Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.2 LAccepted-AOC NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹39.7 L+₹1.3 L (3.34%)Rejected-Finance | L2 | Rejected-Finance Other than lowest. | |
| 3 | L3₹42.8 L+₹4.4 L (11.4%)Rejected-Finance | L3 | Rejected-Finance Other than lowest. | |
| 4 | L4₹45.2 L+₹6.8 L (17.6%)Rejected-Finance 37 222 BUNDU KATRA AGRA UP | AGRA | UP | L4 | Rejected-Finance Other than lowest. |
| Sl No | Description | Qty | Unit | Vijay Electricals L1 | M/S MAMTA CONSTRUCTIONS L2 | PD GUPTA AND COMPANY L4 | Sadhana Enterprises L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | M&L for complete paint removing from surface of existing Panel box and applying two coats of synthetic enamelled paint over a coat of red oxide primer for size of Panel boxes from all in & out side incl angle iron frame work min 04 Sqm area of sheets including angles canopy and legs etc.
Note: Permission to shutdown of electric supply to the panel to be taken from MES before commencement of work. | 20 | Each Job | 200 ₹4,000 Lowest | 200 ₹4,000 Lowest | 500 ₹10,000 | 450 ₹9,000 |
| 2.00 | M&L for finding faults of LT UG cable XLPE of any size and any length by using computerised / primary current injection method / any other method as directed by the GE and locating fault, cutting and removing the faulty portion of the cable and jointing with suitable cable joint and testing after jointing complete all as specified.
Note: Joints shall be paid for separately. | 3 | Each Job | 15,000 ₹45,000 | 8,000 ₹24,000 | 500 ₹1,500 Lowest | 4,500 ₹13,500 |
| 3.00M&L for cable jointing kit for 1.1 KV grade for straight through joint complete with jointing material and accessaries suitable for 3.5/4 core XLPE armourd aluminium conductor cable of following size after detaction of fault location .Make:3 M,Denson or equivalent Note: Earth work and returning filling which require in above job will be measured and paid seperataly. | |||||||
| 3.01 | (a) 25 Sqmm to 50 Sqmm | 6 | Each | 1,200 ₹7,200 | 800 ₹4,800 | 350 ₹2,100 Lowest | 1,700 ₹10,200 |
| 3.02 | (b) 70 Sqmm to 120 Sqmm | 6 | Each | 1,200 ₹7,200 Lowest | 1,200 ₹7,200 Lowest | 2,000 ₹12,000 | 2,150 ₹12,900 |
| 3.03 | (c) 150 Sqmm to 240 Sqmm | 6 | Each | 1,200 ₹7,200 Lowest | 1,800 ₹10,800 | 2,500 ₹15,000 | 3,200 ₹19,200 |
| 4.00 | Excavation in trenches, n. exc 1.5 Mtr wide and n. exc 1.5 Mtr in depth for foundation/laying of cable and getting out in soft/loose soil complete all as specified. | 1,075 | Cum | 100 ₹1,07,500 | 65 ₹69,875 Lowest | 71 ₹76,325 | 75 ₹80,625 |
| 5.00 | Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick complete all as specified. | 666 | Cum | 29 ₹19,314 | 35 ₹23,310 | 25 ₹16,650 Lowest | 25 ₹16,650 Lowest |
| 6.00 | Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point complete all as specified. | 409 | Cum | 29 ₹11,861 Lowest | 30 ₹12,270 | 30 ₹12,270 | 30 ₹12,270 |
| 7.00 | Supply spreading in trenches fine dry river sand for cable protection and punning down gently by hand complete all as specified. | 303.38 | Cum | 300 ₹91,014 | 450 ₹1,36,521 | 250 ₹75,845 Lowest | 400 ₹1,21,352 |
Tender Value
₹49.5 L
EMD Value
₹99,000
Closing Date
8 Aug 2025, 3:00 pmClosed
GE Bharatpur
GE Bharatpur
REPAIR TO LT EXTERNAL ELECTRIC SUPPLY LT CABLE LT OH LINES LT PANELS AND CONNECTED WORKS AT SEWAR FORT PARADE GROUND AND 39 FAD DEPOT AREA UNDER GE BHARATPUR
2025_MES_719936_1
8498/E8
Open Tender
Civil Works
Item Rate
180 days
GE Bharatpur
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
GE Bharatpur
₹99,000
Yes
8 Sept 2025
11 Jul 2025
11 Aug 2025
11 Jul 2025
8 Aug 2025
25 Jul 2025
11 Jul 2025 - 24 Jul 2025
Amount
M&L for complete paint removing from surface of existing Panel box and applying two coats of synthetic enamelled paint over a coat of red oxide primer for size of Panel boxes from all in & out side incl angle iron frame work min 04 Sqm area of sheets including angles canopy and legs etc. Note: Permission to shutdown of electric supply to the panel to be taken from MES before commencement of work.
M&L for finding faults of LT UG cable XLPE of any size and any length by using computerised / primary current injection method / any other method as directed by the GE and locating fault, cutting and removing the faulty portion of the cable and jointing with suitable cable joint and testing after jointing complete all as specified. Note: Joints shall be paid for separately.
M&L for cable jointing kit for 1.1 KV grade for straight through joint complete with jointing material and accessaries suitable for 3.5/4 core XLPE armourd aluminium conductor cable of following size after detaction of fault location .Make:3 M,Denson or equivalent Note: Earth work and returning filling which require in above job will be measured and paid seperataly.
(a) 25 Sqmm to 50 Sqmm
(b) 70 Sqmm to 120 Sqmm
(c) 150 Sqmm to 240 Sqmm
Excavation in trenches, n. exc 1.5 Mtr wide and n. exc 1.5 Mtr in depth for foundation/laying of cable and getting out in soft/loose soil complete all as specified.
Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick complete all as specified.
Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point complete all as specified.
Supply spreading in trenches fine dry river sand for cable protection and punning down gently by hand complete all as specified.
M&L for cable protection cover with sub Class`B` bricks old size laid dry, flat perpendicular across the cable in trenches complete all as directed.
Boring of holes under road, pavement, hard standing by trenchless technology using suitable tools and machinery for laying of pipe upto 150mm bore complete all as specified and as directed . Note :- GI pipe shall be measured and paid in concern Item
S & F or laying galvanised steel tubing light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing of size 50mm bore complete all as specified.
S & F or laying galvanixed steel tubing light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing of size 100mm bore complete all as specified.
M/L for taking out Unsv U/G cable PVC insulated armoured PVC sheathed Al. Conductor, LT cable of any size complete all as specified.
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole of the following sizes:-
(a) 185 Sqmm 3.5 core
(b) 120 Sqmm 3.5 core
(c) 95 Sqmm 3.5 core
(d) 70 Sqmm 3.5 core
(e) 50 Sqmm 3.5 core
(f) 35 Sqmm 3.5 core
(g) 25 Sqmm 4 core
(h) 16 Sqmm 4 core
(j) 10 Sqmm 2 core
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable of single core 120 Sqmm with stranded copper conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole
S&F including taking out of existing MCCBs thermal magnetic ,adjustable type of following capacity :-
(i) MCCB 415 volts thermal magnetic release adjustable type 400 Amps 04 pole 36KA
(ii) MCCB 415 volts thermal magnetic release adjustable type 250 Amps 04 pole 36 KA
(iii) MCCB 415 volts thermal magnetic release adjustable type 200 Amps 04 pole 36 KA
(iv) MCCB 415 volts thermal magnetic release adjustable type 160 Amps 03 pole 36 KA
(v) MCCB 415 volts thermal magnetic release adjustable type 100 Amps 04 pole 25 KA
(vi) MCCB 415 volts thermal magnetic release adjustable type 63 Amps 04 pole 25 KA
M& L for Earthing complete with galvanised mild steel plate electrode 600x600x6 mm thick buried directly in ground vertically (earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate electrode at a depth not less than 1.5m below normal ground level and including GI earth strip 32x6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate electrode at one end connected to metallic bodies of HT/LT equipment etc at the other and earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of earth plate electrode to body of equipment fixed with and including 25x6 mm flat iron clamps bolts, nuts and washers and including providing watering pipe 20mm bore GI Pipe electrode complete all as specified and shown in elctrical plate No 3 of MES SSR Part-I. the scope of work includes necessary excavation and earth work in any type of soil. removal of soil upto 50 metre PCC pit with precast RCC cover, charcoal/ salt funnel, CI frame etc complete all as specified & directed.NOTE:(I) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.50 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars @ 150mm c/c both ways.(ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be adjusted through deviation order (iii) Item includes cost of 7.5 metre earth lead strip .Any variation in length shall be adjusted through deviation order. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thinkness of 15 cm on all sides.
Supplying and laying in repair synthetic Rubber insulated mats 2.0 mm thick for voltage upto 1.1 Kv for electrical purpose suitable for electrical shock safety of sizes 2m x 1m complete all as specified.
Supply and fixing in replacement of Lithium base Energy efficient integrated Solar street light of 30/32 watt in Aluminium Die casting body / FRP Bpdy , corrosion resistance,integrated PV panel Automatic dusk to input voltage 12.8V with suitable battery ,Driver efficiency .85%,PV module itself will be used to sense the ambient light to switch ON/OFF the Lamp, inbuilt MPPT charge controller, IP65,both PIR and fixed dimming available,4500 lumens (at full brightness) with grater than 150 lumen per watt,5700ANSI, cool white(5500K-6500K),CRI.70,moptical used, Metal core PCB,Low voltage cutoff ,high power LED,wide beam Angle(120 degree) LED Life 50000 hrs, weight less than 15 kg with GReen/Red indicator swith with suitable battery rating 12.8V-BIS standard of complete specified & directed.Make: Orient/HAVELLS/Crompton Protections: Short circuit, overload,Reserve polarity and battery protection.Firm should provide vital parametres Test report from NABL accredited lab and should be of made in India with CE & ROHS complaint.
M & L for servicing of existing APFC pane of cap upto 200 KVAR including carrying out minor maintenance/repairs as required to make functional the systems incl providing 03 Nos CT's of suitable rating in existing LT panel alongwith 6 sqmm copper wire to get result of current in existing panel etc complete all as specified.
S&F in repair Capacitors duty contacor as per existing make and type of following capacity.
(a) 20 KVAR
(b) 10KVAR
(c) 5 KVAR
(d) 2 KVAR
(e) 1 KVAR
S & F in repair power factor APFC relay 8 stage 415 V AC,3CT confirming to IS 13340 complete all as specified.
Demolition of old PCC and M&L for cement concrete 1:4:8 type D2 (using 40 mm graded crushed stone aggregate) as in foudation,filling and mass concrete complete all as specified.
Demolition of old PCC and M&L for cement concrete (1:2:4) type B-1 using 20mm graded crushed stone aggregate for pedestal of poles/ coping including necessary formwork, fair finishing to exposed surfaces using extra cement complete all as specified.
M&L for disconnection of LT panel incl LT cables of size upto 240Sqmm X 3.5/4core from existing foundation and reconnection with same panel after taking necessary corrective action to lift the panel height incl excavation and taking down existing cable with loop, providing new AL lugs and cable gland of appropriate size,insulation tape etc to restore electric supply incl necessary iron work to modify height of existing LT panel upto 1.2 Mtrs above existing level incl necessary welding work,nuts & bolts and 2 coat of paint with existing color over one coat of primer and required necessary PCC work complete all as specified. Note: PCC shall be measured & paid separately under respective item.
Supply & fix in replacement 60 watts LED street light fitings new generation energy saving ,environmental friendly ,long life,versatile pressure die cast aluminium with following specification IP66 with 10KV surge protection , PF>0.95, THD < 10%, input voltage 220-240V AC, operating voltage (VAC) 100V -300 V, Lum Flux (+-) 10% , CRI -80 Lum efficienacy (+-) 10% CCT -5700K road way,luminaire with high power LED as light source with suitable drivers etc and connecting with 3 x 1.5 sq mm multistranded PVC insulated copper conductor with PVC Conduit 20mm dia from fittings to the jucntion box and fixing to complete all as specified.
Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof IP-54 protection CPRI approved, factory fabricated, cubical panel free standing type, made out of 3.00 mm thick CRCA sheet with locking arragement , factory made powder coated as approved colour, copper bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 300 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accomodate the following items including supply and fix following items and all as specified and directed by dismantling exisiting unserviceable LT panel complete. Make of LT Panel as per CA.
Incoming:- MCCB 4 pole 200 Amp with breaking capacity 35 KA adjustable type with exended terminals -01 Nos Make: Legrand/Schneider/siemens/L&T Outgoing:- (a) MCCB 4 pole 100 Amps with breaking capacity 25KA adjustable type with extended terminals- 02 No Make: Legrand/Schneider/siemens/L&T (b) MCCB 4 pole 63 Amps with breaking capacity 16 KA adjustable type with extended terminals- 02 No's Legrand/Schneider/siemens (c) MCB TPN 40 Amps,breaking capacity 16 KA -02 Nos (d ) Current Transformers-03 Nos (e) Digital 3 phase energy meter-01 (f) LED RYB indiacator lamps-01/Set Note-: The panel must have separate Bus bar chamber, cable chamber and proper spacing must be maintained between each chamber of panel as per IS .
Supply and fixing, install, test and commissioning of LT busbar Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3.15 mm thick CRCA sheet, factory made powder coated as approved colour, Copper bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 300 Amps rating capacity RYBN insulated with sleeved insulation complete, PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accomodate the following items including supply and fix following items and all as specified and directed by dismantling exisiting unserviceable LT panel complete with LT panel made by CPRI approved manufacturer confiring to IS:-8623-1993. Note - The lay out drawing of the panel shall be got approved by the contractor from GE before panel fabrication and shall be fabricated from CPRI approved manufacture. [a] Incomer: MCCB 4 pole 200 Amps with breaking capacity 30KA adjustable type with extended terminals- 01 No's Make: Legrand/Schneider/siemens/L&T [b] Three phase 4 wire copper busbar 300 Amps rating capacity RYBN insulated with sleeved insulation complete. [c] Digital Ammeter with C.T -03 Nos [d] Digital volt Meter-01 [e] Digital 3 phase energy meter-01 [f] LED RYB indiacator lamps-01/Set
S&F of two way side outdoor wall lights 6 watt IP 65/66 surge protection 3000 K warm lights space beauty and light with havells outdoor lighting range as per existing lights complete all as specified.
Supply , installation and testing of Air circuit breaker (ACB), 800 Amps 4 Pole, 415 V, 50kA in repairs, Manual drawout type with microprocessor release complete all as specified.
Material and labour for replacement of unserviciable existing earthing with bore well earthing with the help of mechanical boring machine of 150 mm dia-30 mtr depth supply and fix 160 mm dia (O.D), UPVC pipe 6 kg/sqcm rating -06 mtr long with the help of suitable size clamp with nut bolt and washer -01 No including charcoal dust ,salt fill in bore well for earth conductivity M&L for covering of bore well with PCC (1:2:4) type B-1 / Brick masonry pit of size 45x45x45 cm complete and give the minimum earth test result below 1 ohm complete all as specified. Note :- (i) The earth pit shall be refilled by boulders free from vegetable soil.
Supply & fixing in replacement of GI tubng 50 mm dia medium grade in incl necessary fittings for lowering in borewell of depth upto 30 mtr complete all as specified.
Supply and fix in repair GI earth strip of size 32 x 6 and fixing screws etc for earth continuity conductors to test point terminal block complete all as specified.
S&F Globe LED Post Top Gate light 15 watt capacity made from engineerining grade polymer supplied along with B22 bulb white/warm white ,IP65 type fixing on wall with connecting suitable wire complete accessories complete all as specified.
S&F Lighting Poles Made from CRCA,with decorative side arms,antiquely designed for architectural street lighting applications,suitable for mounting double street fittings with LED Street light (40W capacity - 02 No.) antiquely designed aesthetically appealing landscape cum steet light,made from aluminium housing,clear polymer diffuser to provide uniform and pleasant light output IP65 Type with complete accessories specified.
Shifting of LT XLPE underground cable with proper connection in trenches / pole etc, aluminium conductor of any sizes complete all as specified. (Note:- Excavationon with Earth Work,sand cushioning will be measured under respective item of BOQ)
Supplying, errecting and fixing steel tubular swaged poles with Mild iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long) including painting with two coats of aluminium paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide including taking down old unserviceable PCC poles of any type complete all as specified. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
Supply, install, test and commissioning in repair factory made THERMOPLASTIC/HDPE CABLE JUNCTION BOXES IP 66/67 “weather proof”, with terminals for outdoor installation (with knockouts for cable entry) of with cable entry size of 10-25 sqmm with 4 No. busbar of capacity 63 Amp and MCB SP 6 Amp-1 No.of make sintex each, with flat iron clamps of size 25 x 3 mm, nuts and bolts complete including taking down complete all as specified.
S&F in replacement new generation energy saving and environmental friendly long life varsatile pressure die cast aluminium IP66 road way light fitting with high power LED as light source of capacity 60 watts (Surge protection of the light should be 10 KV )with suitable drivers etc fixed to Pole/Wall in any position including taking down complete all as specified.
S&F in replacement new generation energy saving and environmental friendly long life varsatile pressure die cast aluminium IP66 road way light fitting with high power LED as light source of capacity 90 watts (Surge protection of the light should be 10 KV )with suitable drivers etc fixed to Pole/Wall in any position including taking down complete all as specified.
S&F street light bracket fabricated from 40 mm bore galvanised iron tubing light grade, 1.2 metre long, bent to shape fixed on pole / bldg including mild steel flat iron clamps, nuts, bolts etc including taking down old bracket from existing position complete all as specified.
Supply, laying and commissioning Single Core HRFR PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volt with copper lugs connection complete all as specified and dircted of following cross sectional area :-
(a) 95 Sqmm, single core cable
(b) 120 Sqmm, single core cable
S&F copper lugs of following sizes:-
(a) 70 Sqmm
(b) 95 Sqmm
(c) 120 Sqmm
(d) 150 Sqmm
S & F MCB TPN 63 Amps C curve 415 V, 10 KA complete all as specified.
S&F in replacement of old unserviceable lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugs including crimping with crimping tools in the existing LT cable 16 sqmm to 50 Sqmm including necessary connection complete all as specified.
All as per item No 44 above but aluminium lugs of size 70 to 120 Sq mm complete all as specified.
All as per item No 44 here-in-before but aluminium lugs of size 150 to 185 Sq mm complete all as specified.
All as per item No 44 here-in-before but aluminium lugs of size 240 to 300 Sq mm complete all as specified.
Supply and fixing in replacement MPPT charge controller of Lithium base Energy efficient integrated Solar street light complete all as specified.
Supply and fixing in replacement Metal core PCB of Lithium base Energy efficient integrated Solar street light complete all as specified.
Supply and fixing in replacement Green/Red indicator of Lithium base Energy efficient integrated Solar street light complete all as specified.
Supply and fixing in replacement battery rating 12.8V suitable for 30W/32W-BIS standard of Lithium base Energy efficient integrated Solar street light complete all as specified.
S&F in repair Battery MNRE approved maintenance free tubular batteries with deep discharge 12 Volt 200 AH suitable for power supply application and working operating temperature range -10 degree centigrade to (+) 55 degree centigrade. [Make: Luminious/ Exide/Amron.
Supply & fix in repair torque motor of capacity 10 kg.cm for servo voltage stabilizer complete all as specified.
S&F in repair ON LOAD change over switch 415V with & including outdoor type sheet metal enclosures of suitable size of sheet metal including necessary angle iron stand grouted in PCC, 4 pole of capacity 100 Amps with in and out cable gland complete all as specified.
M&L for LT cable route indicator made out of PCC(1:2:4) type B-0(12.5mm graded aggregate of size 1000mm (H) x 120mm (W) x 80mm (thick), painted with Specified colur lettering synthetic enamel paint and embedded in PCC block (1:3:6) type C2 (using 40mm grade aggregate ) inuding necessary excavation for PCC block, placed complete all as specified.
Supply in repair MCCB 800 Amp,4 Pole, breaking capacity 50 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified.
Supply in repair changeover 800 Amp,4 Pole, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified.
M&L for preparation of external surfaces of steel tubular poles of any height by rubbing sand paper and cleaning, applying two coats of aluminium paint complete all as specified.
M&L for preparation of surfaces including painting of RCC poles of any height with one primer coat and one finishing coat with cement base paint complete all as specified.
S&F in repair Air Circuit Breaker 630A capacity Thermal-Magnetic DN1 ,4 pole Breaking Capacity Icu=Ics=Icw (1 sec) 415 V - 50 Hz fixed type with carry out necessary copper / Aluminium bus bar to connection as per existing bus barto make it senciable , fixed in existing panel & connecting complete all as specified.
Supply in repair MCCB 630 Amp,4 Pole, breaking capacity 50 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified.
S & F or laying galvanised steel tubing Light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing of following size 40mm bore.
(a) 40 mm bore.
(b) 50 mm bore.
M/S MAMTA CONSTRUCTIONS (BID ID -3379625)
Sadhana Enterprises (BID ID -3379468)
PD GUPTA AND COMPANY (BID ID -3386756)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .