Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹83.8 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹84.8 L+₹1.1 L (1.26%)Admitted-Finance | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/S REAL TECK ENGINEERING L1 | Electromechanics Engineers And Contractors L2 |
|---|---|---|---|---|---|
| 1.00Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch( Red/Black colour switch to be used for UPS) , modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. | |||||
| 1.01 | Group C | 422 | Point | - | - |
| 2.00Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 2.01 | Group C | 82 | Point | - | - |
| 3.00Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required | |||||
| 3.01 | 2x1.5 + 1x1.5 sq. mm | 100 | Metre | - | - |
| 3.02 | 2 x 2.5 + 1x2.5sq. mm | 1,390 | Metre | - | - |
| 3.03 | 2 x 4.0 +1x4.0 sq. mm | 2,314 | Metre | - | - |
| 3.04 | 2 X 6.0 +1x6.0 sq. mm | 40 | Metre | - | - |
| 3.05 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire | 244 | Metre | - | - |
Tender Value
₹1.1 Cr
EMD Value
₹2.1 L
Closing Date
13 Feb 2020, 4:00 pmClosed
Er Pawan Tickoo
Executive Engineer PWD RandB Electric Div Jammu
please reffer BOQ
2020_PWDJK_91801_1
Fresh e-NIT No.EDJ/236 of 2019-20 Dated 03-02-2020
Open Tender
Electrical Works
Item Rate
Women College Parade
please reffer to NIT
4 documents required · 4 mandatory
₹1,000
Yes
Executive Engineer PWD RandB Electric Div Jammu
₹2.1 L
Yes
29 Feb 2020
3 Feb 2020
14 Feb 2020
4 Feb 2020
13 Feb 2020
4 Feb 2020
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch( Red/Black colour switch to be used for UPS) , modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required
2x1.5 + 1x1.5 sq. mm
2 x 2.5 + 1x2.5sq. mm
2 x 4.0 +1x4.0 sq. mm
2 X 6.0 +1x6.0 sq. mm
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
Supplying and drawing co-axial TV cable RG-6 grade, 0.7mm solid copper conductor PE Insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/recessed steel/PVC conduit as required.
Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of Recessed conduit as required
Supplying and fixing following size/modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 module ( 75mm x 75mm)
3 Module (100mmX75mm)
4 Module ( 125mm x 75mm)
6 Module ( 200mm x 75mm)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required
5/6Amp Switch
3 pin 5/6 Amp socket outlet
Telephone socket outlet
TV antenna socket outlet
Bell Push
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 An modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Supply, Installation of 50 pair Telephone krone box suitable for Termination of 50 Pair Telephone cable including Krone connectors for 50 Pair cables.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing 5 amps to 32 amps 10kA rating, 240 Volts, 'C" series, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Double Pole
Triple Pole
Triple Pole & Neutral
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Providing and fixing M.V. danger notice plate of 200mm x 150mm , made of mild steel, at least 2 mm thick , and viterous enamelled white on both sides, and with inscription in single red colour on front side as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
upto 35sq.mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.
upto 35sq.mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
upto 35sq.mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit/Cable Tray as required.
1 x 1.5 sq. mm
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator)
4 Rows x 14 Module
8 Way TPN, Double Door
6 Way TPN, Double Door
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40A - 63 A FP 10kA Class 3 , C Curve
Supplying & fixing of 20/22 watt LED 4 feet tube light fitting/fixture CRCA housing with 2000 Lumens and min lumens efficiency 100 Lumens/watt P.F 0.95 THD < 16% & voltage input range 140-270 V with Shot circuit & overload protection circuit off
Supplying & fixing of 2ftx2ft LED Recess mounting Light Fixture having minimum 3000 Lumens P.F 0.95 THD < 16%
Supplying & fixing of 15/18 minimum1500 Lumens ( system output), surface mounting having dies cast aluminium housing and heat sink, IEC compliant driver
Supplying & fixing of LED Bulkhead.
Supplying & fixing of 2ft LED Batten 17W Ultron scene switch.
Supplying & fixing of Wall / Ceiling Fans 230V 50Hz celing fan with double ball bearing with low power consumption of following sweeps.
1200mm Ceiling Fan
1400mm Ceiling Fan
400mm Wall Fan
Supply of following sizes of heavy duty exhaust fan as per
450mm Sweep
300mm Sweep
250mm Sweep
Supply, Installation, Testing and commissioning of Floor Mounted Low Voltage indoor panel IP 42 suitable for operation on 433V 3 Phase, 50Hz supply, made of 2.0mm CRCA sheet enclosure with Aluminium bus bar Four wire with following switchgears and metering. Necessary arrangement be made for termination of incoming cable and outgoing cables . LT Panel shall be manufactured as per IS 8623 .All accessories such as shunt coils, UV release, contact blocks, locks and keys as required by the scheme shall be included in the panel price while quoting. Contractor to get the G.A. drawings approved before execution. Incomer : 400A 4pole MCCB 36kA - 1 No. with thermal magnetic release overload and short circuit adjustable 200A 4pole ON load changeover - 1 No. Phase Indication LED Lamps shall be provided on each incomer Busbar : 500A 4 Wire Aluminium Bus Bar supported on DMC Insulators. Outgoings : 250A 4P MCCB 25kA - 1 Nos. 200A 4P MCCB 25kA - 1 Nos. 100A 4P MCCB 25kA - 12 Nos. 63A 4P MCCB 25kA - 13 Nos. All MCCBs shall be have overload adjustable setting 80-100% and adjustable short circuit setting and shall be installed with Rotary Operating machanism, auxilliray contacts.
Supply , Installation, Testing and commissioning of Automatic Power Factor Correction Panel Indoor type in IP42 protection, floor standing, fabricated of 2mm thick CRCA sheet , duly powder coated . The panel shall be suitable for operation on 415 Volts , 50Hz, 3 phase system with TPN Aluminium busbar of 300Amps, The Capacitors and Switchgears shall be arranged in a modular arrangement duly comprmentalised. Panel shall be complete with earthing arrangement , markings, single line diagram and shall comprise of the following Switchgears and capacitors, refer technical specifications of tender documents for detailed specs.( Shop Drawing of the Panels to be got approved before taking up manufacturing Incomer : 160A 4 pole MCCB Ics=36kA - 1 no. One Set of Indications using LED type indicators Busbar : Shall be of TPN Alluminium rated for 300Amps with heat shrinkable sleeves and mounted on DMC supports Outgoing : 32Amps 3pole MCB - 12 no. Capacitor Switching Duty Contactors of following ratings 5kVAR - 12 Nos Heavy Duty Resin Filled Capacitors 3 Phase shall have following configuration 5kVAR x 12 APFC Relay of 12 stage shall be used Material Used shall be of list of makes enclosed Shop Drawings to be got approved before manufacturing
Supply of 1.1kV grade , XLPE insulated, Aluminium conductor, Heavy Duty , Armoured cables of following ratings as per IS : 7098 Part-1 with latest amendments.
3.5C x 400sqmm
3.5C x 240sqmm
3.5C x 185 sqmm
3.5C x 70sqmm
3.5C x 35sqmm
Supply, Installation of ABC type Fire extinguishers 6kg , wall mounted
First Aid box complete with medicines
Electric Shock Treatment chart ( larger size) with aluminium frame and glass on front or laminated as approved.
Supply and laying of Fire Retardant 2.5mm Insulation Mat of Class B 11kV class manufactured as per IS 15652:2006 duly tested by CPRI. Test certificate to be provided by the manufacturer/contractor.Dimension of mat shall be 1000mmx2000mm each
Supply, installation, testing & commissioning of maintenance free copper earthing system with 3 mtrs. Electrode 40 mm dia with minium 2mm thick and does not require manual additional of water. The electrode shall be pre-filled with hygroscopic powder and provided with suitable breathing and leaching ports at the ends. the electrode shall be surrounded by suitable powdered form of BEE MOIST so as to provide maximum contact between the electrode and the compund. The compound should be eco-friendly and having ROHS certification. The earthing pit should be covered with PVC cover. along with providing and laying of 25 x 5 mm copper strip from copper rod up-to the main panel.
Supply, installation, testing & commissioning of GI Electrode Earthing with 50mm dia and 3 meter length, with 3mm thick the electrode should be hot-dip galvinised. The GI Electrode shall be pre-filled with Cristaline Conductive Materila (CCM). The GI electrode shall be surrounded with BEE MOIST compound to provide maximum contact betwen the electrode and compound should be eco-friendly and having ROHS certification GI Electrode Earthing should be maintinance free and does not require regular manual addition of water GI Electrode shall be tested from CPRI. The earthing pit should be covered with PVC cover. along with providing and laying of 25 x 5 mm G.I strip from G.I rod upto the main panel.
Providing and fixing of lightning conductor finial, made of 25mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable multi criteria sensing type photothermal detector complete with mounting base complete as required. .
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supplying, installation, testing and commissioning of Analog Addressable type Active/ Passive Repeater Fire Alarm panel with Backlit LCD Display, having Controls For Reset, Mute, Accept, Silence alarms and Self Test Conforming to BS5839 Standards and Duly
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring &LSZH outer sheath complete as required.
Supply & Installation of Wire mesh Electro Zinc Cable Tray of following sizes including couplers, earthing `Mounting brackets or any other accessories for mounting of cable trays on exisiting steel structure to be erected by the contractor specifically for mounting of cable trays as shown in layout drawings. All accessories required to install cable tray shall be included in the cost of cable tray . Cablofil/Tyco/Cooper
150mm x 50mm
300mm x 50mm
600mm x 100mm
Supply, Installation, Testing and commissioning of UPS 3 phase (415 V+ 15%) Volts input & 3 phase output (415 V + 1%), 50 Hz, IGBT based technology, Input harmonic Current THD <=3% typical at 100% load, <=6% maximum at 100% load with and 30 min battery backup for each UPS along with battery cabinet, complete in all respect including supporting steel structure for UPS and Battery as required.Quoted price shall be inclusive of required rating single core copper conductor cable including terminations,connections of UPS to batteries etc complete in all respect and as per direction of Engineer in Charge.
Supply, Installation, Testing and commissioning of fixed 19" , 400mm Depth , 15U capacity, Wall mounting Network cabinet equipped with With reversible rounded print screen glass safety door Pivoting side panels, tool-free removal from inside Lock closure with key, Supplied with 2 x 19" uprights with depth adjusting aid Supplied with earthing kit high and low grilles for natural ventilation, capable of taking a fan in the high part Charcoal grey RAL 7016 .
Supply erection, 24 Port Patch Panel including keystone connectors Cat 6A
Supply erection, Testing and commisioning of Cat 6A UTP patch cord 1m
Supply Installation Testing and commisionng of Cat 6A RJ45 outlet in existing boxes / plates / frames
Supply, Installation Testing and commissioning of IP CCTV system suitable for integration with Networks consisting of the following components, contractor to quote considering all components that may be required to complete the system as per owner satisfaction, no extra cost shall be paid for any item requred to complete this job.
IN/OUT DOOR DOME CAMERA - Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IR Indoor/Outdoor Dome type fixed Camera, 1/3" Progressive Scan CMOS Camera with 4 MP Lens @ 25fps recording & live Viewing. Triple stream, Min. Illumination required 0.03 lux (color), 120dB True WDR, Pixels 2560×1440/2688x1520 P, 2.7mm - 13.5 mm motorized focus & 5X zoom lens, Backlight Compensation, 3DNR, Privacy Mask, Internal/External Smart IR LEDs with upto 40m IR distance, H.265/H.264/MJPEG, 128GB SD card support, IP 66 & IK10, PoE Class 0/12V DC/24VAC, Die-Cast Aluminum Construction, Having Operating temp range : -30°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant, UL, CE, EN, FCC & RoHS compliant.
IN/OUT DOOR DOME CAMERA - Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IR Indoor/Outdoor Dome type fixed Camera, 1/3" Progressive Scan CMOS Camera with 2 MP Lens @ 25fps recording & live Viewing. Triple stream, Min. Illumination required 0.08 lux (color), DWDR, Pixels 1920x1080 P, 2.8 mm fixed lens, Backlight Compensation, 3DNR, Privacy Mask, Internal/External Smart IR LEDs with upto 25m IR distance, H.265/H.264/MJPEG, IP 66, PoE Class 0/12V DC/24VAC, Die-Cast Aluminum Construction, Having Operating temp range : -30°C to 55° C. Certifications: ONVIF Profile S & Profile G compliant, UL, CE, EN, FCC & RoHS compliant.
Recording / Management Server - Supply Installation Testing Commissioning of Suitable Network Video Recorder & Management System with required Licenses for all of the above mentioned Complined Cameras complete with all necessary required software's, Hardware's, Storage, Accessories, Civil, Electrical works & peripheral items required as per specifications & at site of work inline with the engineer in charge instructions. The system proposed should have minimum usable 30 days recording suitable Hard Disk as per requirement with 320MBPS throughput. Certifications Hard Disk Complete in all respect upto entire Satisfaction Engineer in charge of works. IP Camera Input upto 32 Channel and 4 SATA of 8 TB each. Certifications: ONVIF Profile S Compliant, UL, CE, EN, FCC & RoHS Compliant.
6TB Hard disk
24 Ports Layer 2 Non-PoE Switch at Control Room : 26-Port 10/100/1000 Base-T Gigabit Layer 2+ Managed Switch with 4 Gigabit Shared SFP Ports and External RPS support.
24- Ports Layer 2 PoE Switch : 24-Port 10/100/1000 Base-T Gigabit PoE (8-Port PoE+) Smart Managed Switch with 4 Gigabit Dedicated SFP Slots and Static Routing Support.
8 ports Layer 2 PoE Switch: 8-Port 10/100/1000 Base-T Gigabit PoE Smart Managed Switch with 2 Gigabit Fiber SFP Slots D
Surge Protector for IP Camera
42" high resolution LED Display with HDMI interface application with all accessories of wall mount
Supply, installation, testing and commissioning of 82.5 KVA capacity silent DG set comprising of stationary type, Liquid Cooled, turbocharged after cooled developing suitable BHP under NTP condition of BS:5514/ISO3046 & ISO 8528 and alternator brushless, self excited self regulated conforming to BS 5000/IS 4722 suitable for continuous operation, generating 82.5 KVA at 1500 RPM, 415 volts, 0.8 power factor 50HZ, 3 phase. The set shall have Microprocessor/relay based AMF control panel. The Engine and Alternator would be duly aligned and coupled with each other on the common MS fabricated base frame. The sound attenuating system of Silent DG Set shall conform to latest MOEF/CPCB II norms amended upto date, of noise level upto 75db at 1 meter distance. The set shall also have inbuilt fuel tank, fully filled with Diesel, and Batteries. Installation & commissioning of Silent DG Set at site, shall include handling, installation of DG Set on the Cement Concrete Platform, , and Earthing for DG set and Panel as per relevant IS specifications inspected at Manufacturer's works by M/S Cell New Delhi.
Supply of 250 kVA continous rating, 11kV/ 433V, 3 phase , 50Hz,Dyn-11 vector group, step down, out door type, copper wound, ONAN type transformers complete with with all accessories, fittings and conforming to specifications. Transformer shall have cable end box for 11 kV XPLE cable on HT side and Cable chamber on medium voltage side. The tap changing range shall be from + 5% to- 5% in step of 1.25%.
Supply, Installation, Testing and commissioning of 250 KVA Indoor type, Unbalanced input , unbalanced output, LV Automatic Servo Voltage Stabilizer indoor type, suitable for input voltage range of 135V to 460V three phase, and output voltage at 433V +/-1%. The stabilizer shall have all necessary protections i.e. overvoltage , undervoltage, surge protection, overcurrent, short circuit. Contractor shall submit necessary documents, drawings for approval before intiating procurement process. Stabilizer shall have suitable arrangement for termination of cables as per site requirements. Stabilizer shall be supplied with first fill of oil, and complete with bypass panel alongwith MCCB's of suitable rating as its protection.
Supply Installation Testing and commissiong of 32 A 3 phase ( 3P+N+E) Plug and socket with provision for 4P MCB IP67 enclosure, wall mounted.
Supply, Installation, Testing and commissioning of 90 W led Street lights having system lumen efficacy of minimmum 100 lumen per watt, 10 kv built in Surge protection, IP 66, manufacturere name Embossed on dicast Aluminium body .
Supply, Installation Testing and commissioning of 2 Pole Structure suitable for termination of 1 Nos Overhead 11 KV Lines, consisting of SP 56 Steel Tubular Poles conforming to IS:2715, Steel parts such as angles, channels etc as per approved darwing , 1 Nos Horizontal Double Break Air Break Switches 11kV, 200Amps, 1 Nos GODO Switches, LA sets , ACSR Conductor, Pin and Strain Insulators, Cable Supports Earthing Strips, Extended handles for Air Break Switches along with Rods, hardware, nuts and bolts, PCC foundations (1:3:6) . The Contractor to get the General Arrangement.
Supply, installation, testing and commissioning of Interactive Flat Panel Display ( as per technical specification enclosed)
Supply, installation, testing and commissioning of Cabinet including Controller, Visualizer, UPS, Keyboard and Mouse ( as per technical specification enclosed)
Supply, installation, testing and commissioning of Audio Podium Gooseneck microphone,gooseneck lamp,80W amplifier ( as per technical specification enclosed)
Electromechanics Engineers And Contractors
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.38 MB
Tendernotice_2.pdf
PDF • 0.30 MB
Tendernotice_3.pdf
PDF • 0.09 MB
BOQ_172701.xls
BOQ • 0.36 MB
Make.pdf
Other Document • 0.15 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .