Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.5 LAccepted-Finance | ₹9.5 L | L1 | Accepted-Finance Financial Bid Accepted |
Tender Value
₹11.0 L
EMD Value
₹21,979
Closing Date
5 Mar 2026, 3:00 pmClosed
EE(E) HMED(N) PWD,
EE(E) HMED(N) PWD, Dr. BSA Hospital Sec-6 Rohini Delhi-85.
SH Replacement of VRV System installed in Peads Ward
2026_PWD_287681_1
100/EE(E)HMED(N)/PWD/BSAH/2025 26
Open Tender
Composite Works
Percentage
30 days
SRHC Hospital Narela Delhi
Please refer the tender Documents as per NIT
12 documents required · 12 mandatory
₹0
₹21,979
7 Mar 2026
24 Feb 2026
5 Mar 2026
24 Feb 2026
5 Mar 2026
24 Feb 2026
OUTDOOR UNIT Supplying, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), minimum two compressors (with individual separate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required.
To have better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 0C. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability.
The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 5.4, Capacity > 40 and <70 ISEER 5.5, Capacity > 70 ISEER 5.6 for ECSBC Building)
For Cooling or Heating or Both
14 HP to 22 HP (Unit-A)
14 HP to 22 HP (Unit-B)
(Note:- The existing copper piping is available at site and shall be utilized for installation & The new outdoor units shall be installed on the terrace of the building. All arrangements for loading, unloading, and lifting of the outdoor units, including crane arrangements wherever required, shall be made by the agency at their own cost. Nothing extra shall be paid on this account.)
INDOOR UNIT Supplying, Installation, Testing and Commissioning of following minimum capacity High wall type Indoor unit equipped with and comfort washable synthetic media prefilter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc.,
suitable for operation on 230 V ± 10%, 50 Hz, single phase AC supply, complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature. (Make will be same as of Outdoor)
(Note:- The existing copper piping is available at site and shall be utilized for installation.)
INSULATION ON EXISTING PIPE Supplying, laying, fixing, testing and commissioning of following thickness closed cell elastrometric nitrile rubber of class 'O' applied by suitable adhesive , as per specifications and as required complete in all respect
Dismantling of following material and buy back of the same material on as where is basis.
VRV Outdoor Unit of 22HP.
VRV Indoor Unit of 2.0 TR.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.58 MB
NIT.pdf
Tender Documents • 3.57 MB
BOQ_381304.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .