| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹2.7 LAccepted-Finance | L-1 | Accepted-Finance 1st Lowest Bidder | |
| 2 | L-2₹2.8 L+₹15,600 (5.84%)Rejected-Finance | L-2 | Rejected-Finance 2nd Lowest Bidder | |
| 3 | L-3₹4.0 L+₹1.3 L (48.2%)Rejected-Finance | L-3 | Rejected-Finance 3rd Lowest Bidder | |
| 4 | L-4₹4.4 L+₹1.7 L (64.4%)Rejected-Finance | L-4 | Rejected-Finance 4th Lowest Bidder | |
| 5 | L-5₹4.6 L+₹1.9 L (71.9%)Rejected-Finance | L-5 | Rejected-Finance 5th Lowest Bidder |
Tender Value
₹4.0 L
EMD Value
₹5,000
Closing Date
3 Jul 2025, 5:00 pmClosed
Superintending Engineer
Electricity Transmission Circle, UPPTCL, Pareshan Bhawan , Mohaddipur , Gorakhpur
WORK OF REPLACEMENT OF GASKETS OF 40 MVA TRANSFORMER -I (KANOHAR MAKE) AND CENTRIFUSING OF TRANSFORMER OIL AND OTHER ASSOCIATED WORK AT 132 KV S/S SALEMPUR UNDER ETD, DEORIA
2025_UPTCL_1052106_1
Very Short Term E-Tender No. 14-ETC(G)/2025-26
Open Tender
Electrical Works
Item Rate
60 days
Gorakhpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE, ETC, Gorakhpur
₹5,000
17 Jul 2025
26 Jun 2025
4 Jul 2025
26 Jun 2025
3 Jul 2025
26 Jun 2025
Amount
Opening of Jumpers of HV / LV side , removal of earthing strips from bushing at 132 KV S/s Salempur.
Dismantling of 40 MVA T/F-I accessories including radiator , bushing , bucholz relay , oil pipe line from conservator tank to main tank , oil pipe line to OLTC and surge relay conservator tank at 132 KV S/s Salempur.
Complete drain out of T/F oil from the existing 40 MVA T/F-I into empty oil drum / oil tanker.
Replacement of Old & damaged gaskets of 40 MVA T/F including the top cover/ HV, LV bushing / Radiator / Pipe Line of Conservator / Conservator tank / Tap changer / valves of T/F by providing and fixing of new gaskets as per existing size made of rubberized cork sheet Kotika / Turborze/ Nu cork brand grade 07 . Also , replacement of broken glass of conservator tank indicator both side if required. All materials, T&P provided by contractor at his own cost.
Cleaning of core and winding by T/F oil removed the sulg from bottom.
Complete erection of 40 MVA T/F-I by erection of radiator , conservator tank , bushing with its turrets (if available) connecting of all oil pipelines , erection of cooling fans making control cable connection, buchholz relay etc. for completing the work , topping of T/F oil and final oil filling in tank , radiator, conservator tank and all other associated work for complete of work.
Centrifusing of complete T/F oil in T/F by connecting centrifusing pipe circulating the T/F oil through centrifusing machine to be provided by the contractor and taking the BDV value of the periodically till the required value is achieved T/F oil approx. 15 KL.
Carriage of oil tanker 20 KL for the centrifusing of T/F oil including loading , unloading & carriage approx. 110 Km. at 132 KV S/s Salempur and return back after centrifusing work.
Provide Silica Gel blue ( 30 Kg) indicating hydroscopic crystal size 10-12 mm of good quality and filled in the breather of the Transformer.
Jumpering of 40 MVA T/F HV / LV side by tighten of conductor with connector and complete all job satisfactorily for successful work.
Replacement of damaged glass and its rubber packing of T/F marshalling box and T/F 33 KV CB as per sample.
Technocrat Electrical (BID ID -5287901)
Perfect Power Transformer Associates (BID ID -5287550)
Meena Elect & Engg. Works (BID ID -5287854)
Gupta Elect and Engg Works (BID ID -5287857)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .