| 1.00 | Supply, installation, testing and commissioning of copper wound step-down distribution transformer, outdoor, floor mounted type, suitable for 11 kV / 433 V, 3 phase, 4 wire, 50 Hz AC system, of capacity 63 kVA , oil immersed, naturally cooled ONAN (Oil Natural Air Natural) type, complete with all standard accessories, fittings and mounting arrangements. The transformer shall conform to latest amendments of IS 1180 (Part-1):2014, BIS certified, and BEE 5-star rated (latest applicable notification). Transformer shall be suitable for outdoor operation under Indian climatic conditions.
The transformer shall have:
HV side: Delta connected
LV side: Star connected with neutral brought out
Vector group: DYN-11
Tapping: Off-load tap changer on HV side with taps of ±2.5%, ±5%, ±7.5% in steps of 2.5%
Cooling: ONAN with radiators/cooling fins
Technical requirements
i. Winding: Electrolytic grade copper
ii. Insulation: As per IS standards
iii. Percentage impedance: As per IS 1180
iv. Losses: As per Energy Efficiency Level-2 / latest BEE norms
v. Temperature rise limits: As per IS 1180
vi. Vector group: DYN-11 mandatory
vii. Neutral brought out and suitable for solid earthing
Accessories & fittings
i. Cable end box on HV side suitable for 95 Sqmm 3 core (11000 Volts) size XLPE cable. | 1 | Each | 4,00,000 ₹4,00,000 Lowest | 4,75,000 ₹4,75,000 |
| 1.01ii. Cable end box on LV side suitable for 95 Sqmm 3.5 core (1100 Volts) size XLPE cable with cable glands. iii. Conservator with oil level indicator (min/max marking). iv. Silica gel dehydrating breather (first filling included). v. Cooling radiators / fins. vi. Explosion vent / pressure relief device (PRD). vii. Oil temperature indicator (OTI) with maximum reading and reset. viii. Thermometer pocket. ix. Oil filling hole with cap. x. Oil drain valve with sampling facility. xi. Air release valve. xii. Earthing terminals: Minimum 2 nos. for body earthing .Minimum 2 nos. for neutral earthing (separate bushing) xiii. Lifting lugs and pulling lugs. xiv. HV bushings with arcing horns. xv. LV bushings (porcelain/epoxy as per standard). xvi. Rating plate (as per IS) and terminal marking plate. xvii. Danger plate and phase indication markings. xviii. First filling of new, unused, ISI marked transformer oil conforming to IS 335. Notes: (i) The drawing of transformer shall be approved by accepting officer on receipt of request from the contractor through GE. (ii) The transformer shall be tested as per IS for all routine tests in the factory premises and reports will be deposited with purchase voucher. (iii) Factory inspection and testing of the transformer shall be carried out in the presence of the representative of the Accepting Officer/SEI/IEM, and all associated charges shall be borne by the contractor. | |||||
| 2.00 | Supply, Installation, Commissioning of transformer of capacity 200 KVA step down outdoor type Copper Wounded ONAN Cooling 11/0.433 KV (at no load) AC 3 Phase 50 Hz on secondary side double wounded oil immersed naturally all air cooled with external tubes/radiator, delta connected as on primary and star connected with neutral brought on secondary. The maximum temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/LV winding when measured by the resistance method after continuous full load run in ambient temperature the transformer shall confirming to IS 2026, 1997 and comprising of following accessories :-
(a) 01 No Cable end box on HV side consisting of with 03 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3 Core 120 Sqmm including cable joint complete adopter box
(b) 01 No cable end box on LV secondary side consisting of 04 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3.5 Core 185 Sqmm including cable joint complete adopter box
(c) Oil conservator with filter type drain valve and oil level gauge.
(d) Dehydrating breather with first filling of dehydrating agent.
(e) Explosive vent.
(f) Thermometer Pocket.
(g) Two earthing terminal on tank body to facilitate fixing of 32x6mm GI Strip.
(h) One No thermometer dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge max reading panted terminal.
(j) Rating plate with terminal plate.
(k) Oil drain filter valve.
(l) Oil filling hole on top cover with plug.
(m) Air release valve/plug.
(n) 4 Nos plain solid cast steel detachable rollers.
(o) Extra bushing for neutral out side the cable box providing independent earthing for neutral.
(p) First fill of transformer oil confirming to relevant IS and tested upto 60KV dielectric strength. | 2 | Each | 8,50,000 ₹17,00,000 | 6,10,000 ₹12,20,000 Lowest |
| 3.00 | All as per item No. 2 here in before but transformer of 100 KVA capacity. | 2 | Each | 5,00,000 ₹10,00,000 | 3,50,000 ₹7,00,000 Lowest |
| 4.00 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor, of size 95 sq mm 3 core, complete all as specified and directed by Engr-in-charge. | 90 | RM | 1,000 ₹90,000 Lowest | 1,260 ₹1,13,400 |
| 5.00 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, of size 95 sq mm 3.5 core, complete all as specified and directed by Engr-in-charge. | 105 | RM | 550 ₹57,750 Lowest | 800 ₹84,000 |
| 6.00 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, of size 70 sq mm 3.5 core, complete all as specified and directed by Engr-in-charge. | 190 | RM | 440 ₹83,600 Lowest | 640 ₹1,21,600 |
| 7.00 | Excavation in trenches in hard/dense soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level and for foundation, complete all as specified and directed by Engr-in-charge. | 46.39 | Cum | 650 ₹30,153.5 | 50 ₹2,319.5 Lowest |
| 8.00 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by Engr-in-charge. | 32.98 | Cum | 100 ₹3,298 | 50 ₹1,649 Lowest |
| 9.00 | Removing surplus excavated material to a distance not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point complete all as specified and directed by Engr-in-charge. | 32.36 | Cum | 100 ₹3,236 | 50 ₹1,618 Lowest |
Tender Value
₹63.3 L
EMD Value
₹1.2 L
Closing Date
11 Jun 2026, 6:00 pmClosed
CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS, PIN 914133, C/O 56 APO
SPL REPAIR OF TRANSFORMER AND VOLTAGE STABILIZER AGAINST BER EQPT AT DIFFERENT LOCATIONS, REPLACEMENT OF 02X HP CENTRIFUGAL PUMP SET WITH ALLIED INFRA AGAINST BER EQPT AND PROVN OF 63 KVA TRANSFORMER WITH CONNECTED ACCESSORIES UNDER GE 969 EWS
2026_MES_765320_1
CWEK-____/969 EWS/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 969 EWS
Class C and above and Category b (ii)
7 documents required · 7 mandatory
₹1,000
GE 969 EWS
₹1.2 L
28 Jul 2026
14 May 2026
19 Jun 2026
14 May 2026
11 Jun 2026
5 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of copper wound step-down distribution transformer, outdoor, floor mounted type, suitable for 11 kV / 433 V, 3 phase, 4 wire, 50 Hz AC system, of capacity 63 kVA , oil immersed, naturally cooled ONAN (Oil Natural Air Natural) type, complete with all standard accessories, fittings and mounting arrangements. The transformer shall conform to latest amendments of IS 1180 (Part-1):2014, BIS certified, and BEE 5-star rated (latest applicable notification). Transformer shall be suitable for outdoor operation under Indian climatic conditions.
The transformer shall have:
HV side: Delta connected
LV side: Star connected with neutral brought out
Vector group: DYN-11
Tapping: Off-load tap changer on HV side with taps of ±2.5%, ±5%, ±7.5% in steps of 2.5%
Cooling: ONAN with radiators/cooling fins
Technical requirements
i. Winding: Electrolytic grade copper
ii. Insulation: As per IS standards
iii. Percentage impedance: As per IS 1180
iv. Losses: As per Energy Efficiency Level-2 / latest BEE norms
v. Temperature rise limits: As per IS 1180
vi. Vector group: DYN-11 mandatory
vii. Neutral brought out and suitable for solid earthing
Accessories & fittings
i. Cable end box on HV side suitable for 95 Sqmm 3 core (11000 Volts) size XLPE cable. | 1 | Each | - | - |
| 1.01 | ii. Cable end box on LV side suitable for 96 Sqmm 3.5 core (1100 Volts) size XLPE cable with cable glands.
iii. Conservator with oil level indicator (min/max marking).
iv. Silica gel dehydrating breather (first filling included).
v. Cooling radiators / fins.
vi. Explosion vent / pressure relief device (PRD).
vii. Oil temperature indicator (OTI) with maximum reading and reset.
viii. Thermometer pocket.
ix. Oil filling hole with cap.
x. Oil drain valve with sampling facility.
xi. Air release valve.
xii. Earthing terminals: Minimum 2 nos. for body earthing .Minimum 2 nos. for neutral earthing (separate bushing)
xiii. Lifting lugs and pulling lugs.
xiv. HV bushings with arcing horns.
xv. LV bushings (porcelain/epoxy as per standard).
xvi. Rating plate (as per IS) and terminal marking plate.
xvii. Danger plate and phase indication markings.
xviii. First filling of new, unused, ISI marked transformer oil conforming to IS 335.
Notes: (i) The drawing of transformer shall be approved by accepting officer on receipt of request from the contractor through GE.
(ii) The transformer shall be tested as per IS for all routine tests in the factory premises and reports will be deposited with purchase voucher.
(iii) Factory inspection and testing of the DG set shall be carried out in the presence of the representative of the Accepting Officer/SEI/IEM, and all associated charges shall be borne by the contractor. | - | - | - | - |
| 2 | Supply, Installation, Commissioning of transformer of capacity 200 KVA step down outdoor type Copper Wounded ONAN Cooling 11/0.433 KV (at no load) AC 3 Phase 50 Hz on secondary side double wounded oil immersed naturally all air cooled with external tubes/radiator, delta connected as on primary and star connected with neutral brought on secondary. The maximum temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/LV winding when measured by the resistance method after continuous full load run in ambient temperature the transformer shall confirming to IS 2026, 1997 and comprising of following accessories :-
(a) 01 No Cable end box on HV side consisting of with 03 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3 Core 120 Sqmm including cable joint complete adopter box
(b) 01 No cable end box on LV secondary side consisting of 04 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3.5 Core 185 Sqmm including cable joint complete adopter box
(c) Oil conservator with filter type drain valve and oil level gauge.
(d) Dehydrating breather with first filling of dehydrating agent.
(e) Explosive vent.
(f) Thermometer Pocket.
(g) Two earthing terminal on tank body to facilitate fixing of 32x6mm GI Strip.
(h) One No thermometer dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge max reading panted terminal.
(j) Rating plate with terminal plate.
(k) Oil drain filter valve.
(l) Oil filling hole on top cover with plug.
(m) Air release valve/plug.
(n) 4 Nos plain solid cast steel detachable rollers.
(o) Extra bushing for neutral out side the cable box providing independent earthing for neutral.
(p) First fill of transformer oil confirming to relevant IS and tested upto 60KV dielectric strength. | 2 | Each | - | - |
| 3 | All as per item No. 2 here in before but transformer of 100 KVA capacity. | 2 | Each | - | - |
| 4 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor, of size 95 sq mm 3 core, complete all as specified and directed by Engr-in-charge. | 90 | RM | - | - |
| 5 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, of size 95 sq mm 3.5 core, complete all as specified and directed by Engr-in-charge. | 105 | RM | - | - |
| 6 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, of size 70 sq mm 3.5 core, complete all as specified and directed by Engr-in-charge. | 190 | RM | - | - |
| 7 | Excavation in trenches in hard/dense soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level and for foundation, complete all as specified and directed by Engr-in-charge. | 46.39 | Cum | - | - |
| 8 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by Engr-in-charge. | 32.98 | Cum | - | - |
| 9 | Removing surplus excavated material to a distance not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point complete all as specified and directed by Engr-in-charge. | 32.36 | Cum | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.41 MB
Tender09.pdf
Tender Documents • 1.52 MB
BOQ_857153.xls
BOQ • 0.31 MB
DRAWINGS09.pdf
Additional Documents • 0.56 MB
POSTPOND09.pdf
PDF • 0.18 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].