Tender Value
₹4.6 Cr
EMD Value
₹9.2 L
Closing Date
17 Sept 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
+ Capital Works)
Above/Below/Par
TRD BSL
17 conditions · 5 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB(available in GCC), along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet. (In case, the tenderer fails to submit Annexure VIB and/or Audited Balance Sheets, the offer will be summarily rejected).
Tenderer shall have "Electrical Contractor License", which must be valid at least up to Tender closing date. Copy of valid license must be attached along with the offer. In case the validity of the License submitted has expired, the tenderer's offer will be considered only if they have applied for renewal before the expiry of the License and have submitted valid proof of the same along with their offer. Otherwise, the offer shall not be considered.
In case a tenderer is participating as Sole Proprietor in a tender, it is mandatory for him to submit an undertaking on suitable stamp paper to this effect clearly mentioning PAN number also along with tender document at the time of submission of tender. (CEGE/CRly's letter no.CR.PCEE.Secy.Genl.Corresp, dated 13-10-2022.). Sole proprietor Certificate Format is uploaded herewith. (This certificate is mandatory for Proprietor firm and not required from other than Proprietor firm.Other than Proprietor firm may upload a pdf with remark "Not applicable") ( Click here to download Format)
Bidder should submit the documents as prescribed in para 14 of second sheet of GCC-2022 to establish constitution of firm as well as legality of the person submitting the tender.
3 conditions · 1 needing a document upload
In case of other than Company/Proprietary firm, Annexure -V(A) shall also be submitted by each member of Partnership Firm / Joint Venture (JV) / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. as the case may be. Non submission of above certificate(s) by the bidder shall result in summarily rejection of his/their bid. It shall be mandatorily incumbent upon the tenderer to identify, state and submit the supporting documents duly self-attested/digitally signed by which they / he is qualifying the Qualifying Criteria mentioned in the Tender Document. Format of Annexure VA is available in GCC April'2022 uploaded with the tender.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
a. List of personal organization available on hand and proposed to be engaged for the subject work. b. List of Plant & Machinery available on hand (own) and proposed to be inducted (own & hired to be given separately) for the subject work. c. List of works completed in the last three financial year giving description of work, organization for whom executed, approximate value of contract at the time of award, date of award and date of schedule completion of work. Date of actual start, actual completion and final value of contract should also be given. d. List of works on hands indicating description of work, contract value, approximate value of balance work yet to be done and date of award.
Provision of Separate CB (Circuit Breaker) for sectioning of sidings in Bhusawal Division. (PC-BD & BSL-KNW)
BSL_ELECT_TRD_45_2026~CR
BSL_ELECT_TRD_45_2026
Open
Works - General
12 Months
Jalgaon, Maharashtra
₹0
₹9.2 L
20 Aug 2026
20 Aug 2026
3 Sept 2026
163 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 4,60,95,110 | ||
| — | 4.00 | — | — | ||
| Preparation of drawing and Design of FP, TSS and Switching station. | — | — | — | 1,52,000 | |
| — | 750.00 | — | — | ||
| Cement concrete for foundation & plinth in other than hard soil & rock. | — | — | — | 61,92,000 | |
| — | 250.00 | — | — | ||
| Cement concrete for foundation & plinth in hard soil. | — | — | — | 21,17,750 | |
| — | 30.00 | — | — | ||
| Cement concrete for foundation & plinth in Rock. | — | — | — | 3,20,100 | |
| — | 95.00 | — | — | ||
| Supply of galvanized fabricated steel work for gantry & supporting structure | — | — | — | 1,24,26,000 | |
| — | 95.00 | — | — | ||
| Erection of galvanized fabricated steel work for gantry & supporting structure | — | — | — | 7,24,850 | |
| — | 8.00 | — | — | ||
| Supply of galvanized fabricated steel work for small parts steel. | — | — | — | 10,46,400 | |
| — | 8.00 | — | — | ||
| Erection of galvanized fabricated steel work for small parts steel. | — | — | — | 61,040 | |
| — | 10.00 | — | — | ||
| Reinforced concrete for foundation, cable trench. | — | — | — | 90,000 | |
| — | 100.00 | — | — | ||
| Provision of cable trench covers. | — | — | — | 2,42,500 | |
| — | 150.00 | — | — | ||
| Erection of 150 Sq. Mm Copper Feeder Wire, | — | — | — | 23,400 | |
| — | 150.00 | — | — | ||
| Extra on erection charges for power block work for Erection of 150 Sq. Mm Copper Feeder Wire, | — | — | — | 24,150 | |
| — | 8000.00 | — | — | ||
| Erection of 234 sqmm Aluminum (Spider conductor) feeder wire on separate mast | — | — | — | 1,84,000 | |
| — | 40.00 | — | — | ||
| Supply of termination assembly for feeder wire including 25 KV solid core 9 Tone porcelain cut-in insulators & all accessories / fittings & fastners. | — | — | — | 3,01,960 | |
| — | 40.00 | — | — | ||
| Erection of termination assembly for feeder wire including 25 KV solid core 9 Tone porcelain cut-in insulators & all accessories / fittings & fastners. | — | — | — | 72,400 | |
| — | 160.00 | — | — | ||
| Supply of 25 KV solid core 9 Tone porcelain suspension insulator along with all accessories/fittings & fastners required for provision of solid core suspension insulator for feeder wire. | — | — | — | 12,98,080 | |
| — | 160.00 | — | — | ||
| Erection of 25 KV solid core 9 Tone porcelain suspension insulator along with all accessories / fittings & fastners required for provision of solid core suspension insulator for feeder wire. | — | — | — | 85,760 | |
| — | 32.00 | — | — | ||
| Supply of bimetallic parallel clamp & all accessories/fittings & fastners to provide bimettallic parallel clamp to avoid direct connection between aluminum feeder & copper jumper. | — | — | — | 12,352 | |
| — | 32.00 | — | — | ||
| Erection of bimetallic parallel clamp & all accessories/fittings & fastners to provide bimettallic parallel clamp to avoid direct connection between aluminum feeder & copper jumper. | — | — | — | 1,216 | |
| — | 32.00 | — | — | ||
| Supply of guy rod assembly. | — | — | — | 3,01,216 | |
| — | 32.00 | — | — | ||
| Erection of guy rod assembly. | — | — | — | 20,928 | |
| — | 27.00 | — | — | ||
| Erection of any type jumper assembly such as feeder Jumper, G Jumper, AT Jumper, Isolator Jumper etc. | — | — | — | 14,715 | |
| — | 11.00 | — | — | ||
| Extra on erection charges for power block work for Erection of any type jumper assembly such as feeder Jumper, G Jumper, AT Jumper, Isolator Jumper etc. | — | — | — | 1,199 | |
| — | 120.00 | — | — | ||
| Supply of 50x39 mm Al Tubular Busbar | — | — | — | 62,400 | |
| — | 120.00 | — | — | ||
| Erection of 50x39 mm Al Tubular Busbar | — | — | — | 22,320 | |
| — | 120.00 | — | — | ||
| Supply of various connectors in TSS/FP/SP/SSP(as per approved drawing) | — | — | — | 2,17,080 | |
| — | 120.00 | — | — | ||
| Erection of various connectors in TSS/FP/SP/SSP(as per approved drawing) | — | — | — | 9,960 | |
| — | 16.00 | — | — | ||
| Supply of conventional earthing station. | — | — | — | 52,800 | |
| — | 16.00 | — | — | ||
| Erection, testing & commissioning of conventional earthing station. | — | — | — | 10,400 | |
| — | 300.00 | — | — | ||
| Supply of armoured control cable of size 2 Core X 2.5 sq.mm | — | — | — | 19,500 | |
| — | 300.00 | — | — | ||
| Laying, testing & commissioning of armoured control cable of size 2 Core X 2.5 sq.mm | — | — | — | 3,900 | |
| — | 600.00 | — | — | ||
| Supply of Armoured control cable of size 7 Core X 2.5 sq.mm | — | — | — | 1,26,000 | |
| — | 600.00 | — | — | ||
| Laying, testing & commissioning of armoured control cable of size 7 Core X 2.5 sq.mm | — | — | — | 12,000 | |
| — | 300.00 | — | — | ||
| Supply of Armoured control cable of size 2 Core X 4 sq.mm | — | — | — | 28,200 | |
| — | 300.00 | — | — | ||
| Laying, testing & commissioning of armoured control cable of size 2 Core X 4 sq.mm | — | — | — | 3,900 | |
| — | 300.00 | — | — | ||
| "Supply of 10 Sq.mm Single Core Copper Cable Multi Stranded Flame Retardant PVC insulated cable of voltage grade 1100V." | — | — | — | 29,700 | |
| — | 300.00 | — | — | ||
| Erection of 10 Sq.mm Single Core Copper Cable Multi Stranded Flame Retardant PVC insulated cable of voltage grade 1100V. | — | — | — | 7,200 | |
| — | 4.00 | — | — | ||
| Supply of 25 KV vacuum Circuit breaker (Inclusive of terminal connectors suitable for 50 mm Alluminium tubular busbar). | — | — | — | 31,04,000 | |
| — | 4.00 | — | — | ||
| Erection of 25 KV vacuum Circuit breaker (Inclusive of terminal connectors suitable for 50 mm Alluminium tubular busbar). | — | — | — | 73,720 | |
| — | 4.00 | — | — | ||
| Supply of 25 KV, 1500-750/5A current transformer (protection) as per RDSO Specification No. ETI/PSI/90 (6/95) or latest | — | — | — | 5,62,600 | |
| — | 4.00 | — | — | ||
| Erection, testing & commissioning of 25 KV, 1500-750/5A current transformer (protection) as per RDSO Specification No. ETI/PSI/90 (6/95) or latest | — | — | — | 13,580 | |
| — | 4.00 | — | — | ||
| "Supply of 27.5 kV / 110 V Potential transformer. ((protection, Type-II) " | — | — | — | 3,68,600 | |
| — | 4.00 | — | — | ||
| "Erection, testing and commissioning of 27.5 kV / 110 V Potential transformer. ((protection, Type-II) " | — | — | — | 17,460 | |
| — | 4.00 | — | — | ||
| "Supply of 27.5 KV / 100 V Potential transformer. (Indication, Type-I) " | — | — | — | 3,30,252 | |
| — | 4.00 | — | — | ||
| "Erection, testing and commissioning of 27.5 KV / 100 V Potential transformer. (Indication, Type-I) " | — | — | — | 17,980 | |
| — | 4.00 | — | — | ||
| Supply of 42 KV Class lightening arrestor with surge monitor. | — | — | — | 1,80,000 | |
| — | 4.00 | — | — | ||
| Erection, testing and commissioning of 42 KV Class lightening arrestor with surge monitor. | — | — | — | 5,200 | |
| — | 8.00 | — | — | ||
| Supply of 25 KV AC 1600A, Single pole isolator with operating rod insulator. | — | — | — | 5,70,424 | |
| — | 8.00 | — | — | ||
| Erection of 25 KV AC 1600A, Single pole isolator with operating rod insulator. | — | — | — | 85,360 | |
| — | 1000.00 | — | — | ||
| Supply of 40mm X 6mm MS flat for bonding including painting & hole drilling in rail. | — | — | — | 2,23,000 | |
| — | 1000.00 | — | — | ||
| Fabrication & fixing of 40mm X 6mm MS flat for bonding including painting & hole drilling in rail. | — | — | — | 57,000 | |
| — | 200.00 | — | — | ||
| Supply of 50mm X 6mm MS flat for bonding. | — | — | — | 40,800 | |
| — | 200.00 | — | — | ||
| Fabrication & fixing of 50mm X 6mm MS flat for bonding including painting & hole drilling in rail. | — | — | — | 16,400 | |
| — | 100.00 | — | — | ||
| Supply of GI 8 SWG wire earthing | — | — | — | 2,500 | |
| — | 100.00 | — | — | ||
| Erection of GI 8 SWG wire earthing | — | — | — | 1,600 | |
| — | 100.00 | — | — | ||
| "Supply of Fencing Panel, (2.55 Mtr height) at SP,SSP.TSS,FP." | — | — | — | 3,50,000 | |
| — | 100.00 | — | — | ||
| "Erection of Fencing Panel, (2.55 Mtr height) at SP,SSP.TSS,FP." | — | — | — | 19,000 | |
| — | 5.00 | — | — | ||
| Supply of Fencing Uprights. | — | — | — | 2,55,000 | |
| — | 5.00 | — | — | ||
| Erection of Fencing Uprights. | — | — | — | 24,500 | |
| — | 8.00 | — | — | ||
| Supply of Gates for FP/SP/SSP/TSS | — | — | — | 37,600 | |
| — | 8.00 | — | — | ||
| Erection of Gates for FP/SP/SSP/TSS | — | — | — | 3,200 | |
| — | 100.00 | — | — | ||
| Supply of Anticlimbing device at switching station.. | — | — | — | 17,000 | |
| — | 100.00 | — | — | ||
| Erection of Anticlimbing device at switching station.. | — | — | — | 3,500 | |
| — | 50.00 | — | — | ||
| Supply of 20 mm ballast in the switch yard. | — | — | — | 75,000 | |
| — | 50.00 | — | — | ||
| Spreading of 20 mm ballast in the switch yard. | — | — | — | 8,250 | |
| — | 4.00 | — | — | ||
| Supply of Discharge Rod assembly including clamp/cable. | — | — | — | 32,400 | |
| — | 200.00 | — | — | ||
| Supply & erection of caution Board / enameled Number plate/ Danger board. | — | — | — | 1,10,000 | |
| — | 4.00 | — | — | ||
| Supply of Sectioning diagram. | — | — | — | 16,800 | |
| — | 100.00 | — | — | ||
| Supply of single core 35 sq. mm multistrand copper cable. (LA & AT). | — | — | — | 57,000 | |
| — | 100.00 | — | — | ||
| Erection of single core 35 sq. mm multistrand copper cable. (LA & AT). | — | — | — | 4,200 | |
| — | 4.00 | — | — | ||
| Supply of Single Feeder Circuit Breaker Protection relay panel, including feeder protection relay, Delta I relay, DC fail relay, MTR and meter annunciators.(as per latest specification) | — | — | — | 1,12,52,000 | |
| — | 4.00 | — | — | ||
| Erection, testing & commissioning of Single Feeder Circuit Breaker Protection relay panel, including feeder protection relay, Delta I relay, DC fail relay, MTR and meter annunciators.(as per latest specification) | — | — | — | 5,82,000 | |
| — | 4.00 | — | — | ||
| Testing & commissioning of BMs/CBs in existing RTU alongwith necessary cables connection from terminal board/ C&R panel to RTU. | — | — | — | 1,97,880 | |
| — | 4.00 | — | — | ||
| Modification in existing SCADA software at RCC/ BSL to accommodate the additional BM/CBs in SCADA | — | — | — | 10,00,000 | |
| — | 4.00 | — | — | ||
| Integration of numeric relays with TSS/RTU and SCADA system at Remote Control Center. | — | — | — | 25,220 | |
| — | 50.00 | — | — | ||
| Dismentalling of - Fencing Panel & transportation to Railway TRD depot. | — | — | — | 4,350 | |
| — | 2.00 | — | — | ||
| Dismentalling of - Fencing Uprights & transportation to Railway TRD depot. | — | — | — | 4,838 | |
| — | 5.00 | — | — | ||
| Dismentalling of - Gates & transportation to Railway TRD depot. | — | — | — | 760 | |
| — | 20.00 | — | — | ||
| Dismentalling of - Anticlimbing device including barbed wire & transportation to Railway TRD depot. | — | — | — | 260 | |
| — | 25.00 | — | — | ||
| Dismantling of 25 KV Bus bar system | — | — | — | 2,675 | |
| — | 5.00 | — | — | ||
| Dismantling of Equipment foundation & making site clear. | — | — | — | 21,825 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
ACS11.pdf
ATTACHMENT
ACS 12
ATTACHMENT
GCC-2022-ACS10_merged.pdf
ATTACHMENT
Soleproprietorcertificatepdf_1.pdf Sole Proprietorship Certificate
ATTACHMENT
Booklet45-2026.pdf
ATTACHMENT
Explanoryfinal45-2026.pdf
ATTACHMENT
Soleproprietorcertificatepdf_1.pdf
ATTACHMENT
ACS12toGCC2022dtd12-08-2026_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].