Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 13 SHIVPORA SHIVPORA SRINAGAR JAMMU KASHMIR 190004 | SRINAGAR | JAMMU AND KASHMIR | 190004 | Admitted-Finance |
| 2 | Admitted-Finance PLOT NO 78 NUNEDRESHI COLONY B BEMINA BYPASS SRINAGAR SRINAGAR JAMMU KASHMIR 190018 | SRINAGAR | JAMMU AND KASHMIR | 190018 | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Rejected |
Tender Value
₹12.1 L
EMD Value
₹24,200
Closing Date
21 Feb 2024, 3:30 pmClosed
Ex. Engineer MHD, SKIMS JVC
SKIMS Soura
Repairing, replacement of PCB, Fans, Compressors, etc indoor outdoor unit of split VRV other air conditioning system in various areas and wards etc. Replacement of ductable air conditioning system by VRV VRF system at Surgical ICCU SKIMS
2024_PWDJK_244290_1
MHD, SKIMS/JVC 100 OF 2023-24 dated. 03.02.2024
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
30 days
SKIMS Soura
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Ex. Engineer Mech.and Hospital Division SKIMS JVC
₹24,200
office of Ex. Engineer MHD, SKIMS JVC
5 Mar 2024
5 Feb 2024
22 Feb 2024
5 Feb 2024
21 Feb 2024
5 Feb 2024
7 Feb 2024
Amount
Replacement of ductable Air conditioning system by way of VRV /VRF system at surgical ICCU Skims Soura by way of dismantling and extraction of existing defunct ductable AC (Outdoor and Indoor) and handing out to stores.
Supply, installation, testing & commissioning of 20 HP VRV/VRF OUTDOOR UNIT, top discharge, hot & cold type alongwith floor Standing duct type VRV INDOOR UNIT comprising of accessories like compressors sub-panel, air filters, evaporator coil, blower assembly capable of developing 50mm of WG or more static pressure, with Outdoor Units having PCD Controlled mechanism during Snowy Season, automatic control valves (sensor based), copper refrigerant piping of recommended size & thickness duly insulated with nitrile rubber (25mm thick) for liquid and vapour line of lengths as per the site requirement from indoor unit to outdoor unit. Norminal Cooling Capacity: > 55 KW. temperature range of cooling:- indoor W.B. 15.0-24.0ºC outdoor D.B.-5.0-52.0ºC Norminal Heating Capacity: > 55 KW temperature range of heating:-indoor D.B. 15.0-27ºC outdoor W.B.-20.0-15.5ºC Refrigerant piping:- Copper liquid line/gas line as per OEM Catalogue Refrigerant:- R410A/equivilent with Zero Ozone Depletion potential. Power Source:- 3phase, 4-wire, 380-400,415V 50Hz. Max. power input in cooling < 16.5KW Max. power input in Heating mode < 16.0KW COP in cooling mode > 3.50 Noise level < 65 External finish- Pre-coated galavanized steel sheets heating exchanger- Salt resistant crossfin and copper tube. The job includes puncturing of walls/beams for laying of liquid, vapour& condensate pipes along with restoration of same to original decor. The outdoor unit shall be provided with power scanner and L-shaped exhaust duct with bird screen. (composite job)
Providing & Laying Of RCC Foundation (1:2:4 mix) for Outdoor Unit as per the recommendations of OEM.
Providing and fixing of M.S stands for outdoor unit made of structural steels from angle,channels etc.
Supply, installation, testing and commissioning of 50mm PPR pipe ( Triple layer) for draining of condensed water from the evaporator coil (Brackets clips etc included).
Supply, Installation, testing and commissioning of three phase automatic voltage stabilizer of 30 KVA capacity as per ISI specification. input 300-450v, output-420v ± 5% 50 Hz
Providing and fixing of electric power cabling from main control panel to outdoor units suitable for 415v, 3 phase, 50 Hz and from main control panel to indoor units suitable for above same 3 phase supply. The control wiring shall be PVC insulated and PVC sheathed, multicore, stranded copper cable with required no. of cores.
4C x 25 mm², Copper
M/S STAR NEOTECH ENGINEERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .