Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹79.0 CrAccepted-AOC | ₹79.0 Cr Quoted ₹84.5 Cr | L1 | Accepted-AOC As per decision of PC-WTD |
| 2 | L2₹87.3 CrRejected-AOC SATNA MADHYA PRADESH 485005 | SATNA | MADHYA PRADESH | 485005 | ₹87.3 Cr | L2 | Rejected-AOC As per decision of PC-WTD |
| 3 | Rejected-Technical D 90 OKHLA INDUSTRIAL AREA PHASE 1 NEW DELHI NEW DELHI DELHI 110020 | SOUTH EAST DELHI | DELHI | 110020 | - | - | Rejected-Technical Techno-commercial disqualified |
Tender Value
₹66.6 Cr
EMD Value
₹1.3 Cr
Closing Date
1 Aug 2024, 4:00 pmClosed
SE (AUTOMATION, N/M, SP)
VIDYUT BHAWAN, JYOTI NAGAR, JAIPUR
Construction of 132/33 kV, 2x80 MVA GIS Substation at Pratap Nagar (Distt.-Jaipur) alongwith associated transmission lines including survey, supply of all equipments/materials, erection (including civil works), testing and commissioning
2024_RRVPN_392265_1
RVPN/EHV/ASP/TN-119
Open Tender
Electrical Works
540 days
JAIPUR
Please refer Tender documents.
4 documents required · 4 mandatory
₹23,600
SR AO (EA AND CASH) RVPN
₹1.3 Cr
JAIPUR
7 Oct 2024
11 Jun 2024
1 Aug 2024
11 Jun 2024
1 Aug 2024
10 Jul 2024
21 Jun 2024
SUPPLY - 132 KV GIS SUBSTATION AT PRATAP NAGAR
SUBSTATION EQUIPMENTS
Power Transformer:
Power Transformer: 132/33 kV, 80 MVA Transformer with all accessories and 10% extra oil in non-returnable steel drums
RTCC Panel fitted with Transformer Monitoring cum Tap changer control System (TCS) alongwith associated acessories complete in all respect.
132 kV Indoor GIS Switchgear Equipments
145kV, 1250A, SF6 gas insulated Transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer, bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, surge arrestors, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting Power Transformer (Air/ XLPE) with GIS through XLPE cable with cable termination enclosure and other accessories etc. to complete transformer bay module as indicated in the SLD/ Layout of substation and as per technical specifications.
145kV, 1250A, SF6 gas insulated Feeder bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, surge arrestors, PT , SF6 gas monitoring system for complete bay, local control cubicle, gas insulated terminal connection for connecting XLPE cable with cable termination enclosure and other accessories with GIS etc. to complete feeder bay module as indicated in the SLD/ Layout of substation and as per technical specifications.
Double Bus Arrangement, 145kV, 3 Phase, SF6 gas insulated metal enclosed 2500A bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switch, local control cubicle (if required), SF6 gas monitoring system etc. for the complete bus as indicated in the SLD/ Layout of substation and as per technical specifications.
145kV, 2500A, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, disconnectors with safety earthing switches, Local control cubicle, SF6 gas monitoring system for complete bay etc. as indicated in the SLD/ Layout of substation and as per technical specifications.
Suitable Capcity EOT Crane for GIS Hall/ Building
Ventilation system for GIS Hall/ Building (as per technical specification)
36 kV Metal Clad GIS Indoor Switchboard
Metal clad Double Bus Indoor GIS Switchboard Including 2 No. Incomer Transformer Feeders, 7 No. Outgoing Feeders and 1 No. bus-Coupler (as per SLD) alongwith all associated accessories CTs. PTs, Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 3000A, 31.5 kA Class] alongwith 0.2 S class AC Static HT-TVM TOD type Energy Meter
Cable Termination/ Plug for terminating in Metal clad switchgear panels for 6 Nos. of Outgoing Feeder panels (for 2 Nos. 3-Phase Outgoing cable circuit in each) from each (Normally cable sizes is 300 Sq. mm or more and exact size shall be decided with the distribution company during detailed engineering)
33 kV XLPE Cables & Accessories
3 C, 95 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3]for connecting the HV side of Substation Transformer to O/G of 36 kV Metal Clad GIS Switchgear
1C, 1000 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. (This include 12 lengths of cable with suitable Outdoor & Indoor [12+12] end Terminations)
C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
132 kV C&R Panel Type SAS-FCA
133 kV C&R Panel Type SAS-FRA
132 kV C&R Panel Type SAS-BCRA
132 kV C&R Panel Type SAS-TCRA
132 kV C&R Panel Type SAS-BBRA
Substation SAS Netorking Panel SAS-NW
Station HMI [Industrial grade Computer with Approx. 21"TFT monitor as per specification requirements]
Station HMI (Hot Standby)[Industrial grade Computer with Approx. 21"TFT monitor as per specification requirements]
HMI View Node[Industrial grad Computer with Approx. 21"TFT monitor as per specification requirements]
DR Work Station[Industrial grade Computer with Approx. 21"TFT monitor as per specification requirements]
A3 Size Color Laser Printer
Dot Matrix Printer
One Remote Workstation with HMI[Industrial grade Computer with 21"TFT monitor as per specification requirements] & Laser Printer (A4 Size) for RCC
Hardware Gateways (for data transmission to RCC & SLDC)
Modems (both sending and Receiving End) for communication to RCC & Sub SLDC[if required as Communication Equipments are proposed]
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
Substation LAN Commnication Infrastructure
Ethernet Switches:
132 kV Side C&R and Network Panels:16 Nos.{12 Port (8 Nos. 10/100 BaseTX + 4 No. 10/100/1000 Base FX)}, 2 Nos. {24 Port 10/100 Mbps TX + 4 port 10/100/1000 Base FX}]
33 kV Side C&R Panels: 2 Nos.{16 Port (12 Nos. 10/100 BaseFX + 4 No. 10/100/1000 Base FX)}
Other Items:
Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the substation LAN as per specification requirements.
Inverter (3 kVA Capacity) to be operatable on 230VAC and 220 VDCas per availability of supply (Normally on AC)
Inverter (1 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC)
132 kV XLPE Cable & Termination
500 Sq. mm 132 kV XLPE Cable
132 kV Outdoor Cable Termination for XLPE to Air Termination on HV Side of Power Transformer
132 kV GIS Termination for XLPE Cable
Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase
Surge Arresters
132 kV Class of 120 kV rating LA's with grading ring discharge counter with mili ammeter
33kV class of 30kV rating LAs
33kV/415V, 250kVA station transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
Batteries & Battery Charger
Batteries (Sizing shall be as per requirement of technical specification)
220 V [Min 400 AH]
48 V [Min 300 AH]
Battery Charger System
220 V Float and Boost
48 V Float and Boost
Lighting System
Outdoor Lighting & other Works
Lighting Fixture Type -SF2 as per Specification
Lighting Fixture Type -EEC2 as per Specification
Lighting Fixture Type -SF1 as per Specification
Lighting Fixture Type -EEC1 as per Specification
Emergency Lighting Type-PF
Type-RO, 15A, 240V: Outdoor Receptacle 2 pole, 3-pin type
Type-RP, 63A, 415V : Interlocked switch socket outdoor Receptacle
Hot Dip Galvenized Octogonal Lighting Poles (12 m)
Street Lighting Type-EEA for mounting on above Poles
Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast complete with all controgears and accessories, items etc.
Lighting Panel Type ACP-3 as per technical specification
Indoor Lighting & Other Works
Electrification
Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, GIS Hall and administrative office building as per the requirements of the specifications
Illumiation
Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
Indoor Lignting Panels
Lighting Panel (Indoor) Type ACP-1 as per technical specification
Lighting Panel (Indoor) Type DCP as per technical specification
Wall mounted fans Approx. 400 mm sweep
Approx. 1400mm sweep with electronic Step regulator
Exhaust Fans
Fire Fighting System
Nitrogen Injection Fire Protection System for Power Transformer complete in all respects.
Fire Fighting equipment with necessary mounting stands.
DCP Type
Carbon di oxide type – 4.5 Kg
Foam Type- Around 9 Liters
Sand type
i) GI Buckets Around 9 liters capacity
ii) Steel Stands for four buckets
Fire Detection and Alarm System
Siren along with all accessories as specified in technical specification
Microprocessor based Fire Detection & Alarm System alongwith the Desktop, System and application software for geographic monitoring and detection of fires, display of events and alarms etc. as specified in technical specification
Photo-electric Detectors, Smoke Detectors, Heat Detectors, Linear Heat Sensing Cables, Manual Call Points etc. Control Room, GIS Hall, Office Building, Store, Testing Laboratory etc.
Power & Control Cables for fire detection & alarm system
Air Conditioning System
High Wall Split AC units of 2 TR Capacity complete with Indoor, Outdoor Units and required accessories, Stablizers etc.
Substation Structures/Supports & Switchyard Erection
145 kV GIS Switchgear Interconnections for Incomer Line (from incoming 132 kV XLPE Cable for which Cable Termination Kit with support to be supplied by Cable System Contractor) complete with all necessary enclosure support, clamps, connectors and other accessories for successful connection to GIS Switchgear as per Layout of the substation.
145 kV GIS Interconnections for Transfomer Bay complete with all necessary enclosure support, clamps, connectors, other accessories for successful connection to GIS Switchgear as per Layout of the substation.
33 kV Transformer Bay (from Power Transformer LV Terminals to SA, Isolator/ PI for Cable Termination) [Complete with Three Phase Al. (50 mm. Size) tubular conductor, Clamps (rigid/flexible/expansion type), Connectors, Straight/V/Y Taps, nut-bolts and other accessories] as per Layout of the substation.
Tubular/ Lattice Support for Equipments [Complete with all accessories]
132 kV Side
132 kV Cable Termination (XLPE to Air termination for Power Transformer)
132 kV side Surge Arrestor
Isolators
33 kV Side
Isolators (3 Phase) with Single Earth Switch
33 kV XLPE Cable Termination support structure for Connecting to 33 kV Side of 132/33 kV Transformer including 33 kV Class of 30 kV rating LAs (3 Nos.), Supporting PI String (3 Nos.), nut bolts, fixing accessories etc. as per drawing appended in Section-IV of specification
Lightning Cum Lighting Masts. Approximate Unit Weight Appox 3.5 MT for each Mast
Earth Wire
7/3.15 mm Galvanized Steel wire
Clamps (Suspension/Tension), Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
Other Suspension/T Clamps & Power/Terminal Connectors [not covered in respective equipments/ switchgear and respective bays] etc. suitable for ACSR Zebra/Panther [for Outdoor XLPE to Air Termination for Transformer Bay]
Insulators
36 kV class Post Insulator Stack
Other Steel Structures/ members to be designed/ provided by the bidder for the project [Various items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] [ This shall also include the steel to be used in the civil works excluding reinforcement]
Marshalling KIOSK/box
AC Distribution Boxes (Outdoor Type)
Outdoor AC Distbibution Box (Double Front type)
Conduits, Cable Trays, Cable Tags, Cable Racks & Supports, Cable Glands, Cable Lugs, Gland Plates, Junction Boxes [Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room building]
Isolators
Horizontal double break (HDB)motor operated 33kV isolator complete with all fittings including post insulators, accessories, terminal connectors and all other items (as specified in technical specification for 2000 A HDB isolator with single earth switch)
LT Switchgear
LT AC Main Panel
LT AC Distribution Board
Main Lighting Distribution Board
Emergency Lighting Distribution Board
220V DCDB
48V DCDB
Earthing System
40 mm Dia MS Rod
40 mm dia 3000 mm long MS rod (earth electrodes) with/without test links, RCC pits, C.I .cover hinged at C.I. frame alongwith all associated civil works
40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
3m, 20 mm Dia MS Rod Electrode
3m, 40 mm Dia MS Rod Electrode
3m, 42 mm Dia Safe Earthing Electrodes
3m, 60 mm Dia Safe Earthing Electrodes
50X12 mm GS Flat
50X6 mm GS Flat
50 X 6 mm MS Flat
25 X 3 mm GS Flat
50 X 6 mm Copper Flat (for GIS Switchgear Sceening, Sheilding and Earthing)
3 m, 25 mm Copper Rod
Earth Enhancing Compound for treated pits as above and other requirement as per specification
1.1kV Grade PVC insulated Al. conductor power cables and copper conductor armoured control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room building]
Power Cables(XLPE)
3.5Cx300 sq.mm
3.5C x 185 sq.mm
Power Cable(PVC)
1Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4Cx6 sq.mm
Control Cable (PVC)
2Cx6 sq.mm
4CX4 sq.mm.
4CX6 sq.mm.
2Cx2.5 sq.mm
4Cx2.5 sq.mm
5Cx2.5 sq.mm
7Cx2.5 sq.mm
10Cx2.5 sq.mm
14Cx2.5 sq.mm
19Cx2.5 sq.mm
COMMUNICATION EQUIPMENTS
For Establishment of fiber optic communication Link beween 132 kV GSS Pratap Nagar and Terminal Substations (132 kV GSS Sitapuar and 220 KV GSS IG Nagar)
Communication Equipment (including 1 No. IP/MPLS Aggregation Router, 1 No. Ethernet Switch mounted on Panel alongwith necessary accessories for connecting to Fiber Distribution Frame)
Digital Protection Coupler
Electronic Private Automatic Exchange (EPAX)
Electronic Push Button Telephone Instruments with required accessories etc.
TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS
TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements]
Insulation Tester
1000/500 Volts, Digital
Dew Point Meter
SF6 Leakage Detector
SF6 Gas Filling, Evacuation, Filtering, Drying, Storage and Pumping Plant
Digital Multimeter
Digital Clamp Meter
Communication Equipment
Maintenance Tools& Tackles
GIS Tools & Tackles
Inspection tools for dismantling nozzles of Circuit Breakers
Inspection tools for Dismantling arc contacts for Circuit Breakers
Box spanner, hexagonal spanner and snap ring cutting pillar for Circuit Breakers
Operating handle for manual operation for earthing switch
Operating handle for manual operation for disconnectors
Gas Mask
General Tools& Tackles
Oil Sampling Bottle (1 Liter Capacity)
Vaccum Cleaner
Telescopic ladder aluminium 6 meter height
Ring spanner set
Tube spanner set
Pipe wrench 24 inch
Pipe wrench 18 inch
Hydraulic crimping tools up to 1000 sq.mm
Threading die set for pipe threading
Welding machine (arc welding) 10kVA
Heavy duty drilling machine
Bench Vice
Insulated cuttingplier 12 inch
Insulated cuttingplier 8 inch
Screw driver 18 inch
Screw driver 12 inch
Hammer 8 lbs
Hammer 2 lbs
Chain pulley block 5 ton
Pipe derrick
Allen Keys
Box Spanners
Office and Miscellaneous Equipments/ Items
Insulation Rubber mat (1mX2mX 12 mm)
Isulation Rubber Gloves (15 kV Tested)
Furniture for Control Room Building:
Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet)
Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet).
Library Shelf with Glass Door (min 4 Shelf)
Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane.
SCADA Room Furniture (Control Desk for specified consoles and Revolving Chair) matching with the overall interiors as per specification
Archival Storage 4 Drive Type
Lateral Filing Cabinets
3 Drawer Unit
4 Drawer Unit
Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system.
Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system.
Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 18 guage with three waylocking system.
Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments ( 22 guage).
Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG.
Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage
Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round.
Key board (wooden) with Glass door
First Aid Box
Shock Treatment Chart [Laminated with Frame]
Safety Instruction Boards [ Laminated with Frame]
Drinking Water Arrangement
Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr)
RO/ Water Purifier
Refrigirator (380 Lt.)
Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner]
Danger Plate [Size and Color etc. be got approved from owner]
MANDATORY SPARES
POWER TRANSFORMER
HV bushing with metal parts and gaskets
LV bushing with metal parts and gaskets
Neutral bushing with metal parts and gaskets
Magnetic oil level gauge with low oil level alarm contacts
Winding temperature Hot indicator
Oil temperature indicator
Pressure relief device
Cooler fans
Buchlotz Relay
Complete set of Gasket
132 kV Indoor GIS Switchgear Equipments
SF6 Gas pressure relief devices
Pressure gauges(of each type) alongwith Coupling device
Rubber Gaskets "0" Rings and Seal for SF6 Gas
Molecular filter for SF6 gas sets
Density Monitor for SF6 Gas
All type of Control Valve for SF6 Gas
Bottles of SF6 Gas (40 Kg each)
Closing coils for circuit breakers
Tripping coils for circuit breakers
Control switch and auxiliary relays of each type for local control cubicle
Miniature Circuit Breaker (as applicable) of each type
Operating Mechanism for Disconnectors
Operating Mechanism for Earth Switch
Motor for Disconnectors
Motor for Earth Switch
Motor for Circuit Breaker Operating Mechanism
One complete set of circuit breaker
Contact fingers and nozzles for circuit breakers
Valve block with drive cylinder for circuit breakers
One complete set of isolator and earthing switch (Single Phase Unit)
36 kV Metal Clad GIS Switchgears
Drive Mechanism for Circuit Breaker
Drive Mechanism for Combined Disconnector
Spring Charge motor
Trip Coil
Close Coil
Rupture Disk/ Diapharm
LV Panel Equipments: Relay, MCB, Lamps, Push Buttons, terminal Blocks
Pressure Switches
Rubber Gaskets
Bay Control & Protection Unit
C&R Panels & SAS System
Bay Control Unit
Bay Protection Unit (Distance & Differential each type used)
Bay Unit/ Module for Busbar Protection System (each type used)
Breaker failure relay (numerical type)
Trip circuit supervision relay
Self reset trip relay
Hand reset trip relay
Timer relay
DC supervision relays
Flag relays
Auxiliary relays
Hard Disk Used in HMI Computer
Network Card With Driver Used in HMI Computer
Fan Assembly for HMI Computers
HMI Server/ Computer as supplied (CPU Part Only)
HMI View Node/ DR Computer as supplied (CPU Part only)
Mouse
Keboard
Fiber Optic Cable with Connectors
Ehternet LAN Cables with connectors ( 5 Nos. of each type used)
Transducers (2 Nos. of Each Type used in the autoamtion system)
Ethernet Switches (each type used)
Station Transformer
10% of total Transformer Oil quantity in non-returnable drums
HV bushing
LV bushing
Pressure relief device
Tap charger contact
Set of valves
Set of gasket
Silica gel required for five replacements
Surge Arrester
132 kV class 120 kV rating LA complete as specified.
2 Nos. Terminal connector of each type as spare
33kV class 30 kV rating LA complete as specified.
2 Nos. Terminal connector of each type as spare
Battery & Battery Charger
220 V & 48 V Type Battery
Spare battery cell without electrolyte
Terminal connectors with bolts & Nuts
Float level indicators
Vent Plugs
220V/ 50V Battery Chargers
Set of Control Cards
Set of relays
Set of contactor
Micro-switches
Filter Capacitors
Thyristor/ Diode
Set of switches
Set of wound resistors
Potentiometers
Fuses of Thyristor with indicators
L.T. SWITCHGEAR :
Relays
CTs AND PTs
Switches/Push buttons and Meters
TPN Switches/MCB
L.T. Breaker spares
a) Spring charging motor
b) Aux. Contact sets
c) Busbar Seal off insulators
d) Arc-chutes
e) Moving contacts
f) Arcing contacts (Fixed/Moving)
g) Springs (Closing/Opening)
h) Closing coil
i) Tripping coil
j) Aux. finger contact
k) Limit switches
l) Jaw contacts
Busbar
a) Busbar insulators
b) Interphase barrier
c) Busbar strip 1mm (Aluminium)
LIGHTING SYSTEM
MCB (10 Nos. of each type and ratings which shall be supplied)
Triple pole MCB (2 Nos. of each type and rating which shall supplied)
Lighting Fixture (5% of each type of Lighting Fixture which shall be supplied)
Celing Fan of Supplied Type
Electronic Regulator for Celing Fans
Exhaust Fan
Clamps & Connectors
Communication Equipments
8-Port POE Switch (Type-B)
Fire Protection System
NIFPES System
Fitted Nitrogen Cylinder [48 Lit Water Capacity]
Hose Pipe with Fittings
Heat Sensor Assembly
Fire Survival Cable [sufficient for 1 system]
Limit Switches for Fire Detector
Fire Detector (for NIFPES System)
Thermostat
Heating Element
Isolators
Solid core insulator stacks (Requirement of one Isolator)
Limit switches and auxiliary switches-- Each Set containing one no. of each type and rating as offered
Bearings (Requirement of one Isolator)
Current carrying assembly 2000A total (Requirement of one Isolator)
Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key inter lock for electrical control circuit as per approved schematic-- Each Set containing one no. of each type and rating as offered
Motor with gear assembly and bevel gear assembly.
Terminal connectors 1 set containing 1 No of each type.
SUPPLY LINE WORK: ERECTION & MODIFICATION OF 132 KV SITAPURA-IG NAGAR OVERHEAD LINE (RUNNING ON COMPOSITE TOWERS FROM 220 KV CIRCUIT) THROUGH 1CX800 SQ. MM XLPE D/C COPPER UNDERGROUND CABLE FROM COMPOSITE TOWER LOCATION NO.-18 TO PROPOSED 132 KV GIS PRATAP NAGAR (Approx.-4.25 KM)
MAIN MATERIAL/ ITEMS
Overhead Line
(i) Stub 220KV D/C NB TTC (250Mtr SPAN)
(ii) S/S 220KV D/C NB TTC (250Mtr SPAN)
(iii) SST
(iv) Stub 220KV D/C NB TTD (350Mtr SPAN)
(v) S/S 220KV D/C NB TTD (350Mtr SPAN)
(vi) +6 MTR EXTENSION
(vii) SST
ACSR Conductor
ACSR ZEBRA conductor
24 fibre (DWSM)OPGW Fibre Optical Cable
Instalation H/W Set for above Fiber OPGW Including of cable fitting ans Accessories
24 Fiber Joint box for OPGW/underground Fiber Cable
Zebra conductor hardware
a) Double tension hardware
b) Single tension hardware
c) Single Suspension hardware
d) Armour Rod
e) M.S Joint
f) Al. Repair sleeve
g) Vibration damper
Disc Insulator
G.I. Nut-Bolt, Step bolt & spring washer assorted size as per requirement & technical specification [For 220 KV D/C NB TTD Type tower(350 mtr. Span)]
G.I. Nut-Bolt, Step bolt & spring washer assorted size as per requirement & technical specification [For 220 KV D/C NB TTC Type tower(250 mtr. Span)]
Earthing Material
a) Pipe type
Others
a) Number plate
b) Phase plate
c) Danger plate (220 KV)
Underground cable
132 kV, Single Core, 800 Sq. mm XLPE Copper Cable as per foregoing specification requirements
145 kV rated voltage pre-moulded straight through joint 800 Sq. mm XLPE Copper Cable suitable for suitable for the above underground cable
145 kV rated voltage pre-moulded outdoor end termination kit complete with accessories suitable for 800 Sq. mm XLPE Copper underground cable
145kV Plug in type pre moulded end termination kit complete with accessories suitable for above underground cable and suitable for termination in GIS type switchgear
145 KV rated voltage premolded Straight through Joint (with provision for sheath separation fro cross bonding/Mid point Earthing ) suitable for above underground cable as per foregoing specifications
Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase (Both for indoor/Mid point/Outdoor termination earthing
Cross bonding link box, co-axial bonding cable, Sheath Voltage limiters (SVL) complete with other associated accessories for each 3-phase circuit
Galvanized Steel Supporting Structures/arrangement, gantry structure, along-with clamps, connectors, nut-bolts, washers, foundation bolts etc. for suitable and safe termination of XLPE cable at GSS end maintaining statutory clearances and safety as per IE rules including fencing arrangement
Galvanized steel supporting structures/ arrangement etc for suitable and safe termination of XLPE cable to GIS switchgear
Terminal connector suitable for Zebra/Panther Conductor equivalent to ACSR Zebra/Panther on the Outdoor cable termination to connect cable end termination to ACSR Zebra/Panther Line.
Earthing material including cast iron pipes with suitable clamps, charcol, common salt etc complete set for each cable circuit (each having 3 core)
Warning Tapes as per Specification
132 kV class of 120 kV rating LA with grading ring, discharge counter with Milli meter
Line Differential cum Distance - Numerical relay with optical interface and all other accessories/items for retrofiting at both end
2 X 12 Fibre OFC and hardware fittings/ accessories alongwith associated , Joint Box & accessories
OFAC/OFC and hardware fittings/ accessories alongwith associated FODP & accessories
Add: Any other item bidder may require to complete the GIS, works as well as EHV XLPE Cable System as per specification requirements
Description of Work / Item(s)
SERVICE - 132 KV GIS SUBSTATION AT PRATAP NAGAR
SUBSTATION EQUIPMENTS
Power Transformer:
Power Transformer: 132/33 kV, 80 MVA Transformer with all accessories and 10% extra oil in non-returnable steel drums
RTCC Panel fitted with Transformer Monitoring cum Tap changer control System (TCS) alongwith associated acessories complete in all respect.
132 kV Indoor GIS Switchgear Equipments
145kV, 1250A, SF6 gas insulated Transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer, bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, surge arrestors, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting Power Transformer (Air/ XLPE) with GIS through XLPE cable with cable termination enclosure and other accessories etc. to complete transformer bay module as indicated in the SLD/ Layout of substation and as per technical specifications.
145kV, 1250A, SF6 gas insulated Feeder bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, surge arrestors, PT , SF6 gas monitoring system for complete bay, local control cubicle, gas insulated terminal connection for connecting XLPE cable with cable termination enclosure and other accessories with GIS etc. to complete feeder bay module as indicated in the SLD/ Layout of substation and as per technical specifications.
Double Bus Arrangement, 145kV, 3 Phase, SF6 gas insulated metal enclosed 2500A bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switch, local control cubicle (if required), SF6 gas monitoring system etc. for the complete bus as indicated in the SLD/ Layout of substation and as per technical specifications.
145kV, 2500A, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, disconnectors with safety earthing switches, Local control cubicle, SF6 gas monitoring system for complete bay etc. as indicated in the SLD/ Layout of substation and as per technical specifications.
Suitable Capcity EOT Crane for GIS Hall/ Building
Ventilation system for GIS Hall/ Building (as per technical specification)
36 kV Metal Clad GIS Indoor Switchboard
Metal clad Double Bus Indoor GIS Switchboard Including 2 No. Incomer Transformer Feeders, 7 No. Outgoing Feeders and 1 No. bus-Coupler (as per SLD) alongwith all associated accessories CTs. PTs, Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 3000A, 31.5 kA Class]
Cable Termination/ Plug for terminating in Metal clad switchgear panels for 6 Nos. of Outgoing Feeder panels (for 2 Nos. 3-Phase Outgoing cable circuit in each) from each (Normally cable sizes is 300 Sq. mm or more and exact size shall be decided with the distribution company during detailed engineering)
33 kV XLPE Cables & Accessories
3 C, 95 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3]for connecting the HV side of Substation Transformer to O/G of 36 kV Metal Clad GIS Switchgear
1C, 1000 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. (This include 12 lengths of cable with suitable Outdoor & Indoor [12+12] end Terminations)
C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
132 kV C&R Panel Type SAS-FCA
133 kV C&R Panel Type SAS-FRA
132 kV C&R Panel Type SAS-BCRA
132 kV C&R Panel Type SAS-TCRA
132 kV C&R Panel Type SAS-BBRA
Substation SAS Netorking Panel SAS-NW
Station HMI [Industrial grade Computer with Approx. 21"TFT monitor as per specification requirements]
Station HMI (Hot Standby)[Industrial grade Computer with Approx. 21"TFT monitor as per specification requirements]
HMI View Node[Industrial grad Computer with Approx. 21"TFT monitor as per specification requirements]
DR Work Station[Industrial grade Computer with Approx. 21"TFT monitor as per specification requirements]
A3 Size Color Laser Printer
Dot Matrix Printer
One Remote Workstation with HMI[Industrial grade Computer with 21"TFT monitor as per specification requirements] & Laser Printer (A4 Size) for RCC
Hardware Gateways (for data transmission to RCC & SLDC)
Modems (both sending and Receiving End) for communication to RCC & Sub SLDC[if required as Communication Equipments are proposed]
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
Substation LAN Commnication Infrastructure
Ethernet Switches:
132 kV Side C&R and Network Panels:16 Nos.{12 Port (8 Nos. 10/100 BaseTX + 4 No. 10/100/1000 Base FX)}, 2 Nos. {24 Port 10/100 Mbps TX + 4 port 10/100/1000 Base FX}]
33 kV Side C&R Panels: 2 Nos.{16 Port (12 Nos. 10/100 BaseFX + 4 No. 10/100/1000 Base FX)}
Other Items:
Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the substation LAN as per specification requirements.
Inverter (3 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC)
Inverter (1 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC)
132 kV XLPE Cable & Termination
500 Sq. mm 132 kV XLPE Cable
132 kV Outdoor Cable Termination for XLPE to Air Termination on HV Side of Power Transformer
132 kV GIS Termination for XLPE Cable
Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase
Surge Arresters
132 kV class of 120 kV rating LAs
33kV class of 30kV rating LAs
33kV/415V, 250kVA station transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
Batteries & Battery Charger
Batteries (Sizing shall be as per requirement of technical specification)
220 V [Min 400 AH]
48 V [Min 300 AH]
Battery Charger System
220 V Float and Boost
48 V Float and Boost
Lighting System
Outdoor Lighting & other Works
Lighting Fixture Type -SF2 as per Specification
Lighting Fixture Type -EEC2 as per Specification
Lighting Fixture Type -SF1 as per Specification
Lighting Fixture Type -EEC1 as per Specification
Emergency Lighting Type-PF
Type-RO, 15A, 240V: Outdoor Receptacle 2 pole, 3-pin type
Type-RP, 63A, 415V : Interlocked switch socket outdoor Receptacle
Hot Dip Galvenized Octogonal Lighting Poles (12 m)
Street Lighting Type-EEA for mounting on above Poles
Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast complete with all controgears and accessories, items etc.
Lighting Panel Type ACP-3 as per technical specification
Indoor Lighting & Other Works
Electrification
Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, GIS Hall and administrative office building as per the requirements of the specifications
Illumiation
Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
Indoor Lignting Panels
Lighting Panel (Indoor) Type ACP-1 as per technical specification
Lighting Panel (Indoor) Type DCP as per technical specification
Wall mounted fans Approx. 400 mm sweep
Approx. 1400mm sweep with electronic Step regulator
Exhaust Fans
Fire Fighting System
Nitrogen Injection Fire Protection System for Power Transformer complete in all respects.
Fire Fighting equipment with necessary mounting stands.
DCP Type
Carbon di oxide type – Around4.5 Liters.
Foam Type- Around 9 Liters
Sand type
i) GI Buckets Around 9 liters capacity
ii) Steel Stands for four buckets
Fire Detection and Alarm System
Siren along with all accessories as specified in technical specification
Microprocessor based Fire Detection & Alarm System alongwith the Desktop, System and application software for geographic monitoring and detection of fires, display of events and alarms etc. as specified in technical specification
Photo-electric Detectors, Smoke Detectors, Heat Detectors, Linear Heat Sensing Cables, Manual Call Points etc. Control Room, GIS Hall, Office Building, Store, Testing Laboratory etc.
Power & Control Cables for fire detection & alarm system
Air Conditioning System
High Wall Split AC units of 2 TR Capacity complete with Indoor, Outdoor Units and required accessories, Stablizers etc.
Substation Structures/Supports & Switchyard Erection
145 kV GIS Switchgear Interconnections for Incomer Line (from incoming 132 kV XLPE Cable for which Cable Termination Kit with support to be supplied by Cable System Contractor) complete with all necessary enclosure support, clamps, connectors and other accessories for successful connection to GIS Switchgear as per Layout of the substation.
145 kV GIS Interconnections for Transfomer Bay (from SF6 to XLPE termination) complete with all necessary enclosure support, clamps, connectors, other accessories for successful connection to GIS Switchgear as per Layout of the substation.
33 kV Transformer Bay (from Power Transformer LV Terminals to SA, Isolator/ PI for Cable Termination) [Complete with Three Phase Al. (50 mm. Size) tubular conductor, Clamps (rigid/flexible/expansion type), Connectors, Straight/V/Y Taps, nut-bolts and other accessories] as per Layout of the substation.
Tubular/ Lattice Support for Equipments [Complete with all accessories]
132 kV Side
132 kV Cable Termination (XLPE to Air termination for Power Transformer)
132 kV Surge Arrestor
Isolators
33 kV Side
Isolators (3 Phase) with Single Earth Switch
33 kV XLPE Cable Termination support structure for Connecting to 33 kV Side of 132/33 kV Transformer including 33 kV Class of 30 kV rating LAs (3 Nos.), Supporting PI String (3 Nos.), nut bolts, fixing accessories etc. as per drawing appended in Section-IV of specification
Lightning Cum Lighting Masts. Approximate Unit Weight Appox 3.5 MT for each Mast
Earth Wire
7/3.15 mm Galvanized Steel wire
Clamps (Suspension/Tension), Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
Other Suspension/T Clamps & Power/Terminal Connectors [not covered in respective equipments/ switchgear and respective bays] etc. suitable for ACSR Zebra/Panther [for Outdoor XLPE to Air Termination for Transformer Bay]
Insulators
36 kV class Post Insulator Stack
Other Steel Structures/ members to be designed/ provided by the bidder for the project [Various items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] [ This shall also include the steel to be used in the civil works excluding reinforcement]
Marshalling KIOSK/box
AC Distribution Boxes (Outdoor Type)
Outdoor AC Distbibution Box (Double Front type)
Conduits, Cable Trays, Cable Tags, Cable Racks & Supports, Cable Glands, Cable Lugs, Gland Plates, Junction Boxes [Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room building]
Isolators
Horizontal double break (HDB)motor operated 33kV isolator complete with all fittings including post insulators, accessories, terminal connectors and all other items (as specified in technical specification for 2000 A HDB isolator with single earth switch)
LT Switchgear
LT AC Main Panel
LT AC Distribution Board
Main Lighting Distribution Board
Emergency Lighting Distribution Board
220V DCDB
48V DCDB
Earthing System
40 mm Dia MS Rod
40 mm dia 3000 mm long MS rod (earth electrodes) with/without test links, RCC pits, C.I .cover hinged at C.I. frame alongwith all associated civil works
40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
3m, 20 mm Dia MS Rod Electrode
3m, 40 mm Dia MS Rod Electrode
3m, 42 mm Dia Safe Earthing Electrodes
3m, 60 mm Dia Safe Earthing Electrodes
50X12 mm GS Flat
50X6 mm GS Flat
50 X 6 mm MS Flat
25 X 3 mm GS Flat
50 X 6 mm Copper Flat (for GIS Switchgear Sceening, Sheilding and Earthing)
3 m, 25 mm Copper Rod
Earth Enhancing Compound for treated pits as above and other requirement as per specification
1.1kV Grade PVC insulated Al. conductor power cables and copper conductor armoured control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room building]
Power Cables(XLPE)
3.5Cx300 sq.mm
3.5C x 185 sq.mm
Power Cable(PVC)
1Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4Cx6 sq.mm
Control Cable (PVC)
2Cx6 sq.mm
4CX4 sq.mm.
4CX6 sq.mm.
2Cx2.5 sq.mm
3Cx2.5 sq.mm
5Cx2.5 sq.mm
7Cx2.5 sq.mm
10Cx2.5 sq.mm
14Cx2.5 sq.mm
19Cx2.5 sq.mm
COMMUNICATION EQUIPMENTS
For Establishment of fiber optic communication Link beween 132 kV GSS Pratap Nagar and Terminal Substations (132 kV GSS Sitapuar and 220 KV GSS IG Nagar)
Communication Equipment (including 1 No. IP/MPLS Aggregation Router, 1 No. Ethernet Switch mounted on Panel alongwith necessary accessories for connecting to Fiber Distribution Frame)
Digital Protection Coupler
Electronic Private Automatic Exchange (EPAX)
Electronic Push Button Telephone Instruments with required accessories etc.
CIVIL WORKS
Site Levelling: Supplying all labour, machineries, Tools and plants and levelling the switchyard area, associated other areas confined in the entire substation boundary to the required RL including cutting in hard soil in areas above FGL and filling up with excavated/ borrowed earth in layers not exceeding 250mm loose thickness in areas lower than FGL duly compacting and disposing the excess earth to any disposal point with all leads and lifts ,dismantaling of existing buildings/ structures/ foundations etc., complete as per specification, drawings and directions of the engineer incharge of the work
Foundations: Design, Engineering, supply of all labour, material and construction of RCC footings and pedestals of any section/size including the cost of excavation in all types of soil/rock, back filling with available approved earth or borrowed/new earth, disposal of surplus earth/rock to the places directed, concrete (RCC M20 Grade and Lean concrete 1:4:8), reinforcement steel,form work ,grouting , underpinning, foundation strengthening in expansive / B.C soil , curing, sundries and other items not mentioned herein but required for the completion of the work for the following station towers and equipments support structures as per technical specification, approved drawings and directions of the Engineer- in-charge of work
a)Lightning/Lighting mast
b) Equipment Support Structures
i) Indoor GIS Switchgear (complete for existing scope of work)
ii) XLPE to SF6 Interface [ Required civil work for making the interconnection onwards work of cable system bidder i.e. Cable with Cable Kit and support structure] for Incoming Lines (complete existing scope)
iii) XLPE to SF6 Interface [ Required civil work for making the interconnection to cable system bidder i.e. Cable with Cable Kit and support structure] for Transformrs
iv)33 kV Isolator support structure
v) Surge Arrester
v) 132 kV Outdoor Cable Termination
vi) 33 kV Cable Support Termination Structures including PI & SA etc
c)Other Items
i)Marshalling KIOSK
ii) AC Outdoor Distribution board
Cable Trenches:
Design, Engineering,supply of all labour, material and construction of RCC (grade M-20) cable trenches(Out door) and pipe trenches for required section /size including the cost of excavation in all types of soil/rock , Backfilling with available approved earth or borrowed/new earth, disposal of surplurs earth to the places directed, concrete (RCCM20 grade and lean concrete 1:4:8) precast RCC covers, form work, curing, water stops, brickworks, wherever required, reinforcement steel, steel angles, flats, plates, cable trays, sundries and other items not mentioned herein but required for completion of work as per technical specification, approved drawings and directions of the Engineer-in-charge of work.
Section in mm
i) A-Type 850x750 mm
ii) C-Type 550x450 mm
iii) D-Type 360x300 mm
Antiweed Treatment:
Supplying all labour, material, equipments etc and providing soil sterilisation/antiweed treatment including mixing/injecting chemicals to achieve the guaranteed effectiveness of treatment atleast upto three years as per Technical Specification, instructions and directions of usuage of the chemical manufacturer and direction of the enginner incharge of the work.
JELLY SPREADING:
a) Supplying all labour, materials, equipments and Providing and laying 100mm thick granite/trap/basalt jelly using 20mm size jelly including the cost of jelly, sundries and other items not mentioned herein but required for the competion of the work as per technical specifications drawings and direction of the engineer incharge of the work. The jelly used shall be free from dirt, organic material and flakes etc.
b)Concrete Block Masonry Barricades : supplying all labour, materials and Providing barricades to confine jelly spreading including the cost of the following works and other items not mentioned herein but required for the completion of the work as per specifications and directions of the engineer incharge of the workincluding earth work excavation in all types of soil /rock, backfilling and disposal of surplus stuff to the places directed, construction of solid concrete block masonry in cement mortar 1:6 with cement concrete solid blocks of proportion (1:5:3), crushing strength not less than 50Kg per Sq. Cm, 40 x 20 x 20 Cms size (l.b.h) conforming to ISS 2185-1967 including necessary curing etc., complete. The concrete blocks shall be 100mm above FGL, plastering to masonry 12mm thick in CM 1:6 and two coats of water proof cement painting to exposed faces over one coat of primer
Transformer foundation and associated rail track: Design, Engineering, supply of labour, material, equipments and construction of transformer and radiator foundations, rail tracks(Concrete grade M-20) including all associated works, jacking pads, Anchor blocks, MS gratings, gravel filling, pylon support system including the cost of excavation in all types of soil/rock, back filling with available approved earth or borrowed/new earth,disposal of surplus soil/rock to the places directed, concrete (RCC M20 grade and lean concrete 1:4:8), reinforcement steel, strucutural steel, form work, grouting , jelly , painting, curing, sundries and other items not mentioned herein but required for the completion of the work as per technical specification, drawing and directions of the Engineer in-charge of work
i)80MVA, 132/33kV Transformer
ii)Baffle/Fire Wall: Design, Engineering supply of all laobour materials and construction of baffle/fire wall as per technical specification, drawing and directions of engineer incharge of work. (RCC M20)
Size Stone Masonry Transformer Platform:
Construction of size stone masonry Transformer platform for 250KVA, 33/0.415KV LT Transformer as per drawing enclosed, technical specifications and directions of the Engineer- in-charge of work, incuding the cost of excavation in all types of soil/rock , backfilling with available approved earth or borrowed/new earth, disposal of surplus soil/rock to the places directed, concrete (PCC 1:1.5:3 for coping and lean concrete 1:4:8) Strengthening of foundation in expansive /B.C soil Size stone masonry for foundation and basement in cement mortar 1:6 using hammer dressed/chistle dressed stones of not less 15 cm. high with bond stones in each course, plastering 20mm thick in CM 1:6, to the exposed faces, structural steel, reinforcemet steel, curing, water proof cement painting to the exposed faces and other items not mentioned herein but required for the completion of the work.
Road Works:
Design and construction of roads and walkways/shoulders within sub-station or outside the station as per specification, layout, sectional detail drawing (To be furnished by the successful bidder) and directions of Engineer-in-charge of work etc. complete in all respect. [ Area of Concrete Surface shall be considered for measurement]
STORM WATER DRAIN, DECK SLAB CULVERT/PIPE CULVERT FOR DRAIN CROSSINGS:Design, Engineering and construction of Strom water drain, deck slab culvert and pipe culverts with the following items of work
i) Earth work excavation for foundation, pipe line and drainages and removing the excavated earth to a distance not exceeding 50m and with a lift upto 1.50m. In hard soil
ii) Providing and laying cement concrete using 40mm and down size stone aggregate for foundation laid in 15cms thick layers and well compacted including curing etc., complete cement concrete 1:4:8
iii) Random Rubble stone masonry in courses not less than 20cms high with bond stones 2m apart in each course, edges of stones chistle dressed and all quoins 2 line dressed 5cms. Wide on each face including curing etc., complete as per specification in CM 1:6.
iv) Providing pointing to stone Masonary in CM 1:3 after raking the joints to a depth of 2.50 cms and nicely lining curing etc., complete.
v) Earth work filling by using available earth including compacting by filling 15cm layers and consolidation with water etc., complete.
vi) Disposing of the excess earth away from the premises including all loading and unloading, transportation , leads lifts etc., complete
vii) Providing and laying cement concrete using 20mm and down size stone aggragate including mixing, laying, tamping, curing and smooth finished for exposed faces and with necessary centering and form work etc.,complete for SILLS, COPING,BOND SLAB, Basement and for any other such works Cement Concrete 1:2:4.
viii) Providing Haulig and Laying 450mm dia. NP3 class RCC hume pipe in position carefully and jointing with CM:1:2 and curing etc., complete (including the cost pipes and collars) with all leads and lifts whereever required
ix) Providing and fabricating MILD/ HYSD steel reinforcement conforming to IS 1786 including supply of steel and labour for straightening, cutting, bending, hooking, lapping and/or welding wherever required placing in position, tieing with binding wire of approved quality and gauge including the cost of binding wire and anchoring to the adjoining members wherever necessary etc complete as per design specification and directions
x) Providing and laying insitu vibrated cement concrete Grade M20 using 20mm and down size graded coarse aggregate using clean sieved approved sand, including cost and conveyance of all materials, all leads and lifts, labour, hire charges of machinery, scaffolding, form work, centering vibrating, finishing curing etc., complete for solid Deck Slab.
Switchyard fencing:
Design Engineering and construction of new security wall cum chain link fencing and strengthening of existing security wall with chain link fencing,including Earth work excavation for foundation and removing the excavated earth to a distance not exceeding 50m and with a lift upto 1.50m. in hard soil , concrete using 40mm and down size aggregate for foundation laid in 15cms thick layers and well compacted , complete cement concrete 1:4:8, Providing and laying cement concrete using 20 mm down size stone aggregate including mixing, laying, tamping, and smooth fihished for exposed faces and with necessary centering and form work etc., for SILLS, COPING, BOND SLAB, Basement and for any other such works Cement Concrete 1:2:4 ,Stone masonry, stones hammer dressed in courses not less than 20cms high with bond stones 2m apart in each course including curing etc., complete as per specification in CM 1:6.for foundation structural steel using ISMC, ISA, M.S. flats etc., for providing structural works incuding cost of materials, consumables required for the completion of work including charges for fixing welding, cutting, straightening, bending, fastening, grinding, welding etc., complete including two coats of synthetic enamel paint ,etcbarbed G I wire fencing of 12 X 12 guage drawn into stone or iron pillars including drawing in holes wherever necessary excluding the cost of pillars but including the cost of barbed wire and binding wire etc
Providing and fixing M.S gate to RCC pillars with approved clading, fabricated as per the drawing and directions of the Engineer incharge of the work. Rate includes cost of RCC supports, gate, fixing to RCC supports , painting etc., complete chain link fencing 50mm size of 8 guage properly stretched between rectangular poles and fixed with suitable bolts and nuts, the free ends shall be welded to the pole and block pipe at top and bottom as required including cost of all materials, labour and lifts, cutting, bending wherever necessary wastages and lapping etc., complete as per direction of Engineer- in- charge of work including two coats of approved quality synthetic enamel paint over one coat of shop preimer MS rectangular poles made out of 2 equal angles of 65x65x6mm welded together and fixed in CC 1:2:4 with two nos. of 16 mm dia. MS hold fast rods each of length 25 cms. Including cost of all materials cutting, bending, scaffolding wherever necessary nicely finishing the welded joints with all lead and lifts and as per the directions of engineer incharge of the work including providing 2 coats of approved quality synthetic enamel paints over one coat of shop painting. Disposing of the excess earth away from the premises with all lead and lifts including all loading and unloading transportation etc., complete
Control Room Building: Design, Engineering, supply of all labour, materials equipments, tools and plants etc., and construction of Control Room building (RCC M-20 grade) as per the drawing, directions of the engineer incharge of the work with the following items of work. water supply, sanitary ( internal and external ) electrification/illumination, construction of various cable ducts comming within the building are in the scope. The building shall be designed for 2nd floor office loads. The scope is for construction of ground, first and second floor with stair case cabin.
GIS Hall Building: Design, Engineering, supply of all labour, materials equipments, tools and plants etc., and construction of Control Room building (RCC M-20 grade) as per the drawing, directions of the engineer incharge of the work with the following items of work. water supply, sanitary ( internal and external ) electrification/illumination, construction of various cable ducts comming within the building are in the scope. The building shall be designed for 1st floor office loads. The scope is for construction of ground floor.
Rain Water Harvesting: Design Engineering, Supply of all labour, material, tools & plants etc. and construction of Rainwater Harvesting as per technical specification.
Interior Works for the SCADA Room including designer false celing (with rodent repellent sytem installed above it), furnishing, specialized illumination system etc. Complete in all respect as per specifications.
Training
Training on Overall Design, Operation and Maintenance of 132 kV Gas Insulated Switchgear: This training will be for the acquaintance of the GIS technology, brief design principles, Operation and maintenance practices and recommendations of manufacturer.
Training on Overall Design, Operation and Maintenance of 36 kV Metal enclosed Gas Insulated Switchgear: This training will be for the acquaintance of the GIS technology, brief design principles, Operation and maintenance practices and recommendations of manufacturer.
Training on Overall Design, Operation and Maintenance of IEC-61850 based SAS System: This training will be for the acquaintance of the IEC-61850, brief design principles, Operation and maintenance of deployed system.
Maintenance
Maintenance Charges for 3 Years
ERECTION & MODIFICATION OF 132 KV SITAPURA-IG NAGAR OVERHEAD LINE (RUNNING ON COMPOSITE TOWERS FROM 220 KV CIRCUIT) THROUGH 1CX800 SQ. MM XLPE D/C COPPER UNDERGROUND CABLE FROM COMPOSITE TOWER LOCATION NO.-18 TO PROPOSED 132 KV GIS PRATAP NAGAR (Approx.-4.25 KM)
Over head line
Detail Survey as per tentative route:- Which includes the following major activities- Pegging of line rute ,providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey,profile preoaration of approved route on graph sheet and making of offset on either side of line,marking of side clearance for hills,sand dunes etc,as per specification and tower scheduling.
Check survey as per approved route of line which inclused: re-checking of line route as per approved profile, chainage, tower centre marking, pit marking, bisection of angle towers as required at site.
Excavation:- Excavation excluding backfilling including shoring shuttering dewatering etc up to the required depth as per foundation Specification Drawing
(i) Any soil soft rock other than hard rock
Setting of template & stub/anchor or bolts;- Setting of template &Stub/Anchor Bolt & Removal after concreting excluding cost of excavation and concreting but including backfilling with excavated/ borrowed earth (with lead & lift) in layers with ramming and watering as per specification.
(i) Tower Including extension up to 9 meter
Concreting:-Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement sand, stone aggregate 20 mm nominal size, water etc. Preparing surface, shuttering, mixing, placing, ramming, curing, finishing s per specification and drawings
(i) 1:3:6 Mix [M-10]
(ii) 1:1.5:3 Mix [M-20]
Steel Reinforcement:
Cutting, bending, welding of joints if required, fixing and placing of steel reinforcement as per specification and drawings including material.
Earthing:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats & connectors, but including coke/charcoal, etc. excavation, auguring and back filling in all types of soil.
Erection of Tower.- Erection of super structure including D-shackle ACD, Hangers ,Also including tac welding of bolts and nuts up to bottom cross arm/beam level including application of zinc rich paints.
i) Erection of towers (with extension up to 9 meters)
24 Fiber OPGW/ Underground Fiber Cable
24 Fiber Joint Box for OPGW/Underground Fiber Cable
RESTRINGING OF CONDUCTOR/EARTH WIRE
(A) Restringing of ACSR Zebra conductor: Dismantling of vibration dampers and armour rods, fitting in rollers, de-tensioning, holding & lowering of conductor, de-hoisting of insulator string as required, adding/ removing and jointing of conductor, hoisting of insulator string, lifting of conductor into rollers and re-tensioning, jointing, fitting of armour rods and and vibration dampers and clamping per route KM of the line section to be restrung dismantled material not re-used to be deposited in our stores & stacked
(i) Single Conductor
(C) Restringing of earth-wire/ OPGW: De-stringing of earth bond, vibration dampers, de-clipping and fitting in rollers, de-tensioning, holding & lowering of earth-wire/ OPGW, adding/ removing and jointing of earth-wire/ OPGW, lifting into rollers and re-tensioning, jointing, clipping & fitting of vibration dampers & earth-bond per route km of the line section to be restrung. Dismantled material not re-used to be deposited in our stores & stacked
(i) One No. 7/3.15 mm Galvanized Wire/ OPGW
DESTRINGING OF CONDUCTOR
(A) De-stringing of ACSR Zebra conductor: Dismantling of vibration dampers and armour rods, removal of conductor from clamps and fitting in rollers, de-tensioning, de-hoisting of insulator string as required and collecting the material & depositing the same in our store and stacking.
(i) Single Conductor
(B) De-stringing of Earth wire/ OPGW
Dismantling of earth bonds, vibration dampers, de-clipping & fitting in rollers, de-tensioning and collecting the material & depositing Ihe same in our store and stacking.
(i) One No. 7/3. 15mm galvanised wire/ OPGW
DISMANTLING OF TOWER :- Dismantling of Super Structure alongwith extensions, having tack welded Bolts & Nuts, including removing of D shackles, hangers, U-Bolts, step bolts, ACD, Danger Plate, Number Plate, Phase Plate of tower including transportation from site to our store and stacking of all material
(A)132KV and 220KV S/C & D/C towers
CABLE INSTALLATION
Surveying of cable route, excavation of trial holes as per field requirement, preparation of cable route profile, drawing of cable laying, final route alignment marking lines and grades/ preparation of final cable route drawing after approval and preparing bill of materials for complete route shown in drawing i.e. between terminal towers
Evaluation of thermal resistivity of soil along cable route (as per technical specification)
Handling, Transportation to site and laying of 132 kV, Single Core, 800 Sq. mm XLPE Copper Cable as per foregoing specification requirements
Establishing of 3-phase double circuit having (3 Phase each circuit) 132kV single core, 800 sq. mm copper cable in trefoil/ approved formation along-with pilot fiber cable, providing of Warning tape tagging fixing, pipes for drain & gate crossing as per drawings and specifications in trench by pulling, drawing, etc. including cables, using standard cable installation equipments and as per directions of the engineer in charge and returning of unused items in Store.
Handling and making of straight through joints for 132 kV Single Core 800 Sq, mm Power Cable (XLPE Copper Cable) as per specification
145kV Plug in type pre moulded end termination kit complete with accessories suitable for above underground cable and suitable for termination in GIS type switchgear including supply of suitable supporting structure as per specificastion
Handling and making of outdoor type cable end terminations for 132 kV single core power cable as per specification
Handling and making of 145 KV rated voltage premolded Straight through Joint (with provision for sheath separation fro cross bonding) suitable for above underground cable as per specifications
Erection of Galvanized Steel Supporting Structures/ arrangement, gentry structure, ladders etc along-with clamps, connectors, nut-bolts, washers, foundation bolts etc. for suitable and safe termination of XLPE cable from terminal towers maintaining statutory clearances and safety as per IE rules for each phase along with fencing arrangement of tower. (Structure to mount link boxes, cable end termination and surge arrester for each phase)
Erection of solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase.
Erection of Cross bonding link box, co-axial bonding cable, Sheath Voltage limiters (SVL) complete with other associated accessories for each 3-phase circuit
Erection of Galvanized Steel Supporting Structures/Arrangement e.t.c for suitable and safe termination of XLPE Cable GIS switchgear
Earthing Material including cast iron pipes with suitable clamps, charcoal, common salt etc. complete set for Cable Circuit(each having 3 core )
Installation of Terminal connector suitable for ACSR Panther/Zebra to connect cable end termination to ACSR Panther/Zebra Line.
Installation of 132 kV class of 120 kV rating Surge Arrestor with grading ring, discharge counter with Milli meter
Installation of of underground Optical fiber cable and associated accessories/ items as per specification along-with XLPE cable and termination at the both ends
Retroffiting of Line Differential cum Distance - Numerical relay with optical interface and all other accessories/items for retrofiting at both end
Charges for conducting pre-commissioning tests as per specification and successful commissioning of circuits
CIVIL WORKS
Cutting Black Bitumen surface up-to any depth including all layers of crust for laying Power Cables etc, staking of useful material and disposal of surplus debris including all leads including barricading, providing danger board/diversion board, lighting, reflectors etc.
Horizontal Direct Drilling (Trenchless Digging) method (with 250mm dia HDPE Pipe of minimum 6 PN and strength complying ISS) wherever open cut method cannot be adopted. (for double circuit with 3 cable core in each circuit. (If required)
Earth work in excavation for buried cable trenches/foundations including dressing of sides and ramming of bottoms, lift up to 2.5 mtr. including taking out the excavated soil & backfilling of jhiri with watering & ramming , timbering & shoring ( wherever required ) disposal of surplus excavated soil as directed with all lead and lift including barricading, providing danger board/diversion board, lighting, reflectors etc.
Providing and laying of Cement concrete including curing, etc using stone aggregate 40 mm nominal size (crusher broken) in foundation plinth, excluding the cost of shuttering using 1 cement: 4 sand: 8 stone aggregate (For equipment foundation, junction box etc.)
P&L cement concrete in R.C.C. work in foundation ,rafts, footings, strap beams ,bases of columns etc., including curing ,compaction, finishing with rendering in cement sand mortar 1:3 (1cement :3 sand) and making good the joints , excl., the cost of centring and shuttering and reinforcement :M-20 grade mix 1:1.5:3 (1cement:1.5coarse sand : 3 graded stone aggregate 20 mm nominal size (For equipment foundation, junction box , culvert etc.)
Brick wall works, if required
Providing and fabricating steel reinforcement for R.C.C. work bending ,placing in position and binding complete including cost of binding wire in foundation ,raft footing ,strap beams base of column etc., up to plinth level hot rolled deformed (I.S.1139) cold twisted (I.S.1786)bars (For equipment foundation, junction box \ etc.)
Centring and shuttering with plywood or steel plates including strutting, propping bracing both ways with wooden members and removal of formwork for superstructure up to 4.5m height above plinth level for (For equipment foundation, junction box etc.)
Providing & Fixing of steel fabrication made of angles, tees, square bars or other flats black pipe with hold fast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide.
Providing ,Laying and Jointing RCC class NP-2 Non Pressure pipes (IS:458 Mark ) of approved make with collars, jointed with CM 1:2 or having Spigot and socket ends with flexible rubber rings joint including testing of joints etc. complete: 450 mm D
Providing & Fixing of Reinforced Ferro Cement Cable Trench Covers designed for 'A' & 'AA' loading duly marked on cover with adequate reinforcement having thickness 75mm to 100 mm anti corrosive bitumen pained MS plate Rim and MS lifting hooks admixtures like plasticizer bond -improving compound, shrinkage resistance compound, abrasion resistant complete as per approved design ( For cable joint box) (For any span)
Providing & Laying HDPE pipe heavy duty of approved make jointed with solvent cement
(i) 250 mm dia.(for double circuit each circuit with 3 cable cores)
(ii) HDPE PLB Duct for Optical Fiber Cable (2 X 12 Fibre OFC)
Supply and laying inter locking RCC cable covers as per approved drawing
Supply, spreading of clean river sand in the cable trench and cable joint pit as per specification.
Providing & Fixing Cable Route Marker along the route of cable at the spacing of 50 meter etc. as per drawing and site requirement.
RR stone masonary in F/P CSM 1:4
Plastering 20 mm thickness CSM 1:6
Providing & laying plane cement concrete M20 Grade
Maintenance Service [these charges shall be applicable after the completion of guaranteed performance period of cable system for 4 years excluding of item/ material/ equipment already covered for performance guarantee of 5 years.The charges shall be payable on actuals
Maintenance services per visit towards any breakdown of cable system which includes services of expert engineers, technicians alongwith necssary tools/ tackles, testingnequipments, fault locating equipments to detect the faults and its subsequent ractification, re-testing and restoring the electric supply through cable system for both cable circuits
Add: Any other item bidder may require to complete the GIS as well as EHV XLPE Cable System as per specification requirements
Universal Cables Limited
Universal Cables Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid