Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.8 LAdmitted-Finance 8TH FLOOR BRIGADE OPUS KODIGEHALLI MAIN ROAD BANGALORE KARNATAKA 560092 | BENGALURU URBAN | KARNATAKA | 560092 | L1 | Admitted-Finance | |
| 2 | L2₹35.8 L+₹4.0 L (12.7%)Admitted-Finance 46C 5TH FLOOR RAFI AHMED KIDWAI ROAD KOLKATA KOLKATA WEST BENGAL 700016 | KOLKATA | WEST BENGAL | 700016 | L2 | Admitted-Finance | |
| 3 | L3₹52.8 L+₹21.1 L (66.3%)Admitted-Finance SHOP 1 GOURHARI APARTMENT NSB ROAD OPP HDFC BANK BARDHAMAN WEST BENGAL 713347 | PASCHIM BARDHAMAN | WEST BENGAL | 713347 | L3 | Admitted-Finance | |
| 4 | Rejected-Technical | - | Rejected-Technical Technically Rejected | |
| 5 | Rejected-Technical | - | Rejected-Technical Technically Rejected |
| Sl No | Description | Qty | Unit | SNEHA TECHNO EQUIPMENTS PRIVATE LIMITED L2 | Hitachi Energy India Limited L1 | Sashi Commercial Co L3 |
|---|---|---|---|---|---|---|
| 0.00Procurement of 04 nos. 220 KV Outdoor Type Current Transformer as maintenance spare for DPPS, DPL. | ||||||
| 1.00 | 220 KV, Outdoor Type Current Transformer:
5 Core, Ratio: 1600 – 1000 / 1-1-1-1-1 A,
Technical Particulars:
1st Core: 1600 – 1000 / 1 A, 20 VA, Class 0.2S, ISF < 5
Balance Cores: 1600 – 1000 / 1 A, PS Class
KPV: 1000 V, Excitation Current at VK < 50 mA,
Secondary Resistance at 75 °C < 8 Ω (at 1000 / 1 Tap)
Standard: IS: 2705 / IEC: 60044–1 / IEC: 61869,
Highest System Voltage: 245 KV, Insulation Level: 460 kV / 1050 KVP, Frequency: 50 Hz, Short Time Current Rating: 40 KA for 3 Seconds
Extended Current: 120 %, Insulator: Porcelain with Creepage 25 mm / KV
Terminal Connectors: Both side terminal connectors suitable for CT stud to Twin Moose ACSR conductor. (Universal Take-Off) | 1 | No. | 8,70,910 ₹8,70,910 | 7,90,000 ₹7,90,000 Lowest | 13,05,000 ₹13,05,000 |
| 2.00 | 220 KV, Outdoor Type Current Transformer:
5 Core, Ratio: 800 – 400 – 200 / 1-1-1-1-1 A,
Technical Particulars:
1st Core: 800-400- 200 / 1 A, 20 VA, Class 0.2S, ISF < 5
Balance Cores: 800-400- 200 / 1 A, PS Class
KPV: 1200 V (at highest tap), Excitation Current at VK < 60 mA (at lowest tap)
Secondary Resistance at 75°C < 5Ω (at highest tap)
Standard: IS: 2705 / IEC: 60044-1 / IEC: 61869,
Highest System Voltage: 245 KV, Insulation Level: 460 KV / 1050 KVP
Frequency: 50 Hz, Short Time Current Rating: 40 KA for 3 Seconds
Extended Current: 120 %, Insulator: Porcelain with Creepage 25 mm / KV
Terminal Connectors: Both side terminal connectors suitable for CT stud to Twin Moose ACSR conductor. (Universal Take-Off) | 3 | Nos. | 9,02,500 ₹27,07,500 | 7,95,000 ₹23,85,000 Lowest | 13,25,000 ₹39,75,000 |
Tender Value
Refer Docs
EMD Value
₹63,000
Closing Date
7 Sept 2026, 4:00 pmClosed
AGM S and P
Office of the AGM S and P, 5th Floor, Technical Building, DPPS, Durgapur-713201
PROCUREMENT OF 04 NOS 220 KV OUTDOOR TYPE CURRENT TRANSFORMER AS MAINTENANCE SPARE FOR DPPS, DPL
2026_DPL_1036181_1
DPL/DPPS/PUR/NIT/DJ/110/26-27
Open Tender
SUPPLY OF ELECTRICAL GOODS/EQUIPMENTS
Item Wise
90 days
Durgapur
As per NIT
2 documents required · 2 mandatory
₹0
₹63,000
Yes
5 Oct 2026
4 Aug 2026
9 Sept 2026
4 Aug 2026
7 Sept 2026
5 Aug 2026
5 Aug 2026 - 7 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 0 | Procurement of 04 nos. 220 KV Outdoor Type Current Transformer as maintenance spare for DPPS, DPL. | - | - | - | - |
| 1 | 220 KV, Outdoor Type Current Transformer:
5 Core, Ratio: 1600 – 1000 / 1-1-1-1-1 A,
Technical Particulars:
1st Core: 1600 – 1000 / 1 A, 20 VA, Class 0.2S, ISF < 5
Balance Cores: 1600 – 1000 / 1 A, PS Class
KPV: 1000 V, Excitation Current at VK < 50 mA,
Secondary Resistance at 75 °C < 8 Ω (at 1000 / 1 Tap)
Standard: IS: 2705 / IEC: 60044–1 / IEC: 61869,
Highest System Voltage: 245 KV, Insulation Level: 460 kV / 1050 KVP, Frequency: 50 Hz, Short Time Current Rating: 40 KA for 3 Seconds
Extended Current: 120 %, Insulator: Porcelain with Creepage 25 mm / KV
Terminal Connectors: Both side terminal connectors suitable for CT stud to Twin Moose ACSR conductor. (Universal Take-Off) | 1 | No. | 100 | ₹100 |
| 2 | 220 KV, Outdoor Type Current Transformer:
5 Core, Ratio: 800 – 400 – 200 / 1-1-1-1-1 A,
Technical Particulars:
1st Core: 800-400- 200 / 1 A, 20 VA, Class 0.2S, ISF < 5
Balance Cores: 800-400- 200 / 1 A, PS Class
KPV: 1200 V (at highest tap), Excitation Current at VK < 60 mA (at lowest tap)
Secondary Resistance at 75°C < 5Ω (at highest tap)
Standard: IS: 2705 / IEC: 60044-1 / IEC: 61869,
Highest System Voltage: 245 KV, Insulation Level: 460 KV / 1050 KVP
Frequency: 50 Hz, Short Time Current Rating: 40 KA for 3 Seconds
Extended Current: 120 %, Insulator: Porcelain with Creepage 25 mm / KV
Terminal Connectors: Both side terminal connectors suitable for CT stud to Twin Moose ACSR conductor. (Universal Take-Off) | 3 | Nos. | 100 | ₹300 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.17 MB
BOQ_2545458.xls
BOQ • 0.27 MB
4.pdf
PDF • 0.41 MB
3.pdf
PDF • 0.42 MB
3.pdf
PDF • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .