Loading…
Loading…
Tender Value
₹40.1 L
EMD Value
₹40,122
Closing Date
14 Aug 2026, 11:00 amClosed
Repair, Rectification of fire protection system and obtaining fire safety certificate at NBCC imperia, Bhubaneswar Odisha
NBCC/SBG/ODISHA/NIT/26-27/38
NBCC/SBG/ODISHA/NIT/26-27/38
Open Tender-Domestic
Fire & Safety
Odisha
₹2,950
₹40,122
14 Aug 2026
31 Jul 2026
14 Aug 2026
14 Aug 2026
ABSTRACT OF COST
Sl.No. DESCRIPTION DSR-2025 (AMOUNT) TOTAL
REPAIR, RECTIFICATION OF FIRE
PROTECTION SYSTEM AND
CERTIFICATE AT NBCC IMPERIA ,
BHUBANESWAR ODISHA
GRAND TOTAL A 40,12,186.89
GRAND TOTAL A 40,12,186.89
Digitally signed by JAYA
BOQ FOR REPAIR, RECTIFICATION OF FIRE PROTECTION SYSTEM AND OBTAINING FIRE SAFETY CERTIFICATE AT NBCC IMPERIA , BHUBANESWAR ODISHA
Item No. Rate (Rs.) BOQ Amount (Rs.)
S. No. Item Description Unit Qty.
(DSR-2025- DSR Non - DSR DSR Non- DSR
FIRE FIGHTING SYSTEM - -
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to
IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges,
1 tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable
clamp/support frame and painting with two or more coats of synthetic enamel paint of
required shade complete as required
Providing and fixing 25mm Air release valve as per IS:14845 ISI Marked of approved
18.18 DSR Providing & Fixing Ball Valve (Brass) of approved quality, High And Low Pressure With
2023 Plastc Float Complete
2023 25 mm dia
Supplying and fixing single headed internal hydrant valve with instantaneous
Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked
4 27.9.2 conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as Each 3.00 6,632.00 19,896.00 -
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office
red, conforming to IS 884 complete with the following as required. (a) 20 mm nominal
5 27.17 internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 (b) 20 - -
mm nominal internal dia gun metal globe valve & nozzle. (c) Drum and brackets for
fixing the equipmets on wall. (d)Connections from riser with 25 mm dia stop gun metal
valve & M.S. Pipe and socket.
Providing and fixing in position industrial type pressure gauges with gun metal / brass
valves complete etc. as required.
Providing, storing, handling, shifting, installation, testing and commissioning of portable
7 NON DSR - -
fire extinguishers as described below
4.5 Kg carbon dioxide extinguisher IS marked with high pressure discharge tube , horn,
controlvalve , CCE approved cylinder .
7.2 NON DSR 5/6 Kg Mono ammonium Phosphate (ABC) type cartridge operated extingusher Nos. 44.00 2,384.87 - 1,04,934.28
7.3 NON DSR 2 Kg Mono ammonium Phosphate (ABC) type cartridge operated extingusher Nos. 3.00 1,355.04 - 4,065.12
7.4 NON DSR 50 kg. Mech. Foam type extinguisher Nos. 1.00 9,214.28 - 9,214.28
7.5 NON DSR 22.5 kg. CO2 Fire extinguisher Nos. 2.00 20,054.61 - 40,109.22
Providing and replacing broken, cracked, damaged, or missing glass of Fire Hose
Cabinet, including removal of existing glass, supply and fixing of new clear/toughened
8 NON DSR safety glass of approved thickness, cutting to required size, fixing with rubber NOS 10.00 1,090.65 - 10,906.50
beading/gasket, clips, sealant, cleaning, and making the cabinet fully functional,
complete Complete in all respect to the entire Satisfaction of NBCC/Client
Providing and replacing broken, cracked, damaged, or missing Door Fire Hose Cabinet,
including removal of existing glass, supply and fixing of new clear/toughened safety
9 NON DSR glass of approved thickness, cutting to required size, fixing with rubber beading/gasket, NOS 3.00 2,225.00 - 6,675.00
clips, sealant, cleaning, and making the cabinet fully functional, complete Complete in all
respect to the entire Satisfaction of NBCC/Client Complete in all respect to the entire
Satisfaction of NBCC/Client
FIRE ALARM SYSTEM - -
Supplying, installation, testing and commissioning of micro processor based intelligent
addressable main fire alarm panel, central processing unit with the following loop
modules and capable of supporting not less than 240 devices (including detectors) and
minimum 120 detectors per loop and loop length up to 2 km, network communication
card, minimum 320 character graphics/ LCD display with touch screen or other keypad
and minimum 4000 events history log in the non volatile memory (EPROM), power
10 28.2.1 supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free - -
batteries with automatic charger.
The panel shall have facility to connect printer to printout log and facility to have
seamless integration with analog/digital voice evacuation system (which is part of the
schedule of work under SH: PA System) and shall be complete with all accessories . The
panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP
complete as per specifications.
Supplying, installation, testing & commissioning of repeater panel with 320 character/
11 28.2.3 Touch screen LCD display with Each 1.00 1,13,734.00 1,13,734.00 -
inbuilt reset, acknowledge and silence switches complete as required.
12 28.2.4 Supplying, installation, testing & commissioning of intelligent analog addressable Each 100.00 3,004.00 3,00,400.00 -
photothermal detector complete with mounting base complete as required
Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC
13 28.1.1 with rate of rise cum fixed temperature (dual thermistor) type with mounting base Each 6.00 1,136.00 6,816.00 -
complete with all connection etc. as required
Supplying, installation, testing & commissioning of addressable beam detector with short
14 28.2.12 circuit isolator (inbuilt or separate) complete with emitter and receiver including Each 2.00 78,525.00 1,57,050.00 -
connections with remote test features etc complete as required
Supplying, installation, testing & commissioning of addressable manual call point
complete as required
Supplying, installation, testing & commissioning of addressable fire control
module/monitor module complete as required
Supplying, installation, testing & commissioning of fault isolator complete with base as
Supplying, installation, testing & commissioning of response indicator on
18 28.2.5 surface/recessed MS Box having two LED, metallic cover complete with all connections Each 100.00 306.00 30,600.00 -
etc as required
Supplying, installation, testing & commissioning of addressable horn cum strobe
complete as required
CABLING & WIRING - -
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with
20 28.5.1 annealed copper conductor having glass mica fire barrier tape covered by an extruded Meter 700.00 386.00 2,70,200.00 -
layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner
bedding, steel wire armouring & LSZH outer sheath complete as required
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor,
21 1.17 single core cable in
the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit along with
22 1.21 accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
Repair and Refurbishment of Fire Pumping System, comprising Two (2) Main Electric Fire
Pumps, One (1) Standby Diesel Engine Fire Pump, One (1) Jockey Pump, and Water
Curtain Pumps, including inspection, dismantling, repair/replacement of worn-out
components, reassembly, alignment, testing, commissioning, and restoration to
23 NON DSR satisfactory operating condition, complete in all respects. Job 1.00 2,20,000.00 - 2,20,000.00
Comprehensive maintenance including routine inspection, preventive maintenance,
testing, servicing of diesel engine, pump, batteries, controller, cooling system, fuel
system, alignment, lubrication,Oil Change, operational testing, documentation, and
rectification of minor faults complete as required for satisfactory operation Complete in
all respect to the entire Satisfaction of NBCC/Client.
Refilling, of FM-200 Fire Extinguisher/Cylinder of specified capacity, including, leak
24 NON DSR testing, weighing, labeling, and all incidental works complete as required Complete in all Nos. 6.00 35,632.00 - 2,13,792.00
respect to the entire Satisfaction of NBCC/Client
Providing and replacing damaged, worn-out, cracked, leaking, or expired discharge
25 NON DSR hose/pipe assembly of FM-200 Fire Extinguisher, including dismantling of existing Nos. 1.00 3,500.00 - 3,500.00
hose/pipe, supply and installation of new approved hose/pipe assembly with couplings,
seals, adapters,Complete in all respect to the entire Satisfaction of NBCC/Client
13.56 DSR Painting Two Coats With Synthitic Enamel Paint of Approved Colour & Shade of Approved
2023 Brand And Manufacture over a priming coat of Approved Steel Pipe
150 mm Dia Pipe Meter
100 mm Dia Pipe Meter
Providing and replacing the damaged, missing, broken, or deteriorated cover cap of
Twin Outlet Landing Valve installed in the fire-fighting system, including removal of
27 NON DSR existing cover cap, supply and fixing of new approved cover cap with chain, fastening Nos. 10.00 587.00 - 5,870.00
accessories, cleaning, testing, and making the valve assembly fully operational,
Complete in all respect to the entire Satisfaction of NBCC/Client
Providing and replacing the defective, worn-out, hardened, leaking, or damaged gasket
28 NON DSR of 63/80 NB Landing Valve in the fire-fighting system, including dismantling of valve Nos. 20.00 94.99 - 1,899.80
components as required, removal of existing gasket, supply and installation of new
approved gasket, reassembly, testing, and commissioning complete in all respects
Repair, Rectification, replacement of exisiting Fire Fighting Control Panel with all
accessories complete in all respect along with automatic system controller to control
29 NON DSR operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in Nos. 1.00 65,152.30 65,152.30
sequence as per specification consisting of relays, timers. Sensors, annunciation window
for fault indication, complete as per specification and to the entire satisfaction of
Engineer Incharge
Repairing & Servicing for the existing Ventilation System Such as Lift Lobby
Pressurization along with Basement Ventilation as per Fire Norms Complete in all respect
to the entire Satisfaction of NBCC/Client including providing labor, materials, tools, and
32 NON DSR equipment for dismantling and replacing damaged, torn, worn-out, or deteriorated Set 1.00 2,65,000.00 - 2,65,000.00
canvas/flexible cloth connection installed between Air ductwork, including supply and
fixing of new fire-retardant canvas cloth, fastening accessories, sealing, and testing
Complete in all respect to the entire Satisfaction of NBCC/Client
Integration with Fire Suppression System, Access Control system, Lift & HVAC etc.
33 NON DSR complete as per Technical Specification, drawings and directed by Employer/Employer Set 1.00 2,75,000.00 - 2,75,000.00
Representative Complete in all respect to the entire Satisfaction of NBCC/Client
Supply, Installation, testing and Commissioning power supply module. The multifunction
power supply shall provide dual output connection facilities to power .Battery Having UPS
6000VA And Battery 150 H Capacity And Complete in all respect to the entire
Satisfaction of NBCC/Client.
Providing and fixing in position the signages " EXIT ORDER" it should contain the
following matter on 3mm thick "Opaque" PVC foam board of computerized cut, PVC
35 NON DSR reflective with inside green light self adhesive vinyle painted foam board of 3' x Nos 20.00 7,208.00 - 1,44,160.00
4'.Complete in all respect to the entire Satisfaction of NBCC/Client
Total Amount 40,12,186.89
Total Amount 40,12,186.89
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
PMC_GCC_2026 with Amendment01.pdf
Tender Document
SCC.pdf
Tender Document
BOQ NBCC IMPERIA .pdf
Tender Document
Scope of work.pdf
Tender Document
List of Approved Makes.pdf
Tender Document
Fire fighting plan.pdf
Tender Document
Schematic drawing.pdf
Tender Document
Technical Specification.pdf
Tender Document
TECHNICAL CIRCULAR.pdf
Tender Document
corrigendum-5401-Corrigendum01.pdf
pdf • 0.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .