Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.2 CrAccepted-AOC 13 29 304 IIIRD FLOOR EAST PATEL NAGAR OPP HOTEL SIDDARATHA NEW DELHI 110008 | WEST | DELHI | 110008 | ₹1.2 Cr | 1 | Accepted-AOC Being lowest and reasonable rates |
| 2 | 2₹1.2 Cr+₹8.4 L (7.26%)Rejected-Finance | ₹1.2 Cr+₹8.4 L (7.26%) | 2 | Rejected-Finance Not being lowest tenderer |
| 3 | 3₹1.3 Cr+₹12.0 L (10.3%)Rejected-Finance BUILDING NO FLAT NO 19 6TH CROSS ROAD SANJEEVINI NAGAR MUDALAPALYA BANGALORE 560072 | BANGALORE | BANGALORE | KARNATAKA | 560072 | ₹1.3 Cr+₹12.0 L (10.3%) | 3 | Rejected-Finance Not being lowest tenderer |
| 4 | 4₹1.3 Cr+₹13.9 L (12.0%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | ₹1.3 Cr+₹13.9 L (12.0%) | 4 | Rejected-Finance Not being lowest tenderer |
| 5 | 5₹1.3 Cr+₹16.4 L (14.1%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹1.3 Cr+₹16.4 L (14.1%) | 5 | Rejected-Finance Not being lowest tenderer |
Tender Value
₹1.5 Cr
EMD Value
₹2.2 L
Closing Date
30 Jun 2022, 6:00 pmClosed
CWE U
HQ CWE U Delhi Cantt 110010
PROVN OF DG SETS FOR BACKUP POWER ARRANGEMENT AT EXTERNAL WATER SUPPLY INSTALLATIONS UNDER GE U WATER SUPPLY DELHI CANTT 10
2022_MES_526893_1
89037/CWE(U)/D-06/2022-23/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
Delhi Cantt
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
GE U Water Supply
₹2.2 L
Yes
8 Aug 2022
27 May 2022
2 Jul 2022
27 May 2022
30 Jun 2022
25 Jun 2022
Amount
Supplying, installing, testing & commissioning of factory assembled silent Diesel Engine driven generating set 1500RPM of capacity 380 KVA available, 3 phase, 4 wire,415 volt, 0.8 PF, complete with control panel including integrated powder coated acoustic enclosure as per CPCB regulations and duly certified by agencies/labs designated by MoEF/CPCB norms as per new guidelines of Delhi NCR at 100% load under free field conditions for noise and sound pollution level, etc floor mounted including PCC foundation as per manufacturer's instructions complete all as specified and directed and comprising of the following :- (A) DIESEL ENGINE required capacity for driving 380 KVA alternator multi cylinder, vertical type, 4 stroke, water cooled, electric start conforming to IS : 10001/10002/BS-5514 for continuous running capable of taking 10% overload for one hour in 12 hours complete and comprising of the following :-
(i) Radiator (ii) Radiator fan with guard (iii) Flywheel with starter ring (iv) Air cleaner oil bath type (v) Vacuum indicator (vi) Electronic governor class 1A (vii) Exhaust silencer (viii) Fuel filter & fuel hoses (ix) Fuel injection pump (FIP) (x) Fan & water pump assembly (xi) Lub oil filter & Pump (xii) Electric starting system with battery charging alternator and axial type starter motor including adequate number of high capacity maintenance free lead acid battery 2 NOs, 12 volts 180 AH DC as per manufacturers requirement including interconnecting cables/leads with terminals complete with starting/stopping switch, volt meter etc - 01 Set. (xiii) Engine safety shut down system against low lub oil pressure and high water temperaure (xiv) Exhaust gas driven turbo charger (xv) Oil filter (xvi) Lub oil cooler (xvii) All accessories as required.
(B) ENGINE INSTRUMENT PANEL digital type indicating the following (i) Starting switch on/off (ii) Water temp indicator (iii) Hour meter cum RPM indicator (iv) Lub oil pressure (v) Lub oil temperature (vi) Battery charging meter/indicator (vii) Safety alarm against high water temp and lub oil pressure (C) ALTERNATOR Shall be self excited, self regulated, brush less for 380 KVA continuous operation at the speed of 1500 RPM at 415 volts, 50Hz , three phase four wire system with advance electric voltage regulator to ensure high voltage accuracy with +1% with class H insulation and SPDP enclosure directly coupled with engine through flexible coupling and confirming IS- 13364 complete- 1 No. (D) Common fabricated base frame for engine & alternator made from structural channel, jerk proof PCC 1:2:4 type B1 foundation including adequate number of .suitable anti-vibration pads all as per the recommendation of the manufacture- 01 No (NOTE:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor.
(E) Steel fuel tank fabricated out of 14 SWG MS sheet of capacity not less than 12 hrs continuous operation, with fuel level guage, drain plug, locking arrengements, etc with & including GI pipe connections duly laid as per engineering practice complete. (F) AMF CONTROL PANEL Supply, fabrication, fixing commissioning and testing, factory made, floor mounted outdor type, (Make as per OEM) cubical automatic mains failure panel suitable for 380 KVA DG set, fabricated using 14 guage thick CRCA sheet, powder coated painting, suitable rated bus bar, internal wiring with control MCB, provn of connecting incoming & outgoing leads/bus bas as approved with and including the following accessories as under:- (i) Master switch for auto/manual/reset/off/test- 01 No (ii) Ammeter digital type 96x96 mm to read 0 - 630 amps with CT's 1 set of 3, aux supply 230 volts, AC, accuracy class 1.0 (iii) Voltmeter digital type,96 x 96 mm to read 0 - 500 volts aux supply 230 volts, AC, accuracy class 1.0 (iv) (a) Digital frequency meter -01 No. aux supply 230 volts, AC (b) Digital Energy meter Aux supply 230 Volt AC/3 Phase 4 wire. (v) Push button start, stop/ reset - 01 No (vi) Set of lamp for indicating load on DG, high cylinder temperature, load on mains, set fails to start, low oil pressure
Supplying, installing, testing & commissioning of factory assembled silent Diesel Engine driven generating set 1500RPM of capacity 160 KVA, 3 phase, 4 wire,415 volt, 0.8 PF, complete with control panel including integrated powder coated acoustic enclosure as per CPCB regulations and duly certified by agencies/labs designated by MoEF/CPCB norms as per new guidelines of Delhi NCR at 75% load under free field conditions for noise and sound pollution level, etc floor mounted including PCC foundation as per manufacturer's instructions complete all as specified and directed and comprising of the following :-
(A) DIESEL ENGINE required capacity for driving 160 KVA alternator multi cylinder, vertical type, 4 stroke, water cooled, electric start conforming to IS : 10001/10002/BS-5514 for continuous running capable of taking 10% overload for one hour in 12 hours complete and comprising of the following :- (i) Radiator (ii) Radiator fan with guard (iii) Flywheel with starter ring (iv) Air cleaner oil bath type (v) Vacuum indicator (vi) Electronic governor class 1A (vii) Exhaust silencer (viii) Fuel filter & fuel hoses (ix) Fuel injection pump (FIP) (x) Fan & water pump assembly (xi) Lub oil filter & Pump (xii) Electric starting system with battery charging alternator and axial type starter motor including adequate number of high capacity maintenance free lead acid battery 2 NOs, 12 volts 180 AH DC as per manufacturers requirement including interconnecting cables/leads with terminals complete with starting/stopping switch, volt meter etc - 01 Set.
(xiii) Engine safety shut down system against low lub oil pressure and high water temperaure (xiv) Exhaust gas driven turbo charger (xv) Oil filter (xvi) Lub oil cooler (xvii) All accessories as required. (B) ENGINE INSTRUMENT PANEL digital type indicating the following (i) Starting switch on/off (ii) Water temp indicator (iii) Hour meter cum RPM indicator (iv) Lub oil pressure (v) Lub oil temperature (vi) Battery charging meter/indicator (vii) Safety alarm against high water temp and lub oil pressure (C) ALTERNATOR Shall be self excited, self regulated, brush less for 160 KVA continuous operation at the speed of 1500 RPM at 415 volts, 50Hz , three phase four wire system with advance electric voltage regulator to ensure high voltage accuracy with +1% with class H insulation and SPDP enclosure directly coupled with engine through flexible coupling and confirming IS- 13364 complete- 1 No.
(D) Common fabricated base frame for engine & alternator made from structural channel, jerk proof PCC 1:2:4 type B1 foundation including adequate number of .suitable anti-vibration pads all as per the recommendation of the manufacture- 01 No (NOTE:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor. (E) Steel fuel tank fabricated out of 14 SWG MS sheet of capacity not less than 12 hrs continuous operation, with fuel level guage, drain plug, locking arrengements, etc with & including GI pipe connections duly laid as per engineering practice complete. (F) AMF CONTROL PANEL Supply, fabrication, fixing commissioning and testing, factory made, floor mounted outdoor type, (Make as per OEM) cubical automatic mains failure panel suitable for 160 KVA DG set, fabricated using 14 guage thick CRCA sheet, powder coated painting, suitable rated bus bar, internal wiring with control MCB, provn of connecting incoming & outgoing leads/bus bas as approved with and including the following accessories as under:-
(viii) Fault accept/reset push button (ix) Set of relays and contactor with MCCB, 4 ploe, 320 Amps,415 volt, 36/35 KA for automatic start & automatically shut down of DG set of adjustable 75 to 100%-02 Nos (x) By pass arrangement by providing onload change over switch of 320 Amps 4 Pole in AMF including connection with material - 02 Nos Note : AMF Panel shall be installed out side the coustic enclosure and foundation of DG Set and other civil work as per recommendation of OEM shall be included in quoted rate.
Supplying, installing, testing & commissioning of factory assembled silent Diesel Engine driven generating set 1500 RPM of capacity 125 KVA, 3 phase, 4 wire,415 volt, 0.8 PF, complete with control panel including integrated powder coated acpistoc enclosure as per CPCB regulations and duly certified by agencies/labs designated by MoEF/CPCB norms as per new guidelines of Delhi NCR at 75% load under free field conditions for noise and sound pollution level, etc floor mounted including PCC foundation as per manufacturer's instructions complete all as specified and directed and comprising of the following :- (A) DIESEL ENGINE required capacity for driving 125 KVA alternator multi cylinder, vertical type, 4 stroke, water cooled, electric start conforming to IS : 10001/10002/BS-5514 for continuous running capable of taking 10% overload for one hour in 12 hours complete and comprising of the following :- (i) Radiator cooling (ii) Radiator fan with guard (iii) Flywheel with starter ring (iv) Air cleaner oil bath type (v) Vacuum indicator (vi) Electrical governor class 1A
(vii) Exhaust silencer (viii) Fuel filter & fuel hoses (ix) Fuel injection pump (FIP) (x) Fan & water pump assembly (xi) Lub oil filter & Pump (xii) Electric starting system with battery charging alternator and axial type starter motor including adequate number of high capacity maintenance free lead acid battery 2 NOs, 12 volts 150 AH DC as per manufacturers requirement including interconnecting cables/leads with terminals complete with starting/stopping switch, volt meter etc - 01 Set. (xiii) Engine safety shut down system against low lub oil pressure and high water pressure (xiv) Exhaust gas driven turbo charger (xv) Oil filter (xvi) Lub oil cooler (xvii) Accessories as required. (B) ENGINE INSTRUMENT PANEL digital type indicating the following (i) Starting switch on/off (ii) Water temp guage (iii) Hour meter cum RPM indicator
(iv) Lub oil pressure (v) Lub oil temperature (vi) Battery charging meter (vii) Safety alarm against high water temp and lub oil pressure (C) ALTERNATOR Shall be self excited, self regulated, bush less for 125 KVA continuous operation at the speed of 1500 RPM at 415 volts, 50Hz , three phase four wire system with advance electric voltage regulator to ensure high voltage accuracy with + 1% with class H insulation and SPDP enclosure directly coupled with engine through flexible coupling and confirming IS- 13364 complete- 1 No. (D) Common fabricated base frame for engine & alternator made from structural channel, jerk proof PCC 1:2:4 type B1 foundation including adequate number of .suitable anti-vibration pads all as per the recommendation of the manufacture- 01 No (NOTE:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor.
(E) Bottom mounted steel fuel tank fabricated out of 14 SWG MS sheet of capacity not less than 8 hrs continuous operation, inside canopy, with fuel level guage, drain plug, locking arrengements, etc with & including GI pipe connections duly laid as per engineering practice complete (F) AMF CONTROL PANEL Supply, fabrication, fixing commissioning and testing, factory made, floor mounted outdoor type, (Make as per OEM) cubical automatic mains failure panel suitable for 125 KVA DG set, fabricated using 14 guage thick CRCA sheet, powder coated painting, suitable rated bus bar, internal wiring with control MCB, provn of connecting incoming & outgoing leads/bus bas as approved with and including the following accessories as under:- (i) Master switch for auto/manual/reset/off- 01 No (ii) Ammeter digital type 96x96 mm to read 0 - 400 amps with CT's 1 set of 3, aux supply 230 volts, AC, accuracy class 1.0 (iii) Voltmeter digital type,96 x 96 mm to read 0 - 500 volts aux supply 230 volts, AC, accuracy class 1.0 (iv) Digital frequency meter -01 No. Aux supply 230 volts, AC (v) Push button start, stop/ reset - 01 No
Supplying, installing, testing & commissioning of factory assembled silent Diesel Engine driven generating set 1500RPM of capacity 82.5 KVA, 3 phase, 4 wire,415 volt, 0.8 PF, complete with control panel including integrated powder coated acoustic enclosure as per CPCB regulations and duly certified by agencies/labs designated by MoEF/CPCB norms as per new guidelines of Delhi NCR at 75% load under free field conditions for noise and sound pollution level, etc floor mounted including PCC foundation as per manufacturer's instructions complete all as specified and directed and comprising of the following :- (A) DIESEL ENGINE required capacity for driving 82.5 KVA alternator multi cylinder, vertical type, 4 stroke, water cooled, electric start conforming to IS : 10001/10002/BS-5514 for continuous running capable of taking 10% overload for one hour in 12 hours complete and comprising of the following :- (i) Radiator (ii) Radiator fan with guard (iii) Flywheel with starter ring (iv) Air cleaner oil bath type (v) Vacuum indicator (vi) Electronic governor class 1A
(vii) Exhaust silencer (viii) Fuel filter & fuel hoses (ix) Fuel injection pump (FIP) (x) Fan & water pump assembly (xi) Lub oil filter & Pump (xii) Electric starting system with battery charging alternator and axial type starter motor including adequate number of high capacity maintenance free lead acid battery 1 Nos, 12 volts 150 AH DC as per manufacturers requirement including interconnecting cables/leads with terminals complete with starting/stopping switch, volt meter etc - 01 Set. (xiii) Engine safety shut down system against low lub oil pressure and high water temperaure (xiv) Exhaust gas driven turbo charger (xv) Oil filter (xvi) Lub oil cooler (xvii) All accessories as required. (B) ENGINE INSTRUMENT PANEL digital type indicating the following (i) Starting switch on/off (ii) Water temp indicator (iii) Hour meter cum RPM indicator
(iv) Lub oil pressure (v) Lub oil temperature (vi) Battery charging meter/indicator (vii) Safety alarm against high water temp and lub oil pressure (C) ALTERNATOR Shall be self excited, self regulated, brush less for 82.5 KVA continuous operation at the speed of 1500 RPM at 415 volts, 50Hz , three phase four wire system with advance electric voltage regulator to ensure high voltage accuracy with +1% with class H insulation and SPDP enclosure directly coupled with engine through flexible coupling and confirming IS- 13364 complete- 1 No. (D) Common fabricated base frame for engine & alternator made from structural channel, jerk proof PCC 1:2:4 type B1 foundation including adequate number of .suitable anti-vibration pads all as per the recommendation of the manufacture- 01 No (NOTE:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor. (E) Steel fuel tank fabricated out of 14 SWG MS sheet of capacity not less than 12 hrs continuous operation, with fuel level guage, drain plug, locking arrengements, etc with & including GI pipe connections duly laid as per engineering practice complete.
(F) AMF CONTROL PANEL Supply, fabrication, fixing commissioning and testing, factory made, floor mounted outdoor type, (Make as per OEM) cubical automatic mains failure panel suitable for 82.50 KVA DG set, fabricated using 14 guage thick CRCA sheet, powder coated painting, suitable rated bus bar, internal wiring with control MCB, provn of connecting incoming & outgoing leads/bus bas as approved with and including the following accessories as under:- (i) Master switch for auto/manual/reset/off/test- 01 No (ii) Ammeter digital type 96x96 mm to read 0 - 630 amps with CT's 1 set of 3, aux supply 230 volts, AC, accuracy class 1.0 (iii) Voltmeter digital type,96 x 96 mm to read 0 - 500 volts aux supply 230 volts, AC, accuracy class 1.0 (iv) (a) Digital frequency meter -01 No. aux supply 230 volts, AC (b) Digital Energy meter Aux supply 230 Volt AC/ 3 Phase 4 wire. (v) Push button start, stop/ reset - 01 No (vi) Set of lamp for indicating load on DG, high cylinder temperature, load on mains, set fails to start, low oil pressure (vii) Battery charger, connected to load side to charge battery from mains comprising of :-
Supplying, installing, testing & commissioning of factory assembled silent Diesel Engine driven generating set 1500RPM of capacity 40 KVA, 3 phase, 4 wire,415 volt, 0.8 PF, complete with control panel including integrated powder coated acoustic enclosure as per CPCB regulations and duly certified by agencies/labs designated by MoEF/CPCB norms as per new guidelines of Delhi NCR at 75% load under free field conditions for noise and sound pollution level, etc floor mounted including PCC foundation as per manufacturer's instructions complete all as specified and directed and comprising of the following :- (A) DIESEL ENGINE : required capacity for driving 40 KVA alternator multi cylinder, vertical type, 4 stroke, water cooled, electric start conforming to IS : 10001/10002/BS-5514 for continuous running capable of taking 10% overload for one hour in 12 hours complete and comprising of the following :- (i) Radiator (ii) Radiator fan with guard (iii) Flywheel with starter ring (iv) Air cleaner oil bath type (v) Vacuum indicator (vi) Electronic governor class 1A
(vii) Exhaust silencer (viii) Fuel filter & fuel hoses (ix) Fuel injection pump (FIP) (x) Fan & water pump assembly (xi) Lub oil filter & Pump (xii) Electric starting system with battery charging alternator and axial type starter motor including adequate number of high capacity maintenance free lead acid battery 01 No, 12 volts 180 AH DC as per manufacturers requirement including interconnecting cables/leads with terminals complete with starting/stopping switch, volt meter etc - 01 Set. (xiii) Engine safety shut down system against low lub oil pressure and high water temperaure (xiv) Exhaust gas driven turbo charger (xv) Oil filter (xvi) Lub oil cooler (xvii) All accessories as required. (B) ENGINE INSTRUMENT PANEL digital type indicating the following (i) Starting switch on/off (ii) Water temp indicator (iii) Hour meter cum RPM indicator
(iv) Lub oil pressure (v) Lub oil temperature (vi) Battery charging meter/indicator (vii) Safety alarm against high water temp and lub oil pressure (C) ALTERNATOR Shall be self excited, self regulated, brush less for 40 KVA continuous operation at the speed of 1500 RPM at 415 volts, 50Hz , three phase four wire system with advance electric voltage regulator to ensure high voltage accuracy with +1% with class H insulation and SPDP enclosure directly coupled with engine through flexible coupling and confirming IS- 13364 complete- 1 No. (D) Common fabricated base frame for engine & alternator made from structural channel, jerk proof PCC 1:2:4 type B1 foundation including adequate number of .suitable anti-vibration pads all as per the recommendation of the manufacture- 01 No (NOTE:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor. (E) Steel fuel tank fabricated out of 14 SWG MS sheet of capacity not less than 12 hrs continuous operation, with fuel level guage, drain plug, locking arrengements, etc with & including GI pipe connections duly laid as per engineering practice complete.
(F) AMF CONTROL PANEL Supply, fabrication, fixing commissioning and testing, factory made, floor mounted outdoor type, (Make as per OEM) cubical automatic mains failure panel suitable for 40 KVA DG set, fabricated using 14 guage thick CRCA sheet, powder coated painting, suitable rated bus bar, internal wiring with control MCB, provn of connecting incoming & outgoing leads/bus bas as approved with and including the following accessories as under:- (i) Master switch for auto/manual/reset/off/test- 01 No (ii) Ammeter digital type 96x96 mm to read 0 - 630 amps with CT's 1 set of 3, aux supply 230 volts, AC, accuracy class 1.0 (iii) Voltmeter digital type,96 x 96 mm to read 0 - 500 volts aux supply 230 volts, AC, accuracy class 1.0 (iv) (a) Digital frequency meter -01 No. aux supply 230 volts, AC (b) Digital Energy meter Aux supply 230 Volt AC/ 3 Phase 4 wire. (v) Push button start, stop/ reset - 01 No (vi) Set of lamp for indicating load on DG, high cylinder temperature, load on mains, set fails to start, low oil pressure
M&L Earthing with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 m below normal ground level) with top edge of earth platenot less than 1.5 m below normal ground level) connected to galvanized earth lead to GI strip 32 x 6 mm, by means of bolts, nuts, check nuts and washers of brass connected all as shown in the electrical plate No 5 of MES schedule Pt-I 1991, including necessary earth work and PCC 1:2:4 type B2 pit including charcoal & common salt in alternate layers of 150 mm thick, Protection pipe 40 mm bore GI pipe medium grade, GI pipe 20 mm dia light grade watering pipe with PGI funnel with wire mesh, cover 40 mm thick in RCC 1:2:4 with 8 mm dia TMT bar @ 75 mm centre to centre both ways, lifting handel 2 Nos of 12 mm dia MS round bar on both sides fixed in MS angle iron frame 40x40x5 mm and GI strip 32x 6mm from earth plate to test point upto 7.5m including 40mm dia protection pipe, light grade upto 7.5m length including testing point of Phosphorous bronze/gun metal of size 75x75x25 mm and connected to earthing test point including testing on completion complete.
Supplying, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with standard aluminium conductor of size 70 sqmm 3.5 core complete all as specified and directed. Note:- Excavation, earth work sand cushioning, cable protection, etc. shall be measured and paid for separately under respective items of BOQ
Do all as per item 07 above but of size 95 sqmm 3.5 core.
Do all as per item 07 above but of size 120 sqmm 3.5 core.
Do all as per item 7 above but of size 150 sqmm 3.5 core.
Do all as per item 7 above but of size 185 sqmm 3.5 core.
Do all as per item 7 above but of size 240 sqmm 3.5 core.
Do all as per item 7 above but of size 300 sqmm 3.5 core.
Dismantling old serviceable LT Cable of any size from trenches/duct and rerouting/relaying including making connection to existing/new panel complete all as specified and directed.
Excavation in trenches in hard/dense soil not exceeding 1.5 m deep and not exceeding 1.5 m width and getting out including forming bottom surface for laying cables/pipes all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm thick after the cables are laid, jointed & tested complete all as specified and directed.
Removing of surplus excavated spoil not exceeding 50 M distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified.
Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed.
Supplying & Laying Sub Class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection all as specified and directed.
Design, fabricate, supply, install, test and commissioning of factory made floor mounted LT cubical panel board Out door type (double door) made out of 3.15mm thick CRCA sheet totally enclosed with necessary ventilations, weather, dust and vermin proof with front and rear opening and locking arrangement 415Volts, 3 phase, 50 Hz having Copper bus bar of capacity 1250 Amps and full neutral duly colour coded and for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve hearing short circuit current with stand minimum 85 KA for one second complete connection from bus bar to breakers with suitable copper cable , panel board shall be grouted in the ground with suitable size of foundation in PCC 1:2:4 type B1, MS channels for base frame 50x50x6 mm and supports, GI nut, bolts, washers etc. The panel board shall be powder coated and red oxided primed with the following items :-
(A) Incoming :- (a) ACB 4P, 800A, 65KA -01 No (b) The following items are provided in one compartment :- (i) Digital Voltmeter - 01 No (ii) Digital Ameter - 01 No (iii) Three Indiaction LED Lamp (B) Out going :- (a) MCCB 4P, 400A, 35KA -01 No (b) MCCB 4 P 250 Amp, 35 KA - 01 No (c) MCCB 4 P 200 Amp, 25 KA - 01 No (d) MCCB 63 Amp, 16KA - 01 Nos (e) MCCB 4P, 630 Amps,(adjustable type) 50 KA - 01 No
Design, fabricate, supply, install, test and commissioning of factory made floor mounted LT cubical panel board Out door type (double door) made out of 3.15mm thick CRCA sheet totally enclosed with necessary ventilations, weather, dust and vermin proof with front and rear opening and locking arrangement 415Volts, 3 phase, 50 Hz having Copper bus bar of capacity 630 Amps and full neutral duly colour coded and for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve hearing short circuit current with stand minimum 85 KA for one second complete connection from bus bar to breakers with suitable copper cable , panel board shall be grouted in the ground with suitable size of foundation in PCC 1:2:4 type B1, MS channels for base frame 50x50x6 mm and supports, GI nut, bolts, washers etc. The panel board shall be powder coated and red oxided primed with the following items :- (A) Incoming :- (a) MCCB 4P, 400A, 35KA -01 No (b) The following items are provided in one compartment :- (i) Digital Voltmeter - 01 No (ii) Digital Ameter - 01 No (iii) Three Indiaction LED Lamp (B) Out going :- (a) MCCB 4P, 250A, 35KA -01 No (b) MCCB 4 P 125 Amp, 25 KA - 01 No (c) MCCB 63 Amp, 16KA - 01 Nos
S&F Earth continuity conductor or main earthing strip of size 32x6 mm of galvanised iron for fixing to Panels/DG Sets complete all as specified and directed.
M/s JAIMAA ASSOCIATES
Rahul Enterprises
mayur enterprises
Vijay Electricals
GEPS PROJECTS
national engineering
MV Engineers And Contractors
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .