Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹6.9 L
EMD Value
₹5,000
Closing Date
26 Dec 2026, 3:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
The Dy.CE and Area Manager Bankura Area Office
BANKURA AREA OFFICE
Internal Electrical Installation and wiring of the First Floor of Inspection Bungalow I.B including supply of all materials at Bankura Area Office WBSETCL as per schedule
2026_SETCL_1049840_1
SE/AO/BNK/e-NIT/ELEC/26-27/04
Open Tender
Electric Works
Item Rate
BANKURA 132 KV SUB STATION
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹5,000
BANKURA AREA OFFICE
20 Nov 2026
20 Nov 2026
31 Dec 2026
20 Nov 2026
26 Dec 2026
4 Dec 2026
2 Dec 2026
90 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | A1 [DSR NS-8] Sub-main, new I.B. main DB (A6) to the distribution block A13 in FFDB-1, 4 x 25 sq.mm + 2 x 10 sq.mm earth wire, FRLS/HFFR PVC Cu in 32 mm medium class PVC conduit (est. 30 m + 20% provision = 36 m). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3) — any ISI-marked make. | 36 | Mtr | - | - |
| 2 | A2 [DSR NS-1] 63 A TPN MCB, C-curve, 10 kA, on the FIRST-FLOOR OUTGOING WAY of the new I.B. main DB (A6), in series with the 300 mA RCCB A7 — overcurrent protection of sub-main A1 and link feeder A5 — complete with connections, testing and commissioning. Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric. | 1 | No | - | - |
| 3 | A2A [DSR NS-7] 80 A four pole (TPN) MCB, C-curve, 10 kA, IS/IEC 60947-2, DIN-rail mounted, MAIN INCOMER of the new I.B. main DB (A6) — the consumer’s circuit breaker, CEA Regulations 2023, Reg. 37 — complete with connections, testing and commissioning. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric. | 1 | No | - | - |
| 4 | A3 [DSR 2.5.3] 12 way (4+36) TPN vertical MCB DB, double door, without MCBs and incomer — FFDB-1 and FFDB-2. Sheet steel, powder coated, IP-42/43, IS/IEC 61439-3. Make: factory-assembled, of the make of the MCBs (ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric). | 2 | No | - | - |
| 5 | A4 [DSR NS-11] 63 A, 4 pole, 415 V RCCB, 30 mA sensitivity, type A (IS 12640-1 / IEC 61008-1), in MCB DB — incomer and isolating switch of FFDB-1 and FFDB-2, each fed from the distribution block A13 — complete with connections, testing and commissioning. Make: any ISI-marked, preferably the make of the MCBs. | 2 | No | - | - |
| 6 | A5 [DSR NS-8] Link feeder, distribution block A13 in FFDB-1 (line side of the FFDB-1 RCCB) to FFDB-2, 4 x 25 sq.mm + 2 x 10 sq.mm earth wire, FRLS/HFFR PVC Cu in 32 mm medium class PVC conduit (est. 8 m). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3) — any ISI-marked make. | 8 | Mtr | - | - |
| 7 | A6 [DSR 2.5.2] 8 way (4+24) TPN vertical MCB DB, double door, without MCBs and incomer, with an incomer section for the 80 A four pole MCB A2A — NEW I.B. MAIN DB beside the WBSEDCL 3-phase meter. Sheet steel, powder coated, IP-42/43, IS/IEC 61439-3. Make: factory-assembled, of the make of the MCBs (ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric). | 1 | No | - | - |
| 8 | A7 [DSR NS-6] 63 A, 4 pole, 415 V RCCB, 300 mA sensitivity, type AC, in MCB DB — first-floor outgoing of the new I.B. main DB, also isolating the first floor — complete with connections, testing and commissioning. Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs. | 1 | No | - | - |
| 9 | A8 [DSR 2.10.2] 5-32 A SPN MCB (32 A), C-curve, 10 kA — ground-floor outgoing of the new I.B. main DB. Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric. | 1 | No | - | - |
| 10 | A9 [DSR 2.14.2] 40 A 2 pole RCCB 30 mA — ground-floor outgoing of the new I.B. main DB (CEA Regulations 2023, Reg. 44). Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs. | 1 | No | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.71 MB
BOQ_2569274.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .