| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.3 LAccepted-AOC | ₹24.3 L Quoted ₹25.8 L | L1 | Accepted-AOC lowest bid quoted |
| 2 | L2₹32.0 L+₹6.2 L (24.2%)Rejected-Finance RZ 50D GALI NO 13 VASHISHT PARK PANKHA ROAD NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | ₹32.0 L+₹6.2 L (24.2%) | L2 | Rejected-Finance Highest bid quoted |
| 3 | L3₹36.9 L+₹11.1 L (43.2%)Rejected-Finance | ₹36.9 L+₹11.1 L (43.2%) | L3 | Rejected-Finance Highest bid quoted |
| 4 | L4₹37.6 L+₹11.8 L (46.0%)Rejected-Finance 20 8 EWS PREETAM NAGAR COLONY ALLAHABAD | PRAYAGRAJ | UTTAR PRADESH | 211001 | ₹37.6 L+₹11.8 L (46.0%) | L4 | Rejected-Finance Highest bid quoted |
| 5 | L5₹43.1 L+₹17.3 L (67.3%)Rejected-Finance RZ 1 7 167 GALI NO 6 DURGA PARK NASIRPUR SOUTH WEST DELHI DELHI 110045 | SOUTH WEST | DELHI | 110045 | ₹43.1 L+₹17.3 L (67.3%) | L5 | Rejected-Finance Highest bid quoted |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
14 Sept 2022, 6:00 pmClosed
GE (AF) Gurgaon
Gurgaon
REPAIR MAINTENANCE OF LT DISTRIBUTION SYSTEM MAINTENANCE OF POWER HOUSES REPAIR REPLACEMENT OF UNSV DBs SUB MAIN WIRING AND REPLACEMENT OF UNSV FITTINGS FIXTURES, REPLACEMENT OF LT PANEL FEEDER PILLAR BOX EARTHINGS PERIMETER SECURITY LIGHTS ALONGWIT
2022_MES_545856_1
CA NO GE/GUR-/NIT-30/2022-23
Open Tender
Miscellaneous Works
Piece-work
240 days
GE (AF) Gurgaon
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) Gurgaon
₹1 L
17 Oct 2022
17 Aug 2022
16 Sept 2022
17 Aug 2022
14 Sept 2022
31 Aug 2022
Amount
M&L for Carry out 'B' check and servicing of DG set as per OEM specification for DG set of 250 KVA capacity, (including the cost of the following spares parts all as per OEM and directed by Engineer in Charge). (i) Engine oil (ii) Spinon lube oil filter (iii) Fuel Filter Kit 1.1 Ltrs (iv) Coolant (v) Air cleaner Safety Element (vi) Air cleaner primary element (vii) K clean 1 ltrs (viii) Poly V belt 4PK/8PK (any type & length) (ix) Thermostat Element (x) Rubber hoses of any type with tie clips of suitable size (xi) Gaskets,glands, nut, bolts & washers (xii) Radiator cleaning from outside with pressure jet spray, chemical & brush (xiii) Cleaning of DG set engine within canopy and AMF panel (xiv) Air Filter (xv) Freight & labour charges Freight & labour charges
All as per item No- 1 here in before but for 160-140 KVA DG set.
All as per item No- 1 here in before but for 100 KVA DG set.
All as per item No- 1 here in before but for 70 KVA DG set or below.
M&L for visiting of service engineer/ technician at site and inspecting DG set upto 250 KVA (including AMF panel problems, control unit/sensors, Engine, radiator, Alternator or any other type of complaint i.e. Mechanical, electrical or electronic or including all the three teams togather) and checking for fault/defect and noting down items required for rectification, including rectifying minor defect on site if possible, complete all as specified and directed. Note: (i) visit for servicing of DG set will not be considered in this item. (ii) Minor complaints occuring within one month after servicing of a particular DG set will not be considered in this item after lodging complaint to Contractor by Engineer-in-charge (iii) Visiting of Different technician i.e. electrical, mechanical, electronic or combine of three for the same complaint will be considered as one visit or one complaint only. (iv) Subsequent visit after first visit (defect found or not), if founded then visit for rectification of defect will not be considered in this item.
M & L for Dismantling of Fuel pump assembly and fuel injectors of any nos of engine for DG Set of capacity upto 250 KVA, and transporting it to workshop and Caliberation fuel pump & its fuel injection system and overhauling of pump valve, valve seat, Nozzel pin holes by metal deposition and machining on lathe machine, gasket, bolts etc. and refixing the same and commissioning till fuel consumption and quality & quantity of smoke is within permissible level complete all as specified & directed : Note: Transportation charges are deemed to be included in quoted rates.
M & L for Taking out of turbo charger from DG Set transportation to workshop for overhauling, repairing and replacement of turbo assembly including fan, gears and machining of vortex flow chamber of turbo & refixing to DG Set and refixing the same and commissioning till fuel consumption, quality & quantity of smoke and load development/ sound of DG is satisfactory to EIC all as specified & directed. Note: Transportation charges are deemed to be included in quoted rate
M & L for Dismantling of radiator assembly of engine of following capacity, and transporting it to workshop (if required) from site otherwise performing job at site. thereafter cleaning fins and chocked tubes after draining out water, washing with caustic, descaling and brazing for water tube leakage, repalcing of copper tube of suitable length and and size and refixing the same properly by deploying sufficient numbers of labour and commissioning and again checking for leakage after running DG on Load and checking flow speed of water through it, complete all as specified & directed : Note: Transportation charges are deemed to be included in quoted rate.
140 to 250 KVA
Upto 100 KVA
M & L for Dismantling of Self Starter motor of following capacity for DG Set of capacity upto 250 KVA, and transporting it to workshop and rewinding with suitable gauge of copper wire, overhauling, repair & replacement of gears, pinion & its locking arrangment, armature, Carbon plate, carbon bush & brush, Gears etcand and refixing the same and commissioning for the torque developed by it for starting DG Set, complete all as specified and directed. Note: Transportation charges and charges for dismantling & reconnecting electric cable of starter & synchronising with control unit are deemed to be included in quoted rate.
140 to 250 KVA (Suitable for 24 V)
Upto 100 KVA (Suitable for 12 V)
S& F of AVR S/F VARIABLE SPEED DCDG suitable for DG set with input voltage range 415 Volt AC with neutral & Out put DC voltage for DG set upto 250 KVA as per OEM specifications, including wiring as per required at site after taking down old unserviceable one, complete all as specified and directed.
M & L for Dismantling of alternator of DG Set of capacity upto 250 KVA, and transporting it to workshop and rewinding, overhauling, repair & replacement of rewinding with suitable gauge of copper wire, gear, pinion, pulley, carbon bush & brush etc upto 250 KVA as per OEM specification, including belts, wiring, demounting as per required at site after taking down old unserviceable one, complete all as specified and directed.
Supply and fixing following spares parts upto 250 KVA DG Set: Note: Taking down old spare parts and connecting new one by deploying skill technician (mechanical, electrical, electronics or combination) including necessary nut, bolts, washers, wiring, thimbling, tagging is deemed to be included in quoted rate for item no 12.01 to 12.34
Water pump assembly Make: Kirloskar
Flexible connection (crank case to pump) Make: Kirloskar
Water pump pulley (2 grooves, 190 PCD) Make: Kirloskar
Fresh water outlet connector on heat exchanger Make: Kirloskar
Fresh water outlet connector on heat exchanger Make: Kirloskar
Non return valve 1" BSP Make: Kirloskar
Thermostat and housing assembly Make: Kirloskar
MAGNETIC PICK UP 16X1.5 THREADING (UNITCH MAKE) for dg upto 250 KVA Make: Kirloskar
Engine control unit EMS 907 including relay card, PCB & logic card) Make: Kirloskar
CONTROL RELAY, 24 V D.C., THREE CHANNEL R.B. ELECTRONICS Make: Kirloskar
RELAY BOARD UL MAKE 24 VDC 2CH. 2C/O (RELAY- OMRAN make: Kirloskar
ENGINE WIRING ASSEMBLY SUITABLE FOR EMS 907 UNIT Make: Kirloskar
WIRING HARNESS FOR CPCB CANOPY WITH PRICOL PANEL Make: Kirloskar
WIRING HARNESS ASSEMBLY WITH EMS 907 UNIT make: Kirloskar
SENSOR UNIT(FOR ELEC TEMP GAUGE) Make: Kirloskar
LUB OIL PRESSURE SENDOR 0.75 +/- 0.15 BAR TWO TERMINAL Make: kirloskar
WATER TEMPERATURE SWITCH (NO/NC) Make: Kirloskar
STOP SOLENOID assembly suitable for 12/24V Make: Kirloskar
Thermostat element (74 Deg) make: kirloskar
CURRENT TRANSFORMER (SET OF 3 CT) 300/5A Make: Kirloskar
CURRENT TRANSFORMER (SET OF 3 CT) 500/5A Make: Kirloskar
KG 934 controller unit make: Kirloskar
Relay board 2 and 1/2 12 V DC Make: Kirloskar
Engine wiring harness assembly with KG 934 Make: Kirloskar
LEFT HAND LOCK WITH CATCHER (UPTO 82.5 KVA) Make: Kirloskar
LEFT HAND LOCK WITH CATCHER ( 100 TO 600 KVA) Make: Kirloskar
RIGHT HAND LOCK WITH CATCHER (UPTO 82.5 KVA) Make: Kirloskar
RIGHT HAND LOCK WITH CATCHER (100 TO 600 KVA) Make: Kirloskar
LEFT HAND HINGE Make: Kirloskar
Right HAND HINGE Make: Kirloskar
V BELT RAW EDGED COGGED.(LP1176) Make: Kiloskar
FLEXIBLE LUB OIL PIPE(FOR REMOTE FILTER) Make: Kirloskar
KG 545 controller unit make: Kirloskar
ENGINE WIRING ASSEMBLY SUITABLE FOR EMS KG 545 UNIT Make: Kirloskar
S&F of Lead acid Battery of 150 Ah, 12 V heavy duty for DG set with 24 month gurrantee , maintenance for battery, complete all as specified and directed.
Excavating in post holes (or similar holes) soft / loose soil each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken dubble mixed with earth around, in layers not exceeding 25 cm
M&L for plain Cement concrete type B2, 1:2:4 (40 mm graded agg) in foundations, filling and mass concrete complete all as specified and directed
S&F of Rolled sections Fe 410-W (Gde- E- 250) quality- as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for sliding doors; fixed with angle cleats or other connecting plates.complete all as specified and directed
S&F of Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as in repair all as specified and as directed.
M & L for Appliying Synthetic enamel paint on steel surfaces of any description, preparation of new or old untreated surface,one coat of red oxide zinc chrome primer & two coats of synthetic enamel paint over treated steel surface not otherwise descri-bed, over 10cm width or girth complete all as specified and as directed.
M&L for Rendering 15mm thick on fair faces of brick work or concrete surface with CM 1:4 complete all as specified and as directed.
M&L for cutting and removing burnt out AMF panel wiring and rewiring it with copper wire of solid/stranded conductor all as per existing size with proper labelling/tagging, new thimble/ termination, connecting all circuit & logical controls, repalcing relays, timers, sensors & signal reciever, removing carbon deposition on bus bars & terminals, repairing cable tray, rewiring and proper connection of AMF panel parameters with DG set safety control unit, replacing new CTs etc. Testing and commission of AMF panel in auto and manual mode and demostrating the functionality of all the safety parameter both from saftey control panel and AMF panel all as per EIC. NOTE: wiring, CTs, thimble, tagging, rewiring of DG set mounted safety control unit etc required are deemed to be in quoted rate.
Supply and fixing of digital VAF + PF meter, Cl 1in square in size of 96mm x 96mm cross-section for DG sets suiatble for DG set upto 250 KVA, complete all as specified and directed.
Supply and fixing of DC Ammeter 0-30Amps of square in size of 96mm x 96mm cross-section, for DG sets suiatble for DG set upto 250 KVA, complete all as specified and directed.
Supply and fixing of 'under/over voltage relay, 3 phase, 415 volts', for DG sets of capacity upto 250 KVA complete all as specified and directed by engineer-in-charge.
Supply and fixing of 'under/over voltage relay, single phase, 240 volts', (set of 3 for each phase in one panel) for DG sets of capacity upto 250 KVA complete all as specified and directed by engineer-in-charge.
Supply and fixing of battery voltage relay 12/24 VDC suiatble for DG set upto 250 KVA, complete all as specified and directed.
Supply and fixing Three element overcurent and earth fault relay as per site suiatble for DG set upto 250 KVA, complete all as specified and directed.
Supply and fixing of frequency relay as per site suiatble for DG set upto 250 KVA, complete all as specified and directed.
Supply and fixing engine start relay as per site suiatble for DG set upto 250 KVA, complete all as specified and directed.
Supply and fixing speed relay as per site suiatble for DG set upto 250 KVA, complete all as specified and directed.
Supply and fixing of Fuse (HRC type) 400 amps, for DG sets of capacity upto 250 KVA complete all as specified and directed.
Supply and fixing of LED lamp of any colour (Red, yellow, green and blue) suitable for 12/24 v DC & AC for DG sets of capacity upto 250 KVA, complete all as specified and directed.
Supply and fixing of 250/200 Amp, 415 Volts,4 pole, 50 Hz Power contactor of coil voltage 240 Volts, including spring operated add-on block and spring operated locking block along with spread suitable to bear current upto 350 Amps complete all as specified and directed. Make: L&T/Schineider/Havells
Same as item no- 35, but of 400 Amp, 415 Volts,3 pole, 50 Hz Power contactor, spreader suitable to bear current upto 500 Amps complete all as specified and directed.
Supply and fixing of MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and as directed.
Supply and fixing of MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and as directed.
Supply and fixing of MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA complete all as specified and as directed.
Maintenace of STPs of following sizes including cleaning of Sewage syatem, sewage lines, rectifcation of sewage blockages etc complete to ensure smooth and trouble free operation of capacity 1.5 KLD all as specified and as mentioned below:-.
i) Checking of regular parameters required for smooth operation of STP. ii) Ensure desired water quality and quantity. iii) All necessary measures to be taken for satisfactory operation of plant. iv) Regular cleaning of bar screen. v) Regular backwash and rinsing of Multi-grade filter, and Activated carbon filter. vi) To undertake regular preventive maintenance of the mechanical equipment’s such as pumps, valves etc and take corrective action in order to ensure smooth operation of the STP. vii) Checking of oil & grease and servicing of all blowers and gear boxes. viii) Physical monitoring of abnormal sound, alignment of pumps, motors, blowers, ix) To check and repair the Electrical LT panel including its components and it’s wiring for proper functioning. x) Clearing sludge bed on regular basis.
Note: i) The rates quoted are deemed to be inclusive of Repairs and replacement of spares as and when required basis by employing trained manpower. How ever the items will be measured and paid under relevant item of schedule ii) Contractor shall send trained technicians to make the plant opeartional within 3 to 4 hours by repairing the system in case of repair. Cost of replacement of spares shall be measured and paid under relevant items of schedule. Failure of operation of plant will be penalised @ Rs 1000/ per day. Suitable number of technicians shall be employed by the contractor to monitor the system on daily basis. No extra payment will be done on this account.
Nature of effluent - Domestic Sewage from toilet, Kitchen waste water shall be discharged into the STP.
INLET EFFLUENT CHARACTERSTICS
DOMESTIC SEWAGE
BOD - 250-400 Mg/L
S. Solids - 150-450 Mg/L
COD - 600-800 Mg/L
Oil & Grease - upto 50 Mg / L
DISCHARGE EFFLUENT CHARACTERSTICS AFTER TREATMENT
BOD - Less than 30 Mg/L
S. Solids - Less than 100 Mg/L
COD - Less than 100 Mg/L
Oil & Grease - Less than 5 Mg / L
Sewage treatment plant shall include the following items:-
Grit chamber
Screen Chamber
Oil & Grease Trap
Sewage equalization tank/sump
Tube Settler Tank
Sludge Holding Tank
Air Blowers, Pumps & equipment
Piping, valves etc
Irrigation / Flushing Water tank
Tertiary Treatment MGF/ACF
Electrical Panel & Cabling
Desludging the following existing chambers and getting out through sucking super soccer machine and depositing to a distance exceeding 1.5 KM out side defence land and cleaning with clean water and reuse for proper functioning complete all as specified and as directed. Note: Pumping out sludge water from MBBR tank by using diesel engine operated pump is to be arranged by contractor
Sewage well
Filter Feed tank
MBBR tank
Tube Settler Tank
Chlorine tank
Treated water tank
Collection tank
Screen Chamber
Oil and grease Chamber (3 m3)
S&F of air diffuser rod type at least 1metre long with rubber coating and SS mouth diffuser and SS clamps after removing water & sludge from equalizer tank & MBBR tank, complete all as specified and directed. Note :- Contractor shall make alternative arrangement to meet the sewage disposal during the the desluding period. The rates quoted shall be deemed to inclusive of such arragement and no extra payment will be done on this account.
M&L for Cleaning & Replacement of unserviseble sand media from sludge drying beds, and filling with clean and fine river sand or New Media for Sludge Drying Bed in layers
Supply only sodium hypochloride complete all as specified and as directed by Engr-in-Charge.
Supply only Bio Culture complete all as specified and as directed by Engr-in-Charge.
Supply only liquid chlorine all as specified and as directed by Engineer -in-charge.
Supply only MBBR media cylindrical with extended fin, black in colour of superior quality and UV stable complete all as directed by Engineer-in-charge
M & L for servicing of air blower with positive displacement type twin lube root blower with Motor of Various capacities, including Opening the blower motor blower shaft and shaft Key ways, shaft holes etc and replacing the gland packing, gland nuts, topping up engine lubrication oil and coupling as per existing size including re-fixing the same to the original position and commissioning testing complete all as specified and directed
M & L for installing electrical timer in existing electrical LT panel for air blower for auto working with inter-locking system between both air blowers. Time setting between both blower in manual way and including all accessories. complete all as directed by Engineer-in-charge
Labour only for lifting /taking out the non clogging sewage submersible pump set and motor of capacity upto 5 HP including column pipe of any bore by dismantling nut bolt washers and rubber packing etc including disconnecting of submersible cable complete from the sewage equalizer tank of depth up to 7 meter and lowering back the pump after repairing /removing the sludge from the pump including making electrical connection with the existing panel /starter and connecting the complete the column pipe assembly with nut ,Bolts,washers/packing to the existing header without any leakage complete all as directed. Note for :- Rate are deemed to be inclusive for jointing of Submersible Cable upto 7mtr, Steel wire of suitable gauge tied with motor before lowering down upto the depth of motor, reconnecting the delivery pipe line of submersible pump sets to water mains , testing for satisfactory running & continuous flow of water complete all as specified.
M&L for rewinding of electric motor monoblock 3HP 50 HZ 400/415 volts of any make and type with super enameled copper winding wire including bearing bushes and other accessories etc required to make motor functional and testing on load complete all as specified and as directed .
M&L for rewinding of electric motor 5HP , 50 HZ 400/415 volts of non clogging/ mono block/centrifugal elctric motor of any make and type with super enameled copper winding wire including bearing bushes and other accessories etc required to make motor functional and testing on load complete all as specified and as directed .
Supply, install, connect, testing and commission factory made cubicle type dust and vermin proof LT Feeder Pillar of suitble size outdoor type for STP, made out of 3.15 mm thick CRCA sheet and 50x50x6 mm (ISA- 5050) MS angle frame with hinged cubicle doors with locking arrangement, duly painted with two coats of synthetic enamel paint over a coat of red-oxide primer with seven tank process with twin shutter closing & locking arrangements complete and fixed in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate as in foundation 40 cm above ground level. It should be outdoor type and approved through CPRI . LT Feeder Pillar comprising of the following accessories :-
(I) MCCB, AC 415 volts,4- Pole, 200 Amps current rating, 36 KA rupturing capacity with adjustable (70% to 100%) thermal setting and fixed magnetic setting conforming to IS: 13947-II complete with connections to the bus-bars. - 01 No.
(ii) Aluminium Bus-Bar strip used of suitable rated capacity of 300Amps with coloured PVC insulating sleeves, mounted on post insulatore, 1100 volt grade - 04 Nos.
(v) Phase Indicator Lamps, LED type. - 01 Set
(vi) Panel instrument fuses - 01 Set
OUTGOINGS
MCCB 3 pole- 63 Amp - 4 nos duly attached with DOL Starter (including Single phase preventer &Thermal Relay 13-22 Amps) - 4 Nos suitable for 5 HP submersible pumpset along with spare space for fixing of 01 Nos MCCB
Maintenance and repair and making serviceable to fire fighting sytem including de- of centrifual motors upto 75HP and reapir to pumps upto 85 HP, LT panel wiring, pumpset DOL contactors, replacing pumpset foot valve, pressure switch, hydrants, pipe line, sprinlkers etc and refilling of all the fire extinguisher installed in Auditorium cum cinema hall including functionality of all components, cleaning all device , replacement of defective spares / components, comprising of following installed at all as specified and directed Note:- a) Contractor Shall Give The Demo and training for all duty staffs about the firefighting System the Quoted Rate is deemed to be included in the Same. b) T&P, saftey belts, ladder, tools etc required for working at height of 80ft are deemed to be included in quoted rate. c) Contractor has to make necessary arrangement for T&P and Safety of Technician & helper while working to a hieght of 80FT. Deptt will not be responsible for any mishappening during work at such hieght.
S&F of Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard, complete all as specified and directed.
Annual Maintenance contract of 3 phase Online UPS of capacity 40 KVA make Sukam at Auditorium. AMC include following scope of work: (i) Repair replacement of worn out parts. (ii) Checking and rectifying/replacing u/s PCB boards, PLC, logical units, LED light, LED display unit, logic control units, push button, switches, voltmeter, ammeter, cooling fan and motor, MCCB, MCB, transformer, insulators, bus bars, voltage stablizing unit, battery lugs and terminals and internal and external wiring. (iii) Servicing, oiling, greasing and checking periodical or as when required. (iv) Periodically checking and performing test like earth test, battery checking, battery backup checking and maintaining battery back up of 45min at any instant. complete all as specified and directed
S&F of Lead acid Battery of 65 Ah, 12 V sealed maintenance free for three phase online UPS of 40 KVA, complete all as specified and directed.
Dismantling steel poles/ struts, any size
M&L for Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long) complete all as specified and as directed.
Supply and fixing of LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.complete all as specified and directed
All as per item No 60 here in before above item no 3 but 70 w.
All as per item No 60 here in before above item no 3 but 90 w.
All as per item No 60 here in before above item no 3 but 100 w.
Supply and fixing of LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp all as specified and as directed
All as per item No 64 here in before above item no 7 but 120 w.
Supply and fixing of post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed
Supply and fixing LED Solar street light fitting 36 Watt including galvanized steel pole in built, lithium ion battery, solar panel, charge controller with dusk down sensor complete. (Excavation & earth work shall be measured separately) complete all as specified and directed
M&L for painting of steel tubular pole (straight and bend on top ) with aluminium powder base paint including painting of barbed wire at the top & ms frame pointer on pole and cable protection pipe and all iron parts of 9/11 mtr long pole complete with two coats of aluminium paint after cleaning all rust and dust and preparing surface with wire brush and including painting of strip (not less than 1 feet width) with white and red colour of synthetic enamel paint along with painting metallic junction box with aluminium paint complete all as specified. Note:- Numbering of pole with red paint on white paint base is deemed to be included in quoted rate.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sq. mm 4 core.complete all as specified and directed
M&L for PCC 1:4:8 type D2 Concrete 40 mm graded 15cm Depth in bottom of Pit for bed concrete steel tubular pole.complete all as specified and directed
M&L for PCC 1:3: 6 Concrete 40 mm graded 1.5 Mtr Depth of concrete for fixing of streel light steel tubular pole.complete all as specified and directed
M&L for PCC 1:2: 4 Concrete 40 mm graded 1.5 Mtr Depth for coping of above ground level of steel pole.complete all as specified and directed
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and laying sand in trenches for protection of cable sand cushioning to cable 8 cm thick below cable and 15 cm thick above cable in layers all as specified and as directed.
S & F of Bricks; common burnt clay building bricks, sub-class ‘B’ designation 75 Old size bricks for the protection for underground cable.
S&F in repair GI pipe light grade 50mm bore in trenches/wall/poles for protection of cable complete all as specified and as directed.
Supply and fix of 3 Phase automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz. The sensor based timer should also have over voltage and low voltage trip with auto reset facility the sensor alongwith suitable power contactor, MCB and support terminals should be enclosed in pole/wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade special moulding compounds confirming to IP 65. The contactor MCB and circuit wiring shall have enough capacity to take load of 5/7 KW equally distrubuted over 3 phase complete all as specified and as directed. Make : Healer/Universal Swtich Gear/Kakatiya Note: Copper cable of 4 Sqmm x1core (12 Rm) and fixing timer on wall/pole with the help of faster & ms strip, nut bolt & washer is deemed to be included in quoted rates.
S & F of treminal control street light box SPN 240 volts hinged,with suitable size of bus bar 4 nos ( 3 Nos for phase 01 No for neutral) water,vermine & weather proof , made out of CRCA sheet ,steel not less than 1.6mm thick duly painted of size 300 x 200 x 105 mm including fixing arrangement and fixed to concrete pole/steel pole with steel clamps, complete all as specified and directed Note : The rates quoted are inclusive of provision and fixing of suitable lugs and glands for cable connection and suitable clamps with nuts and bolts etc for fixing of terminal box to pole.
M&L for annual maintenance of solar LED street lights - 24 Nos (make: Aura). Replacement or repair to LED luminaire of 30 watts, including repair to its driver, PCB card, sensor, solar photo voltic panel/cell, inbuild Li-on batteries and any physical damage cause to panels, pole, hoding strip, GI supporter strips etc (fabrication of GI/MS frame on site and repairing tilted frames) by deploying authorised rep of Aura solar lightings, complete all as specified and directed Note: (i) Replacement of spare parts is included in quoted rates including battery, driver, PCB card, sensor, connecting terminals,photo voltic cell/panel, LED luminaire of 30 watt. (ii) contractor has to arrange T&P & labour for fabrication on site, repairing any physical damage to Solar street ights. (iii) Visiting charges by technicians is any nos of time included in quoted rates. (iv) Panelity of Rs. 1000 per light per day will recovered from contractor if light not found serviceable.
S&F of LED bollard of 9 watt tulip type with soft 360° light, IP 65 protection, Resistant to corrosion for better optics and uniform distribution including making foundation (As per manufacturer specification) for bollard light along with bolt integrated with PCC and nut & washer to tightened bollard light and making provision for cable entry and exit through pcc block, complete all as specified and directed.
S&F of constant current led driver of existing street light model suitable for 30 watt LED street Light complete all as specified and direct. Make:- C&S/Crompton/Bajaj
S&F of constant current led driver model suitable for 45 watt LED street Light complete all as specified and direct. Make: C&S/Crompton/Bajaj
S&F of constant current led driver model suitable for 72 watt LED street Light complete all as specified and direct. Make:C&S/Crompton/Bajaj
Supply and fixing of 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed .
Supply and fixing of round shape 12 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders,LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed
M/S PARKASH ENTERPRISES
NAVDURGA BUILDERS
MOHIT ENTERPRISES
YASHVI ENGINEERS
akhil enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .