.5 feet powered coated yellow colour very clear fonts and clean moulding and including pcc concrate for supporting of root marker angle bottom all as directed.
Disconnection of LT panel board out door type carefully and shifting of panel at new location including all electrical connections all as directed includig PCC work.
Taking down and shifting of tubular pole with cables ,lugs and fixing in MT side with pcc work and cable connections for running conduits.
Disconnection of UG cables of any size and diverting the line new locations complete system is in working condition.
Material and labour for cutting PCC /road, existing hard standing/flooring not exceeding 150mm width x 300mm depth for LT UG cable / GI pipes and making good the distrubed surfaces with cement concrate 1:2:4 type B1 using 20 mm graded stone aggregate compelte all as directed.
Material and labour for straight through joint (epoxy) Cold shrinkable type for UG cable including jointing kit and all accessories complete for making joints suitable for LT UG cable of Aluminium conductor of size 25 to 50 sqmm 3.5/4 core all as directed.
Material and labour for straight through joint (epoxy) Cold shrinkable type for UG cable including jointing kit and all accessories complete for making joints suitable for LT UG cable of Aluminium conductor of size 70 to 95 sqmm 3.5/4 core all as directed.
Supply,laying and testing PVC insulated PVC sheathed cable galvanised steel strip or wire armoured electric contol cables heavy duty with stranded copper conductor of size 2.5 sqmm 2 core 1100 volts grade complete drawn through PVC conduit suitable size with all accessories fixed as directed.
Fire fifghting/alarm system: Supply,Installation,Testing & Commissioning of Analogue Addressable 4 Loop Fire Alarm Control Panel expandable via plug-in loop driver boards, loop current 500 mA maximum per loop dual flash based microprocessor, supports to connect up to 200 Detector/devices for both automatic fire detection cum alarm and manually operated electronic alarm system in each loop via fully digital communication protocol,equipped with a white backlit display (1500 Character/240x64 pixel resolution /10" Touchscreen) graphical LCD Display with atleast 6 lines of information, 400 fire zones (soft zones), fully programmable via alphanumerickeypad or configuration software without using any king of DONGLE /LICENCE /SPECIAL CABLE, dediacted USB and RS-232 serial port for direct or PC connection.
10500 events storage, loop current 500 mA, panel shall be equipped with in-built multi-meter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, in-built fault- tolerant network card to network with compatible addressable panel(s) and repeater panel(s), capable to connect maximum 200 network nodes on a standard network, features battery charger status and temperature, supports programmable cause / effect on outputs, panel housing meets min IP30 ingress protection classification finished in RAL 7035, The panel shall support more then one OEM protocol to allow user of using other make detector & devices at later stage. (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design). Approved by: British Standards Institute (BSI) and Vertrauen durch Sicherheit (VdS), Independently certified as complying with requirements of BS EN 54 Part 2, 4, and 13
Supply, Installation, Testing & Commissioning of Active Repeater Panel (Remote Control Panel) with white backlit (240x64) graphical LCD display, incorporates function buttons for Silence, Mute, Resound, Reset and Disable/Enable, flash memory and advanced graphical display allows it to be easily configured to operate in virtually any language, with any character set and allows for the installer’s logo and corripany details to be displayed on the LCD display during normal operation. Networked for system display and control, in-built fault-tolerant network card to network with compatible addressable panel(s) and repeater panel(s), fully on-site programmable via alphanumeric keypad or configuration software, panel housing meets min IP30 ingress protection.
Material and labour, Installation,commissoning and Testing of Isolator Base fully monitored for short/Open circuit compatible with ESP Analogue Addressable Protocol,Electronically addressed, approved by LPCB,unit incorporated an amber LED to show when it is isolating a section of a Loop.
Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 2.5 sq mm ,2 core, 1100 Volts grade.
Supply, laying & testing PVC insulated, PVC sheathed cable galvanizedsteel strip or wire armoured, electrical control cable(Heavy Duty) with stranded copper conductor of size 2.5Sqmm 2 core complete all as directed.
Cutting existing steel tubing of size 150 mm dia MS tube for alterations or addns (each cut measured)
Materilal and labour for fixing of hose reel of 20 mm dia and 30 meter length conforming to IS 5132 and hose reel arrangement shall confirming to IS 884.
Materilal and labour for fixing of hose reel of 20 mm dia and 30 meter length conforming to IS 5132 and hose reel arrangement shall confirming to IS 884.
Supply and fix 100 mm dia pressure sensing valve .
Supply and fix 100 mm dia Air releasing valve . Note for items 63 to 72: (i) Sch 'A' Notes also to be taken into consideration while quoting. (ii) The work shall be carried out all as directed by Eng-in-charge.
UNITED TECHNO PROJECTS PVT LTD
AFSON ENGINEERS & CONTRACTORS
SIGNATURE INFRASTRUCTURES(E DHARANI KUMAR REDDY)
Phoenix Infra
C R R CONSTRUCTIONS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .