| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.3 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹34.3 L+₹2.8 L (8.74%)Rejected-AOC | L2 | Rejected-AOC Other than lowest Bidder | |
| 3 | L3₹34.8 L+₹3.3 L (10.3%)Rejected-AOC 499 A VIDHYUT NAGAR A AJMER ROAD JAIPUR 302021 | JAIPUR | JAIPUR | RAJASTHAN | 302021 | L3 | Rejected-AOC Other than lowest Bidder | |
| 4 | L4₹36.5 L+₹5.0 L (15.8%)Rejected-AOC 70 VARDHMAN NAGAR A P O SHYAM NAGAR AJMER ROAD JAIPUR PIN 342019 | JAIPUR | 342019 | L4 | Rejected-AOC Other than lowest Bidder | |
| 5 | L5₹36.7 L+₹5.1 L (16.3%)Rejected-AOC | L5 | Rejected-AOC Other than lowest Bidder |
Tender Value
₹44.3 L
EMD Value
₹88,500
Closing Date
12 Aug 2020, 6:00 pmClosed
GE(S) Jaipur
GE(S) Jaipur, MES, Kalyan Marg, bani park, Jaipur-302006
Special repair to LT switch gear, panels, cables near bldg No. P-162,P-163 and P-551 Offrs qtr, Bldg No. P-112 to 114, 154 to 156 and P-358 and 359 offrs qtr and spl repair to LT system at Signal centre in Zone-I area at Jaipur Mil Stn under GE(S)Jpr
2020_MES_363604_1
GE (S)J-19P/2020-21 8572/ /E8
Open Tender
Civil Works
Item Rate
180 days
Jaipur
Category D b( i )
9 documents required · 9 mandatory
₹500
Yes
GE (S) Jaipur
₹88,500
Yes
14 Sept 2020
24 Jul 2020
14 Aug 2020
24 Jul 2020
12 Aug 2020
7 Aug 2020
24 Jul 2020 - 31 Jul 2020
Amount
01/SR/M&O/2020-21 Excavation in trenches n.exc 1.5 metre wide and n.exc 1.5 metre in depth for foundation etc or for laying of cable etc and getting out in soft/loose soil. 01/SR/M&O/20-21 - 419 03/SR/M&O/20-21 - 505 04/SR/M&O/20-21 - 394
Returning, filling in, including spreading, leveling, watering and well ramming in layers n.exc 25 cm in depth. 01/SR/M&O/20-21- 282 03/SR/M&O/20-21- 340 04/SR/M&O/20-21- 245
Removal of excavated material(soil) to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 m above the starting point. 01/SR/M&O/20-21- 137 03/SR/M&O/20-21- 165 04/SR/M&O/20-21- 119
M&L bricks for protection cover to under ground cable (with old size sub class `B` bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10 mm as directed by Engineer in-charge. 01/SR/M&O/20-21 - 13.4 03/SR/M&O/20-21 - 16.00 04/SR/M&O/20-21 - 11.70
M & L Sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required cover. 01/SR/M&O/20-21 - 125.60 03/SR/M&O/20-21 - 151.00 04/SR/M&O/20-21 - 109.00
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming:- (i) MCCB 250 amps, 4 pole, 35 KA with adjustable thermal over load release 50 Hz, 415 volts grade - 01 Nos. Make: L&T , Legrand, Sechneider, C&S. (ii) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 400 Amp, 4 pole, not less than 100 cm long mounted on insulators for incomming supply 01 No. Outgoing (i) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release 50 Hz, 415 volts grade - 4 Nos. Make:L&T , Legrand, Sechneider,C&S. (ii) MCCB 63 amps, 4 pole,25 KA , with adjustable thermal over load release 50 Hz, 415 volts grade - 1 Nos. Make - L&T , Legrand, Sechneider,C&S. (iii) Time Switch complete Assymbly astro rex D 21- 01 No and 3 phase contactor with on off control MCB TPN 63 amp and other connected accessories complete all as specied and directed by Engineer-in-Charge. Make:- L&T , Legrand, Sechneider,C&S Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands.
All as above items No -06 here and there but with following accessoies comlete. For Sub Panel of Incoming (a) MCCB 250 amps, 4 pole, 35 KA with adjustable thermal over load release50 Hz, 415 volts grade - 01 Nos. Make: L&T , Legrand, Sechneider,C&S. (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 400 Amp, 4 pole, not less than 100 cm long mounted on insulators for incomming supply 01 No. (c) LED indicating lamps (R, Y & B) -01 Set. Outgoing (i) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release 50 Hz, 415 volts grade - 4 Nos. Make:L&T , Legrand, Sechneider,C&S.
M & L PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of stay assembly / struts / poles etc. 01/SR/M&O/20-21 - 6.5 04/SR/M&O/20-21 - 7.4
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping including necessary form work complete. 01/SR/M&O/20-21 - 0.60 04/SR/M&O/20-21 - 0. 70
Dismantling of prestressed cement concrete poles/RCC poles/Steel poles complete of any size including PCC foundation and necessary excavation & earth work and making good to disturbed surfaces as directed by Engineer-in-Charge. 01/SR/M&O/20-21 - 15.0 04/SR/M&O/20-21 - 18.0
Supply & install steel tubular swaged poles Type 410 SP-31 (9 Metres long) complete with CI base plate and finial including earth work and painting as directed by Engineer-in-Charge. 01/SR/M&O/20-21 - 15.0 04/SR/M&O/20-21 - 18.0
S & F 40 mm dia light grade GI pipe bracket single swan neck shape suitable to fix on top of tubular pole complete with clamps, nuts, bolts and washers. 01/SR/M&O/20-21 - 15.0 03/SR/M&O/20-21 - 18.0
S&F in replacement of conventional street light fitting any type/capacity with LED street light fitting 60W (IP-66) with integrated lens for asymmetrical light distribution, system lumen output of ≥ 6500 (± 2.5% )lumens, system efficacy ≥ 100 lm/W, LED lumen efficacy ≥ 120 lm/W, CCT 3000K~6500K, CRI >70, electronic driver, 10 kV in-built surge protection, Output open/short circuit protection, phase to phase protection, over-voltage protection, etc. as per IS-15885, THD<10%, PF ≥ 0.95, housed in pressure die cast aluminium housing including necessary fabrication for fixing of LED stree tlight all as per directed by Engineer-in-Charge. Make :- Syska, Havells,Philips, Bajaj, Wipro 01/SR/M&O/20-21 - 15.0 03/SR/M&O/20-21 - 17.0
S & F in replacement of thermoplastic, polystyrene unbreakable junction box size 260 x 210 x 116 mm suitable for pole mounted outdoor type IP 65 insulated complete with FI clamps & nuts, bolts, washers and including terminal block heavy duty with phase seperators between R, Y, B terminals, one MCB SP 6 amp 10 KA, all duly fixed on din channel, cable glands for cable entry.Make : Hensel Cat Part No K9350 or eqvt in SINTEX / EQVT. 01/SR/M&O/20-21 - 15.0 03/SR/M&O/20-21 - 17.0
Dismantling old existing ACSR conductor of any type/size for reuse or to be deposited to MES store yard all as directed by Engr-in-Charge. 01/SR/M&O/20-21 - 0.70 03/SR/M&O/20-21 - 1.00 04/SR/M&O/20-21 - 0.40
Dismantling old existing MS cross arms of any type/shape. 01/SR/M&O/20-21 - 0.50 03/SR/M&O/20-21 - 1.00 04/SR/M&O/20-21 - 0.40
Dismantling old existing Insulators of any type/shape all as directed by Engr-in-Charge. 01/SR/M&O/20-21 - 60.00 03/SR/M&O/20-21 - 68.00 04/SR/M&O/20-21 - 24.00
Supplying, laying, connecting and testing in trenches, under floors/ roads or on walls Cable XLPE insulated screened PVC bedded galvanized steel strips or wire armored, electric power cables (heavy duty) ISI marked with stranded aluminium conductor, 1100 volts grade, of following sizes
120 Sqmm 3.5 Core. 01/SR/M&O/20-21 - 525.00 04/SR/M&O/20-21 - 90.00
35 Sqmm, 3½ core cable. 01/SR/M&O/20-21 - 975.00 03/SR/M&O/20-21 - 375.00 04/SR/M&O/20-21 - 100.00
16 Sqmm, 4 core cable. 01/SR/M&O/20-21 - 630.00 03/SR/M&O/20-21 - 555.00 04/SR/M&O/20-21 - 765.00
150 Sqm, 3.5 Core cable. 04/SR/M&O/20-21 - 170
95 Sqmm, 3.5 cable. 03/SR/M&O/20-21 - 620
70 Sqmm, 3.5 core cable. 04/SR/M&O/20-21 - 85.00
50 Sqmm, 3.5 core cable. 04/SR/M&O/20-21 - 255
25 Sqmm, 3.5 core cable. 03/SR/M&O/20-21 - 955.00 04/SR/M&O/20-21 - 200.00
16 Sqmm, 2 core cable. 04/SR/M&O/20-21 - 150.00
M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 25mm x 4mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. 01/SR/M&O/20-21 - 8.00 03/SR/M&O/20-21 - 8.00 04/SR/M&O/20-21 - 10.00
Supply & fixing or laying galvanised steel tubing light grade 80 mm dia (ISI marked) for protection of under ground cable on poles / walls under road crossing all as specified and directed by Engr -in-Charge. 01/SR/M&O/20-21 - 30.00 03/SR/M&O/20-21 - 36.00 04/SR/M&O/20-21 - 18.00
S&F GI tubing light grade with fittings to wall or pole as required of 50 mmdia including bends as in cooping etc. complete. 01/SR/M&O/20-21 - 18.00 04/SR/M&O/20-21 - 18.00
M&L for boring of existing road/path for laying of GI pipe protection for UG cable including making good distrurbed area/surface all as specified and directed. 01/SR/M&O/20-21 - 24.00 03/SR/M&O/20-21 - 24.00 04/SR/M&O/20-21 - 18.00
M&L for existing LT feeder pillar box repair in doors, hinges, locking,welding cutting and painting and removing all MCCBs , bus bar after panel rapair and refixing poperly including making good distrurbed all as specified and directed.
Supply and fixing in replacement of PVC sheathed multi stranded copper conductor cable of size 2.5 sqmm 3 core. 01/SR/M&O/20-21 - 150.00 03/SR/M&O/20-21 - 150.00
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming (a) MCCB 400 amps, 4 pole, 35 KA with adjustable thermal over load release . 50 Hz, 415 volts grade - 01 Nos. Make: L&T , Legrand, Scheineider,C&S. (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 100 cm long mounted on insulators for incomming supply 01 No. Outgoing (a) MCCB 200 amps, 4 pole, 35/36 KA with adjustable thermal over load release . 50 Hz, 415 volts grade - 1 Nos. Make: L&T , Legrand, Scheineider,C&S. (b) MCCB 160 amps, 4 pole, 35/36 KA with adjustable thermal over load release . 50 Hz, 415 volts grade - 4 Nos. Make: L&T , Legrand, Scheineider,C&S. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands.
All as above items No -25 here and there but with following accessoies comlete. Incoming (i) MCCB 200 amps, 4 pole, 25 KA, with adjustable thermal release, 50 Hz, 415 volts grade - 01No. L&T , Legrand, Scheineider,C&S. (ii) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 400Amp,4 pole, not less than 45 cm long mounted on insulators 01 set Outgoing (i) MCCB 160 amps, 4 pole, 25 KA, with adjustable thermal release, 50 Hz, 415 volts grade - 01No. L&T , Legrand, Scheineider,C&S. (ii) MCCB 100 amps, 4 pole, 25 KA, with adjustable thermal release, 50 Hz, 415 volts grade - 04No. L&T , Legrand, Scheineider,C&S. (iii) Time Switch complete Assymbly astro rex D 21- 01 No and 3 phase contactor with on off control MCB TPN 63 amp and other connected accessories complete all as specied and directed by Engineer-in-Charge. Make:- L&T , Legrand, Sechneider Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands.
All as above items No -25 here and there but with following accessoies comlete. Incoming (i) MCCB 160amps, 4 pole, 25 KA, with adjustable thermal release, 50 Hz, 415 volts grade - 01No. L&T , Legrand, Scheineider,C&S. (ii) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 300Amp,4 pole, not less than 45 cm long mounted on insulators 01 set. Outgoing (a) MCCB 100 amps, 4 pole, 25 KA, with adjustable thermal release, 50 Hz, 415 volts grade - 04No. L&T , Legrand, Scheineider,C&S. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands.
S & F in replacement MCCB 4 pole, 415 volts grade with adjustable short circuit and over load of following rating :-
200 amp, 36 KA suitable frame size Make:-L&T ,Scineiders, legrand,C&S.
250 amp, 36 KA suitable frame size Make:-L&T ,Scineiders, legrand,C&S.
S&F MCCB 100 Amp 4 pole ,25 KA confirming with sheet metal enclouser complete all as specified and directed by Engineer-in-ChargeMake:-L&T Scineiders, Legrand,C&S.
ON Load Changeover switch 400 amp. Make:-L&T ,Scineiders, Legrand,C&S.
M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with copper earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to copper earth strip 25mm x 4mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 20mm bore medium grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete.
Supply and fixing of 60 W LED street light with lens optics on LEDs, IP66 protected luminaire fixture made from pressure dia cast aluminum housing & heat resistance toughned glass cover with one number of 60 W driver, operating voltage range 130-275 Volt, suitable upto 50 mm mounting pipe as directed by engineer-in-charge. Make: Bajaj, Syska, Philips/Wipro/HPL Crompton Greaves.
S&F polycarbonated unbreakable Junction box with fuse provn and suitable connection for three phase incoming cable, single phase out going cable endorsed in thermo plastic enclosure. Shock proof safe IP 65, weather proof, rust proof, dust and water proof internally embedded gasket with provn for cable entry through glade of size 260x210x116mm along with MS Clamps copper bus bar for three phase connection and 01X MCB SP 6 Amp 10 KA incl single phase 2.5 sqmm copper conductor PVC sheathed as required at site for electric connection to LED lights and connecting wire from JB to LED fitting as required complete all as specified directed.
M/S Anil Enterprises
DIVYA ASSOCIATES
Pioneer Enterprises
SHREE BHAGWATI ENTERPRISES
LAKSHMI ASSOCIATES
Ravi Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .